Operation of Generator
HOW TO USE YOUR GENERATOR
(continued)
ELECTRIC/PULL (RECOIL) START MODELS:
4.
Using provided key, turn the ignition switch to the “ON” position. Rotate the key
one more position to the “START” position in order to engage the starting motor.
Hold key switch in the “START” position until engine starts, for NO MORE than 10
engine rotations. If the engine does NOT start, repeat procedures beginning
with Step One (1).
REMOTE START MODELS:
7.
Place the remote start switch on the control panel in the “ON” position.
CAUTION: Leaving the remote start switch in the “ON” position for more than six
hours without operation will result in a dead battery and the inability to start the
unit with the key switch or the remote start.
8.
Double-‐click and hold the “ON” button (marked with a lightening bolt) on the
remote start until the engine starts.
NOTE (all models):
If generator does not start within three pulls, check the crankcase
oil level. The engine’s “Low Oil Shutdown Protection” circuit may be activated and
preventing the engine from starting.
NOTE (all models):
Unit is equipped with an Automatic Choke.