background image

14

System Start-Up

Manual Restart after Manual Off
If Manual Restart has been selected (rather than Auto-
Restart) and someone has turned the unit off, the Output
Circuit Breaker will probably be closed.  Just press the ON
button to turn on the UPS inverter.

Auto-Restart
The factory enables this feature.  The UPS automatically
restarts and supplies power to the load after battery
depletion.  The UPS supplies power to the load as soon as
utility service is restored.
Turning the UPS OFF disables Auto-Restart until the ON
button is pressed.

Manual Restart after Low Battery Shutdown or REPO
Manual Restart (instead of Auto-Restart) opens the Output
Circuit Breaker upon battery depletion during a power
outage.  Pressing the customer-supplied REPO switch
also opens the Output Circuit Breaker.  To manually
restart the UPS, close the Output Circuit Breaker (turn it
OFF, then ON to reset breaker).  When the ”Press ON to
start system...” message appears, press the ON button.

Normal Operation

When the utility power is available and within acceptable
limits, the unit supplies filtered and regulated power to the
load through the inverter.  The battery charger maintains a
charge on the battery.
During normal operation, the LCD display informs you of
UPS status.  The display indicates when the UPS
transfers the load to or from bypass (if available), when
the load is On Battery, and when alarms or faults occur.
See the alarm chart in the Appendix for alarm message
meanings and corrective actions.

Battery Operation

On Battery
During low input voltage, the battery supplements inverter
power.  During a utility power failure, the battery provides
all power required for normal operation.  A fully charged
battery provides at least 10 minutes of output power.
More battery power is available if your system includes an
optional external battery cabinet (see Options).  Less load
increases the battery back- up time.  If your UPS supports
several computer systems, turning some of them off
allows others to run longer.  Battery Run Time curves in
the Appendix show performance of the internal battery and
external battery cabinets.
NOTE: If utility power remains off, perform an orderly
shutdown of the critical load before exhausting the battery.
If utility power returns during battery operation, normal
operation resumes and battery recharging begins.

Battery Recharge
Upon return of acceptable utility power after battery
operation, the battery charger begins to charge the
batteries.  Battery charging stops upon pressing the OFF
button four times or activating the REPO.

The battery charger compensates for battery temperature.
In addition, the charger has two recharge rates, user-
selectable through the LCD display.  The ”turbo” rate
recharges batteries to 95% capacity within 10 times the
discharge duration.  The ”standard” rate recharges
batteries to 95% capacity within 20 times the discharge
duration.  Select the ”standard” factory default setting rate
if your utility system has frequent (weekly) blackouts.
With ”turbo” mode enabled, the microprocessor
determines how often to use the fast recharge rate, in
order to optimize battery life.

Bypass Operation

The bypass provides an alternate path for power to the
critical load.  On bypass, utility power feeds directly to the
load.
Auto-Bypass
Upon overload or inverter
failure, the UPS
automatically transfers to
(and from) bypass.
During an overload, the
UPS attempts to
retransfer from bypass to
the inverter up to 15 times
within a 20-minute period.
If the overload prohibits
retransfer after 20
minutes, the unit remains
on bypass.
Manual Bypass
Manually select the
bypass power to the
critical load by operating
the bypass switch on the
back of the unit.  When
activated, the unit immediately transfers to bypass and
turns OFF the inverter, PFC, and battery charger.  The
UPS remains in bypass until the switch is moved to the
UPS position.  The user may also initiate manual bypass
via the LCD display or RS-232 remote communications.

Bypass
Switch

Содержание UPStation S

Страница 1: ...User Manual English Power Protection UPStation S ...

Страница 2: ... pursuant to Part 15 of FCC rules Operating this device in a residential area is likely to cause harmful interference to radio and TV reception which the user must correct at his own expense ADVERTISSEMENT Des pièces sous alimentation seront laissées sans protection durant ces procedures d entretien Un personnel qualifié est réquis pour effectuer ces travaux Les fusibles à c c de la batterie d acc...

Страница 3: ... de I aide médicale Lorsque I électrolyte est renversée la surface affectée devrait être nettoyée en utilisant un agent neutralisant adéquat Une pratique courante est d utiliser un mélange d approximativement une livre 500 grammes de bicarbonate de soude dans approximativement un gallon 4 litres d eau Le mélange de bicarbonate de soude devra être ajouté jusqu à ce qu il n y ait plus apparence de r...

Страница 4: ... Transferring from Maintenance Bypass Operation to UPS Operation 15 System Shutdown 15 Manual Off 15 Remote Emergency Power Off 15 UPS Alarms 15 OPTIONS 16 Distribution 16 Configurable Distribution CD 16 Load Modules 17 POWER MANAGEMENT 25 Getting Started 25 Power Management Programming Elements 26 Loads 26 Events 26 Power Management Sample 1 27 Power Management Sample 2 27 Remote Emergency Power ...

Страница 5: ...A 20 A 36 A 35 A 33 A 31 A 30 A 45 A 43 A 41 A 39 A 38 A 50 A 49 A 46 A 44 A 42 A 76 A 72 A 69 A 66 A 63 A AC Input Voltage VAC 3 Wire Ground 200 100 208 120 220 110 220 127 220 L N 230 115 240 120 240 L N 200 100 208 120 220 110 220 127 220 L N 230 115 240 120 240 L N 200 100 208 120 208 120 3 Ph 220 110 220 127 220 L N 230 115 240 120 240 L N 200 100 208 120 208 120 3 Ph 220 110 220 127 220 L N ...

Страница 6: ...mpensated battery recharge for longer battery life Programmable voltage and frequency Tower configuration with small footprint Two phase pulse width modulated PWM inverter with isolated neutral UL 1778 and CSA 22 2 listed for user safety Standard System Components Integral Battery LCD Display for comprehensive user indications and controls Audible Alarm Remote Emergency Power Off REPO capability A...

Страница 7: ...tation is phase A leads phase B See Site Planning Data and Table NEC Wire Specifications in the Appendix 3 5 6 kVA Liebert UPStation S systems include the UPS and the AC unit The unit provides connection to both utility power and UPS output power through the use of a simple Maintenance Bypass Switch See the Operation section for instructions on Maintenance Bypass Switch use Input The input power c...

Страница 8: ...hread hex nuts back onto guide pins with a 7 1 6 wrench 8 Verify the Maintenance Bypass Switch switch SW2 on the unit is in the UPS position 9 Turn off all UPS supported loads and plug them into the POD 10 Install the two battery fuses F3 and F4 The second fuse completes a circuit The spark is a normal indication 11 Roll unit to final position Allow at least one foot of rear clearance Adjust level...

Страница 9: ... AC Output 14 2 0 Ground and GEC 14 6 2 0 6 45 8 40 10 14 35 15 18 kVA Liebert UPStation S AC Input Optional Dual AC Input AC Output Optional Ext Battery Cabinet Ground and GEC 14 2 0 2 0 6 45 8 40 10 14 35 1581EBD External Battery Cabinet Input DC and Ground 14 2 0 2 0 6 120 8 40 10 14 35 NOTES 8 18 kVA systems require a local Grounding Electrode per NEC 250 Minimum size grounding conductors per ...

Страница 10: ...its The fans and LCD display activate 8 The LCD display prompts you to review and accept default settings or configure the UPS for your application See page 11 for default settings 9 After configuration automatic self tests begin If self tests are OK a horn sounds and the Close Breaker then Press ON message appears If any other message appears contact Liebert at 1 800 222 5877 10 Close turn ON Out...

Страница 11: ...cels selections It returns values to original settings and the display to the main menu The LCD panel displays messages and operating parameters It usually displays a Normal Operation screen see figure on right which includes date time and a prompt on the help line to select the Main Menu Alarms or faults displace the Normal Operation screen The user screens are organized in a multi level menu sys...

Страница 12: ...te use remote use Date Table 2 Factory Default Settings NOTE To change input or output voltage frequency or wiring push the OFF button twice Though the input is connected and the display is active there is no output to the loads after pressing OFF twice Other changes may be made during UPS operation The UPS Meters option allows review of the following UPS meters Load kVA A and B Phase Input A Phas...

Страница 13: ...T FREQUENCY 50 Hz 60 Hz LOW BATTERY WARNING TIME AUTO BATTERY TEST PARAMETERS TOTAL UPS RUNTIME ADVANCED CONFIGURATION Input Wiring Output Wiring Time Date Language Configuration Modem Mode Horn Volume Screen Contrast Battery Charging Mode Slew Rate Input Frequency Sync Range Start up Mode Set Password UPS on off Transfer UPS to Bypass Battery Installation Date Custom Relays L1 L2 N G L1 L2 G L1 N...

Страница 14: ...ack up time If your UPS supports several computer systems turning some of them off allows others to run longer Battery Run Time curves in the Appendix show performance of the internal battery and external battery cabinets NOTE If utility power remains off perform an orderly shutdown of the critical load before exhausting the battery If utility power returns during battery operation normal operatio...

Страница 15: ...sition 5 UPS display indicates Start up test warning check messages Press the right arrow button If Load on Manual Bypass appears turn the UPS ON by pressing the ON button twice 6 Wait for the UPS display to indicate Normal Operation Set unit Maintenance Bypass switch SW2 to the UPS position UPS now supplies controlled power to the loads System Shutdown Manual Off Pressing the OFF button twice rem...

Страница 16: ...erminal block allows for daisy chaining of additional distribution units Customer Output Power Management Communications Connector RIGHT SIDE Output Terminal Blocks Output Breaker TB7 TB2 L1 L2 Output Terminal Block wire range 1 14 2 AWG per connection Output Wiring Access Area Output Conduit Landing Area Input Conduit Landing Area 8 12 kVA Rear View G NOTES Weight including load modules about 100...

Страница 17: ...LES Receptacle Voltage configuration Circuit Breaker 5 15R2 120 L N G 15 A 2 Pole L5 15R1 120 L N G 15A 1 Pole L6 15R1 208 or 240 L L G 15 A 2 Pole 5 20R2 120 L N G 20 A 2 Pole L5 20R1 120 L N G 20 A 1 Pole L6 20R1 208 or 240 L L G 20A 2 Pole L14 30R1 208 120 or 240 120 L L N G 20A 2 Pole 6 15R1 208 or 240 L L G 15A 2 Pole L5 30R1 120 L N G 30 A 1 Pole L6 30R1 208 or 240 L L G 30 A 2 Pole L14 30R1...

Страница 18: ...ng handle prevents unauthorized access A holder for the User s Manual and any site documentation is provided on the inside cover of the door This enables the customer to keep all documentation relating to their UPS and maintenance bypass with the unit Auxiliary contacts rated at 15 amps and 600 volts are available if the customer requires remote monitoring of the maintenance bypass Conduit knock o...

Страница 19: ...troubleshooting purposes Maintenance When the rotary switch is placed in the Maintenance position contacts A and C are open and B is closed The power for the load is coming from the maintenance bypass source as illustrated below The UPS is now completely isolated from the source as well as the critical load UTILITY FEED CRITICAL LOAD MAINTENANCE BYPASS UPStation S BATTERIES BYPASS BYPASS INVERTER ...

Страница 20: ...ge to the unit Report any damage to the shipping carrier and complete a freight damage claim form Insure that the system ordered is what was received prior to mounting Mounting The Liebert UPStation S Maintenance Bypass Cabinet is designed for wall mount only Prior to installation verify that the wall can support the weight of the bypass cabinet Weights can be found on page 18 The dimensions requi...

Страница 21: ...ns between the maintenance bypass and the UPS must be run in separate conduit Due to the clearance requirements for service on the UPS it is recommended that flexible conduit be used UPStation S 1 Input and Output Power wiring must be run in separate conduit 2 Control and Power wiring must be run in separate conduit 3 Wire and breaker sizing must be in accordance with NEC and local electrical code...

Страница 22: ...e 1512MBC and the 1518MBC maintenance bypass have four basic connections maintenance bypass input to UPS rectifier input to UPS output and to critical load The input to the maintenance bypass comes from the utility source to the system There must be a breaker feeding the system Size the input feed breaker and wiring as per NEC The total current into the maintenance bypass should not exceed 46A for...

Страница 23: ...e between the following points in the bypass cabinet TB1 L1 to TB3 L1 TB1 L2 to TB3 L2 Return the UPS LCD to the Normal Operation screen Transfer the UPS to bypass by placing the bypass UPS switch on the back of the unit in the bypass position Again with a DVM verify that the there is no voltage difference between the following points in the bypass cabinet TB1 L1 to TB3 L1 TB1 L2 to TB3 L2 Rotate ...

Страница 24: ...sition Rotate the bypass switch on the maintenance bypass clockwise to the Test position Close the input breaker on the UPS The UPS should now be going through its normal testing and start up procedure Follow the LCD screen instructions After the output breaker is closed and the ON button is pressed the unit should return to the Normal Operation screen Proceed to the meter screen on the LCD Verify...

Страница 25: ...program step To program or review a program step box appears Power Management programs consist of four elements Which Load Module What event triggers the Load Module Whether the Load Module turns ON or OFF The time delay between the event and the Load Module reaction CAUTION A program step becomes active as soon as it is entered Therefore program the scheduled ON action for each load before progra...

Страница 26: ...es from 99 in increments of 1 Override The Override selection causes immediate action to a load module regardless of what was programmed Linked outputs are ignored during an override command These Override selections are available As Scheduled Force Power OFF Force Power ON Reboot OFF ON OFF for 30 seconds The screen displays Load X Use right or left arrow to display 1 to 8 Load Label See Load Lab...

Страница 27: ... one minute after going on battery and load 2 two minutes after going on battery When utility power returns put loads 1 and 2 back on line Define Parameters Start Loads 1 2 Action Turn OFF loads Event Utility Failed Delay 1 2 minutes Closure Loads 1 2 Action Turn ON loads Event Utility Restored Delay None Step 1A Step 1A indicates selection of load module 1 Step 1B Step 1B shed load 1 one minute a...

Страница 28: ...liminates the need for a second UPS for the agent Remotely configure the agent via BOOTP and TFTP Configuration and bootstrap are stored in non volatile memory The MIB is MIB II compliant The SNMP option ships with the MIB in DOS and TAR formats complete with a configuration cable Terminal Modem Connection All information and functions accessed through the control panel are also accessible by a te...

Страница 29: ...lay Then the message Press any key to enter terminal mode displays again Press a key to enter terminal mode and show the LCD display as described earlier in Terminal Operation If no keys are pressed for 45 seconds the UPS hangs up RS 232 with User Configurable Relays VCR232C This provides user selected contact closure output on the RS 232 board for use with remote monitoring devices The board also...

Страница 30: ...y cabinet wiring allows for cabinet location directly adjacent to the UPS module See Figures below and on the following page See Battery Time Curves in Appendix Battery CB 35A External Connectors Battery Fuse 30A Rear View Top View VBD061 3 5 6 kVA Battery Fuse 30A Battery CB 30A External Connectors Rear View VBS061 VBS062 3 5 6 kVA Battery CB 70A External Connectors Battery Fuse 70A VBD121 8 12 k...

Страница 31: ... non condensing Altitude 5000 feet without derating AC INPUT Voltage Range 176 to 264 VAC Voltage Configuration and Connection Single phase 3 wire plus ground L1 L2 N G Single phase 2 wire plus ground L1 N G Three phase 4 wire plus ground L1 L2 L3 N G 8 18 kVA only Three phase 3 wire plus ground L1 L2 L3 G 8 18 kVA only Frequency Range 45 Hz to 65 Hz Current THD 5 THD maximum at full load Power Fa...

Страница 32: ...XHHW USE Types TA TBS SA SIS THHN THHW THW 2 THWN 2 RHH RHW 2 USE 2 XHH XHHW XHHW 2 ZW 2 AWG kcmll Copper Aluminum or Copper Clad Aluminum AWG kcmll 18 14 16 18 14 20 20 25 12 25 25 30 20 20 25 12 10 30 35 40 25 30 35 10 8 40 50 55 30 40 45 8 6 55 65 75 40 50 60 6 4 70 85 95 55 65 75 4 3 85 100 110 65 75 85 3 2 95 115 130 75 90 100 2 1 110 130 150 85 100 115 1 1 0 125 150 170 100 120 135 1 0 2 0 1...

Страница 33: ... Internal Batteries 2 VBS062 Cabinets Internal Batteries 1 VBS 061 Cabinet 1 VBS062 Cabinet PERCENT LOAD 25 50 75 100 UPStation S 4 5 kVA Battery Run Times 1 Runtime mins 400 350 300 250 200 150 100 50 0 Internal Batteries 1 VBD061 Cabinet Internal Batteries 1 VBS062 Cabinet Internal Batteries 1 VBS 061 Cabinet Internal Batteries Only PERCENT LOAD 25 50 75 100 UPStation S 4 5 kVA Battery Run Times...

Страница 34: ... 2 VBS062 Cabinets Internal Batteries 1 VBS061 Cabinet 1 VBS062 Cabinet PERCENT LOAD 25 50 75 100 UPStation S 8 kVA Battery Run Times 1 Runtime mins 400 350 300 250 200 150 100 50 0 Internal Batteries 1 VBD122 and 1 VBD121 Cabinet Internal Batteries 1 VBS121 Cabinet Internal Batteries 1 VBS122 Cabinet Internal Batteries Only PERCENT LOAD 25 50 75 100 UPStation S 8 kVA Battery Run Times 2 Runtime m...

Страница 35: ... 3 VBD121 Cabinets Internal Batteries 2 VBD121 Cabinet PERCENT LOAD 25 50 75 100 UPStation S 12 kVA Battery Run Times 1 Runtime mins 240 210 180 150 120 90 60 30 0 Internal Batteries 1 VBS122 and 1 VBD121 Cabinet Internal Batteries 1 VBD121 Cabinet Internal Batteries 1 VBS122 Cabinet Internal Batteries Only PERCENT LOAD 25 50 75 100 UPStation S 12 kVA Battery Run Times 2 Runtime mins 600 525 450 3...

Страница 36: ...VBD181 Cabinets Internal Batteries 3 VBD181 Cabinets Internal Batteries 2 VBD181 Cabinet PERCENT LOAD 25 50 75 100 UPStation S 18 kVA Battery Run Times 1 Runtime mins 160 140 120 100 80 60 40 20 0 Internal Batteries 1 VBD181 Cabinet Internal Batteries Only PERCENT LOAD 25 50 75 100 UPStation S 18 kVA Battery Run Times 2 Runtime mins 400 350 300 250 200 150 100 50 0 PERCENT LOAD 25 50 75 100 Intern...

Страница 37: ... to bypass load returns to UPS power control for most temporary conditions Review and record any other alarm messages If manual transfer to bypass return to UPS power control when possible Bypass power out of tolerance Bypass out of Sync Bypass power voltage or frequency outside acceptable limits Automatic bypass transfer prohibited Manual transfer to bypass not recommended Wait for bypass power t...

Страница 38: ... 1000 kVA Integrated systems that provide both environmental and power protection in a single flexible package Monitoring and control on site or remote from systems of any size or location Service and support through more than 100 service centers around the world and a 24 hour Customer Response Center Power Protection UPStation S While every precaution has been taken to ensure accuracy and complet...

Отзывы: