background image

 

22

 

TROUBLESHOOTING GUIDE 

PROBLEM 

CAUSE 

SOLUTION 

UPS is short circuited or 
overloaded 

Ensure UPS is off.  Disconnect all loads 
and ensure nothing is lodged in output 
sockets.  Ensure loads are not defective 
or shorted internally. 

UPS fails to start 
when on button is 
pressed 

Internal fuse is blown, 
indicating internal fault 

Do not attempt to open or service the 
UPS.  Contact your dealer or LTS. 

UPS not plugged in 

UPS is operating from battery mode, 
make certain UPS is securely plugged 
into the wall socket 

UPS input protection has 
opened 

UPS is operating from battery mode.  
Save data and close applications.  
Replace UPS input fuse or reset input 
breaker, then restart UPS. 

Battery indicator is 
illuminated 

Utility voltage out of UPS 
input range. 

UPS is operating from battery mode.  
Save data and close applications.  
Ensure utility supply voltage is within 
acceptable limits for UPS. 

Batteries not fully charged 

Keep UPS plugged in continuously at 
least 24 hours to recharge batteries 

UPS is overloaded 

Check load level display and reduce load 
level 

UPS has reduced 
battery time 

Batteries may not be able to 
hold a full charge due to age 

Replace batteries.  Contact your dealer 
or LTS for replacement battery kit 

Fault and Bypass 
indicators and all load 
level LEDs are 
illuminated 

UPS overloaded or load 
equipment is faulty 

Check load level display and remove 
non-essential loads.  Recalculate load 
VA and reduce number of loads 
connected to UPS.  Check load 
equipment for faults. 

Fault and Bypass 
indicators and 
diagnostic LED A are 
illuminated 

UPS internal fan has a 
problem or UPS shutdown 
due to temperature condition.  
Load is on bypass power 

Ensure UPS is not overloaded, 
ventilation openings not blocked, or room 
ambient temperature not excessive.  
Wait 30 minutes to allow UPS to cool, 
then restart UPS.  IF it does not restart, 
contact your dealer or LTS. 

Fault and Bypass 
indicators and 
diagnostic LED B are 
illuminated 

UPS internal DC bus 
overvoltage 

UPS requires service.  Contact your 
dealer or LTS. 

Fault and Bypass 
indicators and 
diagnostic LED C are 
illuminated 

UPS power control fault. 

UPS requires service.  Contact your 
dealer or LTS. 

Fault and Bypass 
indicators and 
diagnostic LED D are 
illuminated 

UPS PFC fault. 

UPS requires service.  Contact your 
dealer or LTS. 

Fault and Bypass 
indicators and 
diagnostic LED E are 
illuminated 

UPS inverter fault. 

UPS requires service.  Contact your 
dealer or LTS. 

Fault and Bypass 
indicators and 
diagnostic LED A  & C 
are illuminated 

UPS failed the battery test. 

Replace batteries.  Contact your dealer 
or LTS. 

Fault and Bypass 
indicators and 
diagnostic LED C & E 
are illuminated 

UPS shutdown due to a 
command from the 
communications port(s) 

Your UPS has received a signal or 
command from the attached computer.  If 
this was inadvertent, ensure the 
communication cable used is correct for 
your system.  For assistance, contact 
your dealer or LTS. 

Содержание UPStation GXT

Страница 1: ...POWER PROTECTION USER MANUAL English Español R 700 3000 VA 120V UPStation GXT ...

Страница 2: ... PROPER DISPOSAL OF BATTERIES IS REQUIRED REFER TO YOUR LOCAL CODES FOR DISPOSAL REQUIREMENTS POUR LE REMPLACEMENT UTILISER LE MÉME NOMBRE ET TYPE DE BATTERIES L ÉLIMINATION DES BATTERIES EST RÉGLE MENTÉE CONSULTER LES CODES LOCAUX À CER EFFET 5 Read all safety and operating instructions before operating the UPS Adhere to all warnings on the unit and in this manual Follow all operating and user in...

Страница 3: ...e end of this section The UPStation GXT is a compact on line UPS An on line UPS continuously conditions and regulates its output voltage whether the utility power is present or not It supplies connected equipment with clean sinewave power Sensitive electronic equipment operates best from sinewave power For ease of use the UPStation GXT contains a light emitting diode LED display to indicate either...

Страница 4: ...cting this sinewave input current achieves two objectives the utility power is used as efficiently as possible by the UPS and the amount of distortion reflected on the utility is reduced This results in cleaner power being available to other devices in the building not being protected by the UPStation GXT INVERTER In normal operation the inverter utilizes the DC output of the power factor correcti...

Страница 5: ...un times for the rack tower RT models For battery run times refer to the Typical Battery Discharge Curves DYNAMIC BYPASS The UPStation GXT provides an alternate path for utility power to the connected load in the unlikely event of a UPS malfunction Should the UPS have an overload over temperature or UPS failure condition the UPS automatically transfers the connected load to bypass Bypass operation...

Страница 6: ...he 700 1000 or 1500 VA units a 20 amp device for the 2000 VA unit and a 30 amp device for the 3000 VA unit The wall receptacle must be grounded 6 Locate the UPS indoors in a controlled environment where it cannot be accidentally disconnected Locate it in an area with unrestricted air flow away from water flammable liquids gases corrosives or conductive contaminants Maintain a minimum of 4 inches 1...

Страница 7: ...nit on its right side and remove the six rubber feet with the screw driver Remove and retain screws from the two front feet NOTE The rubber feet are not used for rack mount installations 6 Locate securing flanges in the top of packing material and fasten to the UPS using the flange screws from steps 4 and 5 7 Remove display template to change the orientation of the display You may also rotate the ...

Страница 8: ...then turn on the connected load equipment The UPS is ready for normal operation OPTIONAL BATTERY CABINET S INSTALLATION Up to two optional battery cabinets may be connected to the UPS to provide additional run time Battery cabinets are designed to be placed on either side or beneath the UPS 1 Unpack the UPS battery cabinet s carefully noting the packing method Retain the box and packing material f...

Страница 9: ... the ferrite bead so that the ferrite bead s case snaps closed with the cable routed inside the ferrite bead s case SNMP Installation Attach the larger enclosed ferrite bead clamp to the network cable as shown in the drawing using the following directions Open the ferrite bead Place the network cable inside the ferrite bead grove Wrap the cable once around the bead Position the ferrite cable as cl...

Страница 10: ...Indicator Load Battery Level Indicators 700 1000 VA Mini Tower 1000 1500 VA Rack Tower 2000 VA Rack Tower 3000 VA Rack Tower 2 6 4 5 3 1 1 6 2 4 6 6 2 2 4 4 3 5 7 5 7 7 5 1 3 5 3 3 1 Output Receptacles 2 DB 9 Interface Port 3 AC Inlet 4 Intellislot Communications Port 5 Circuit Protector or fuse 6 Output Voltage Selector Switches 7 Battery Cable Connector ...

Страница 11: ...conds will result in loss of power to the output sockets and connected loads Perform all necessary shutdown procedures on connected loads before pressing this button twice Load Battery Level Indicators 4 Green 1 Amber The Load Battery Level indicators have dual functions During normal mode operation LED indicators display the approximate electrical load placed upon the UPS and during battery mode ...

Страница 12: ...ges 100 VAC both switches up 110 VAC first switch up second down 120 VAC both switches down Factory Default 127 VAC first switch down second up NOTE Setting output voltage to 100 VAC will cause UPS unit to be derated to 90 of the VA and Watt rating listed in specification section OPERATION NORMAL MODE OPERATION During normal operation utility power provides energy to the UPS The filters the power ...

Страница 13: ...eases fewer indicators remain illuminated Refer to the Troubleshooting Guide For battery run times refer to the Typical Battery Discharge Curves To increase this time turn off non essential pieces of equipment such as idle computers and monitors or add the optional external battery cabinet NOTE External battery cabinets can only be added to rack tower RT models CAUTION Turning off the UPS while in...

Страница 14: ...RING The UPStation GXT UPS has the capability of being monitored with stand alone computers network workstations network servers or UNIX hosts via the DB 9 female connector located on the rear of the UPS This capability is used in applications requiring the UPS to provide status and power monitoring information to the computer system For example during a utility power failure the information can b...

Страница 15: ... the optional internal Ethernet SNMP card Optional SiteNet SNMP Manager software is available to allow communication through several network management systems Contact your local Liebert representative dealer or reseller CAUTION TO MAINTAIN SAFETY SELV BARRIERS AND FOR ELECTROMAGNETIC COMPATABILITY SIGNAL CABLES SHOULD BE SEGREGATED AND RUN SEPARATE FROM ALL OTHER POWER CABLES WHERE APPLICABLE MAI...

Страница 16: ...bers are located at the end of this section MINI TOWER BATTERY REPLACEMENT Battery connector Battery door screws FOR 700 1000 VA MINI TOWER MODELS 1 Gently lay the UPS on its right side 2 Loosen and remove the five screws on the battery door Remove the door by sliding it toward the rear of UPS and lifting it off Lay the battery door aside for reassembly 3 Gently pull battery wiring out and disconn...

Страница 17: ...he large battery door Remove the door by pulling it forward and lifting it off Lay aside for reassembly 4 Pull battery assembly out approximately 50mm 2 in Gently pull the battery wiring out and disconnect the battery connector 5 Completely remove battery assembly from the UPS 6 Unpack the new battery assembly taking care not to destroy the packing Compare new and old battery assemblies to make su...

Страница 18: ...CEMENT Large battery door Battery connector Large battery door Screw hidden by small battery door Small battery door Two front rubber feet Front bezel cover Rear View Aerial View w top cover removed Flange screws Top cover screws ...

Страница 19: ...00RT 10 N A N A 479 554 408 343 273 20 N A N A 255 337 215 204 140 30 N A N A 150 212 125 133 78 40 N A N A 110 154 95 100 57 50 N A N A 85 116 75 77 44 60 N A N A 66 89 57 60 35 70 N A N A 56 73 48 50 30 80 N A N A 48 63 40 43 26 90 N A N A 41 53 35 36 22 100 N A N A 35 46 29 31 18 Internal Battery 2 External Battery Cabinets minutes Load 700MT 1000MT 1000RT 1000RTE 1500RT 2000RT 3000RT 10 N A N ...

Страница 20: ... holder locks into position 5 Reconnect the input power lead to the UPS and the input power lead to the input AC supply 6 Restart the UPS The UPS is ready for normal operation NOTE For 2000 VA units press the reset circuit protector button and 3000 VA units reset circuit protector AUDIBLE ALARM CONDITIONS CONDITION ALARM Battery mode utility failure One short beep every ten seconds more than two m...

Страница 21: ...s All On bypass due to output overload beep every half second A On bypass due to over temperature condition beep every 4 seconds B On bypass due to DC bus overvoltage beep every 4 seconds C On bypass due to control power supply failure beep every 4 seconds D On bypass due to PFC failure beep every 4 seconds E On bypass due to inverter failure beep every 4 seconds A C UPS failed battery test long b...

Страница 22: ...evel display and remove non essential loads Recalculate load VA and reduce number of loads connected to UPS Check load equipment for faults Fault and Bypass indicators and diagnostic LED A are illuminated UPS internal fan has a problem or UPS shutdown due to temperature condition Load is on bypass power Ensure UPS is not overloaded ventilation openings not blocked or room ambient temperature not e...

Страница 23: ... Output Receptacles 4 NEMA 5 15R 4 NEMA 5 15R Voltage 100 110 120 127 switch selectable VAC 3 Frequency 50 Hz or 60Hz Waveform Sinewave Main Mode Overload 200 for 8 cycles 130 for 10 seconds with transfer to bypass BATTERY PARAMETERS Type Valve regulated nonspillable lead acid Qty x Voltage x Rating 2 x 12V x7 or 7 2 AH 3 x 12V x 7 or 7 2 AH Batt Mfg Part CSB GP1270F2 or Panasonic LC R127R2CH1 Bac...

Страница 24: ...MA 5 15R 8 NEMA 5 15R Voltage 100 110 120 127 switch selectable VAC 3 Frequency 50 Hz or 60Hz Waveform Sinewave Main Mode Overload 200 for 8 cycles 130 for 10 seconds with transfer to bypass BATTERY PARAMETERS Type Valve regulated nonspillable lead acid Qty x Voltage x Rating 3 x 12V x 7 or 7 2 AH 6 x 12V x 7 AH Batt Mfg Part CSB GP1270F2 or Panasonic LC R127R2CH1 Back up Time See Typical Battery ...

Страница 25: ...A 5 20 plug 6 ft detached w NEMA L5 30 plug OUTPUT AC PARAMETERS Output Receptacles 8 NEMA 5 15R 6 NEMA 5 15R 2 NEMA 5 20R 6 NEMA 5 15R 1 NEMA L5 30R Voltage 100 110 120 127 switch selectable VAC 3 Frequency 50 Hz or 60Hz Waveform Sinewave Main Mode Overload 200 for 8 cycles 130 for 10 seconds with transfer to bypass BATTERY PARAMETERS Type Valve regulated nonspillable lead acid Qty x Voltage x Ra...

Страница 26: ...Str x Batt Voltage x Batt Rating 2x3x12Vx7 0 or 7 2 AH 2x4x12Vx7 0 or 7 2 AH 1x8x12Vx7 0 or 7 2 AH Batt Mfg Part CSB GP1270F2 or Panasonic LC R127R2CH1 Back up Time See Typical Battery Discharge Curves Recharge Time 5 Hours to 95 capacity after full discharge into 100 load ENVIROMENTAL Operating Temperature 32 F to 104 F 0 C to 40 C Storage Temperature 5 F to 122 F 15 C to 50 C Relative Humidity 0...

Страница 27: ... unauthorized modification alteration or repair use beyond rated capacity or improper installation maintenance application or use including without limitation use in a manner contrary to the accompanying instructions or applicable codes WARNING Warranty is void if the battery is allowed to discharge below the minimum battery cutoff point To prevent such discharge DO NOT leave the unit power switch...

Страница 28: ...rom 250 VA to more than 1000 kVA Integrated systems that provide both environmental and power protection in a single flexible package Monitoring and control on site or remote from systems of any size or location Service and support through more than 100 service centers around the world and a 24 hour Customer Response Center R 700 3000 VA 120 V UPStation GXT While every precaution has been taken to...

Отзывы: