14
3000 VA GX SPECIFICATIONS
Model Rating (VA/Watts)
3000 VA / 2100 W at 240 VAC, 2600 VA / 1820 W at 208
VAC
INPUT
Voltage
240 VAC or 208 VAC, 3-Wire plus Ground
Voltage Range
+10%, -20% (transfer to battery at –21%)
Frequency
47 to 63 Hz
Current
15 Amps (12 Amps RMS per phase)
Power Factor
Minimum .94 at Full Load
Voltage Transients
Meets Requirements of IEEE 587 Category A & B
Power Cord
6’ / 1.88 m w/NEMA L14-20 Plug (20 A)
OUTPUT
Voltage and Current
120 VAC at 25 A, 208 VAC at 12.5, 240 VAC at 12.5 A
Voltage Regulation
±3%
Frequency Locked to Utility
Selected nominal 50 or 60 Hz ± 1Hz
Output Distortion
Maximum 5 % THD with non-linear load
Waveform
Sinewave
Overload
150% Full Load Amps for 10 Cycles Max, 120 % Full Load Amps
for 1 Sec
Load Power Factor Range
0.6 Lagging pf to Unity (Rated at 0.7 pf)
Transient Response Time
100% Full Load Amps for 10 Cycles Max, 120 % Full Load Amps
for 1 Sec
Bypass Transfer
4 –6 Milliseconds
Efficiency (AC to AC)
85% at 100% Load
Receptacles
4 NEMA 5-15R (2 Duplex), 1 NEMA L6-30, 1 NEMA L12-
20
BATTERY
Backup w/1 Ext. Cabinet
10 Minutes
Backup w/2 Ext. Cabinets
25 Minutes
Backup w/3 Ext. Cabinets
50 Minutes
Battery Quantity
6 per Cabinet (1 to 3 cabinets may be connected)
Nominal Voltage
72 VDC
Battery Rating
12 V / 15 AH
Transfer Time
Uninterrupted
Battery Recharge Time
4 Hours to 90% (10 Minute Discharge Rate, 1 Cabinet)
Battery Type
Sealed, Maintenance-Free
ENVIRONMENTAL
Operating Temperature
10° to 35° C
Storing Temperature
-20° to 40° C with Battery, -35° to 50° without Battery
Relative Humidity
0 to 95% Non-Condensing
Operating Attitude
Full Rating, Up to 3,000 M – 10% Derating per 1,000 M above
3,000 M
Electromagnetic Noise
Meets FCC Part 15, Subpart J, Class A
Audible Noise
52 dBA at 1 Meter
Agency Approvals
UL 1778, CSA No. 107
PHYSICAL
Dimensions HxW*xD
7” x 17” x 21” / 177 mm x 432 mm x 534 mm
UPS Weight
49 lbs. / 22.2 kg
External Cabinet Weight
111 lbs. / 50.3 kg
Rear & Front Clearance
4” / 102 mm