1000-2100 VA GX SPECIFICATIONS 

Model Rating (VA/Watts) 

1000 VA / 700 W 

1500 VA / 1050 W 

2100 VA / 1500 W 

INPUT 
Voltage 

120 VAC, 2-Wire Plus Ground 

Voltage Range 

+10%, -20% (transfer to battery at –21%) 

Frequency 

60 Hz ±5% 

Current 

8 Amps 

12 Amps 

16 Amps 

Power Factor 

Minimum .94 at Full Load 

Voltage Transients 

Meets Requirements of IEEE 587 Category A 

Power Cord 

6’ / 1.88m w/NEMA 5-15 Plug (15 A) 

6’ / 1.88m w/NEMA 5-20 

Plug (20 A) 

OUTPUT 
Voltage and Current 

120 VAC at 8.4 A 

120 VAC at12.5 A 

120 VAC at 17.5 A 

Voltage Regulation 

±3% 

Frequency Locked to Utility 

60 Hz ±1Hz 

Output Distortion 

Maximum 5% THD with Non-Linear Load 

Waveform 

Sinewave 

Overload 

150% Full Load Amps for 10 Cycles Max, 120% Full Load Amps for 1 Sec 

Load Power Factor Range 

0.6 Lagging pf to Unity (Rated at 0.7 pf) 

Transient Response Time 

100% load step to within 90% nominal output voltage within 30 

milliseconds 

Bypass Transfer 

4 –6 Milliseconds 

Efficiency (AC to AC) 

82 % at 100% Load 

Receptacles 

4 NEMA 5-15R (2 Duplex) 

4 NEMA 5-15R (2 Duplex) 
2 NEMA 5-20R (1 Duplex) 

BATTERY 

Backup w/Int. Battery Only 

10 Minutes 

Backup w/ 1 Ext. Cabinet 

90 Minutes 

40 Minutes 

Backup w/ 2 Ext. Cabinets 

160 Minutes 

90 Minutes 

Battery Quantity 

4 per Cabinet (Int) 

8 per Cabinet (Ext)

 

6 per Cabinet 

8 per Cabinet 

Nominal Voltage 

48 VDC 

72 VDC 

96 VDC 

Battery Rating 

12 V / 7 AH, Internal Battery –12 V /15 AH, External Battery 

Transfer Time 

Uninterrupted 

Battery Recharge Time 

4 Hours to 90% (10 Minute Discharge Rate Internal Battery) 

Battery Type 

Sealed, Maintenance-Free 

ENVIRONMENTAL 
Operating Temperature 

10° to 35° C 

Storage Temperature 

-20° to 40° C (with Internal Battery) 

Relative Humidity 

0 to 95% Non-Condensing 

Operating Altitude 

Full Rating, Up to 3,000 M – 10% Derating per 1,000 M above 3,000 M 

Electromagnetic Noise 

Meets FCC Part 15, Subpart J, Class A 

Audible Noise 

45 dBA at 1 Meter 

50 dBA at 1 Meter 

Agency Approvals 

UL 1778, CSA No. 107 

PHYSICAL 
Dimensions HxW*xD 

7” x 17” x 21” / 177 mm x 432 mm x 534 mm 

UPS Weight w/Int. Battery 

71 lbs. / 32.0 kg 

83 lbs. / 37.4 kg 

97 lbs. / 43.7 kg 

External Cabinet Weight 

139 lbs. / 62.6 kg 

111 lbs. / 50.0 kg 

139 lbs. / 62.6 kg 

Rear & Front Clearance 

4” / 102 mm 

Содержание UPStation 1000 VA GX

Страница 1: ...POWER PROTECTION 1000 VA to 3000 VA UPStation GX R...

Страница 2: ...ULTER LES CODES LOCAUX 8 WARNING TO REDUCE RISK OF FIRE OR ELECTRIC SHOCK INSTALL IN A TEMPERATURE AND HUMIDITY CONTROLLED AREA FREE FROM CONDUCTIVE CONTAMINANTS 9 AVERTISSEMENT POUR REDUIRE LE RISQUE...

Страница 3: ...stable However during transmission it may be subject to load variations or accidents that cause power problems like low voltage voltage spikes or complete power failure These problems may interrupt c...

Страница 4: ...h normal charging They maintain UPS output at full rated power for 10 minutes Reducing the load increases battery back up time Bypass This standard UPStation GX feature provides an alternate power sou...

Страница 5: ...Locate UPS where it cannot be accidentally turned off in an area free of moisture flammable liquids gases or corrosives RACKMOUNT INSTALLATION 1 Turn the ON OFF switch at the front of the UPS OFF Rem...

Страница 6: ...cabinets plug the power cable of the second battery cabinet into the battery connector of the first battery cabinet UPS OPERATION Normal Mode Normally the utility supplies UPS power The UPS filters a...

Страница 7: ...e when batteries have not fully recharged If after 4 hours of recharge or in the test mode the 3 left most LEDs still flash contact Liebert Technical Support at 1 800 222 5877 and ask about replacemen...

Страница 8: ...N for normal operation after initial start up 4 Output Voltage Selector 3000VAONLY This switch on the rear of the unit allows choice of 208 or 240 VAC NOTE The output must match the input if bypass is...

Страница 9: ...DB 25 port provides several signals listed below by pin number PIN FUNCTION PIN FUNCTION 1 Reserved 14 On Inverter active low 2 RxD 15 On UPS active closed 3 TxD 16 On battery active closed 4 Not Used...

Страница 10: ...lation prolonged overloads or high temperature environments may cause overheating Immediately save work in process and correct the problem TROUBLESHOOTING If the UPS shuts down due to a fault conditio...

Страница 11: ...ate critical applications and save data Shutdown all loads and the UPS Batteries uncharged Reduced battery time Batteries unable to hold charge due to age Plug UPS in and turn ON for a minimum of 4 ho...

Страница 12: ...is manual at all times Call Liebert Technical Support at 1 800 222 5877 for battery replacement instructions Battery Safety Precautions WARNING Battery maintenance procedures expose hazardous live par...

Страница 13: ...MA 5 15R 2 Duplex 4 NEMA 5 15R 2 Duplex 2 NEMA 5 20R 1 Duplex BATTERY Backup w Int Battery Only 10 Minutes Backup w 1 Ext Cabinet 90 Minutes 40 Minutes Backup w 2 Ext Cabinets 160 Minutes 90 Minutes B...

Страница 14: ...ull Load Amps for 1 Sec Bypass Transfer 4 6 Milliseconds Efficiency AC to AC 85 at 100 Load Receptacles 4 NEMA 5 15R 2 Duplex 1 NEMA L6 30 1 NEMA L12 20 BATTERY Backup w 1 Ext Cabinet 10 Minutes Backu...

Страница 15: ...ill Liebert be responsible beyond the purchase price of the product SELLER DISCLAIMS ANY IMPLIED WARRANTY OF MERCHANTABILITY OF THE GOODS OR THE FITNESS OF THE GOODS FOR ANY INTENDED PURPOSES LIEBERT...

Страница 16: ...g and UPS with power ranges from 250 VA to more than 1000 kVA Integrated systems that provide both environmental and power protection in a single flexible package Monitoring and control on site or rem...

Отзывы: