Guide Specifications

7

3.0

G

UIDE

 S

PECIFICATIONS

3.1

General

Each condenser shall consist of housing, condenser coil, propeller fans direct-driven by individual fan 

motors, fan guards, electrical controls and mounting legs. The air-cooled condenser shall have a 

_____volt, 3-phase, _____ Hz power supply.

3.2

Coil

Liebert manufactured coil shall be constructed of copper tubes in a staggered tube pattern. Tubes are 

expanded into continuous, corrugated aluminum fins. The fins have full depth fin collars completely 

covering the copper tubes, which are connected to heavy wall Type "L" headers. Inlet coil connector 

tubes pass through relieved holes in the tube sheet for maximum resistance to piping strain and 

vibration. Coils are factory leak-tested at a minimum of 300 psig (2068kPag), dehydrated, then filled 

with a nitrogen holding charge and sealed for shipment.

3.3

Fans

Fans shall have aluminum blades secured to corrosion protected steel hubs. Fans shall be secured to 

the fan shaft by means of a heavy-duty keyed hub and dual setscrews. Fan diameter shall be 26" 

(660mm) or less. Fans shall be factory balanced and run before shipment. Fan guards shall be heavy 

gauge, close-meshed steel wire with corrosion resistant PVC finish that shall be rated to pass a 

675-hour salt spray test.

3.4

Fan Motors

The variable speed fan motor shall be an inverter duty motor with permanently lubricated ceramic 

bearings. The Liebert variable frequency drive control system shall provide overload protection for 

the variable speed motor. Each ambient-temperature-controlled fan motor shall have built-in over-

load protection. All motors shall have rain slingers, permanently lubricated bearings and shall be rig-

idly mounted on die-formed galvanized steel supports.

3.5

Head Pressure Control

The Liebert VFD Condenser control system shall include a variable frequency drive, inverter duty fan 

motor operating from 0% to 100% motor RPM based on head pressure, refrigerant pressure transduc-

ers, ambient-temperature thermostat(s), motor overload protection and electrical control circuit, fac-

tory-wired in the control panel. VFD control shall be furnished on the fan adjacent to the connection 

end of the condenser, which runs continuously with the compressors. Other condenser fans shall be 

controlled by ambient thermostats and are either On or Off. This system permits operation at temper-

atures as low as -20°F (-28.9°C).

3.6

Housing

The condenser housing shall be constructed of bright aluminum sheet and divided into individual fan 

sections by full width baffles. Structural support members, including coil support frame, motor and 

drive support, are galvanized steel for strength and corrosion resistance. Aluminum legs are provided 

with rigging holes for hoisting the unit into position.

3.7

TVSS and Unit Disconnect Switch

Transient Voltage Surge Suppression and locking disconnect shall be factory-installed and wired in 

the enclosed condenser electrical panel section.

3.8

Alarm Contacts

Normally open, dry contacts shall be provided for indication of VFD and TVSS alarm condition.

3.9

Electrical Controls

All electrical connections and controls shall be provided in a weatherproof enclosure. The enclosure 

shall be integral with the condenser for pleasing appearance as well as functional protection.

Содержание TCDV165

Страница 1: ...Precision Cooling For Business Critical Continuity Liebert VFD Condenser Model TCDV Product Information Manual 50 60Hz ...

Страница 2: ......

Страница 3: ...ontacts 7 3 9 Electrical Controls 7 FIGURES Figure 1 Liebert Model TCDV Condenser 2 fan 1 Figure 2 Major electrical control components 2 Figure 3 Cabinet and anchor dimensional data VFD control condensers 50 and 60Hz 5 Figure 4 Electrical field connections VFD control condensers 6 TABLES Table 1 Electrical data 50 and 60 Hz 2 Table 2 VFD condensers for indoor units 50 and 60Hz 2 Table 3 Condenser ...

Страница 4: ...ii ...

Страница 5: ...ing including digital scroll compressors and varying condenser capacity created by lower ambient temperatures The VFD adjusts fan speed to provide stable fan speeds and condensing temperatures Provides protection for motor overload and incoming power supply phase loss undervoltage and overvoltage Built in EMC filter Electromagnetic emission levels comply with EN61800 3 Second Envi ronment Light In...

Страница 6: ... 95 F 35 C 100 F 38 C 105 F 41 C DH VH75A N A N A TCDV165 N A N A N A DH VH114A TCDV165 TCDV165 TCDV205 N A N A N A DH VH125A TCDV165 TCDV165 TCDV205 N A N A N A DH VH199A TCDV205 TCDV308 TCDV308 N A N A N A DH VH245A TCDV308 TCDV308 TCDV415 N A N A N A DH VH290A TCDV308 TCDV415 TCDV415 N A N A N A DH VH380A TCDV415 TCDV510 N A N A N A N A DS VS028A TCDV165 TCDV165 TCDV205 TCDV205 TCDV205 TCDV251 ...

Страница 7: ...90 148 7 423 075 123 9 338 460 99 1 253 845 74 3 16 923 8 9 24 800 42 135 78 5 4 TCDV510 552 240 161 7 460 200 134 8 368 160 107 8 276 120 80 9 18 408 9 7 19 200 32 621 R 407C Refrigerant TCDV165 143 160 41 9 119 300 34 9 95 440 27 9 71 580 21 0 4772 2 5 13 300 22 597 75 5 2 TCDV205 242 100 70 9 201 750 59 1 161 400 47 3 121 050 35 4 8070 4 3 11 200 19 029 TCDV251 277 380 81 2 231 150 67 7 184 920...

Страница 8: ... 680 133 1 378 900 110 9 303 120 88 8 227 340 66 6 15 156 8 0 20 600 35 000 74 0 4 TCDV510 479 040 140 3 399 200 116 9 319 360 93 5 239 520 70 1 15 968 8 4 16 000 27 184 R 407C Refrigerant TCDV165 129 960 38 1 108 300 31 7 86640 25 4 64 980 19 0 4 332 2 3 11 100 18 859 71 0 2 TCDV205 212 280 62 2 176 900 51 8 141520 41 4 106 140 31 1 7 076 3 7 9 300 15 801 TCDV251 250 920 73 5 209 100 61 2 167280 ...

Страница 9: ...356 164 4166 82 2083 80 2032 815 370 TCDV510 4 171 1 2 4356 164 4166 82 2083 80 2032 1188 540 All condenser fan motors are 3 4 hp 1 7 8 47 6mm DPN001049 Rev 0 1 3 4 44 5mm 4 1 4 108mm 1 3 4 44 5mm 4 1 4 108mm 1 25 4mm 1 7 8 47 6mm Typical Footprint Typical Diameter 9 16 14 3mm Unit Anchor Plan 4 legs furnished for 2 and 3 fan models 6 legs furnished for 4 fan models B D C 37 11 16 957mm A 70 1778m...

Страница 10: ... electric panel Earth ground connection 60Hz Connection terminal for field supplied earth grounding wire when factory disconnect is supplied Earth ground bar optional on 50Hz only Connection terminals with factory ground from each high voltage component for field supplied earth grounding wire Factory installed fuse block on 60Hz units Circuit breaker supplied in lieu of fuse block on 50Hz units El...

Страница 11: ...ture controlled fan motor shall have built in over load protection All motors shall have rain slingers permanently lubricated bearings and shall be rig idly mounted on die formed galvanized steel supports 3 5 Head Pressure Control The Liebert VFD Condenser control system shall include a variable frequency drive inverter duty fan motor operating from 0 to 100 motor RPM based on head pressure refrig...

Страница 12: ...mes referred to are trademarks or registered trademarks of their respective owners Technical Support Service Web Site www liebert com Monitoring 800 222 5877 monitoring emersonnetworkpower com Outside the US 614 841 6755 Single Phase UPS 800 222 5877 upstech emersonnetworkpower com Outside the US 614 841 6755 Three Phase UPS 800 543 2378 powertech emersonnetworkpower com Environmental Systems 800 ...

Отзывы: