background image

Dear Customer,

Please accept our thanks for giving us the privilege to serve you by

choosing a Liebert make ‘UPS’.

If this is your first Liebert UPS, we hope it is the beginning of a long

relationship which delivers value to your organisation. If you already

own and use a Liebert product, we are doubly honoured by your decision

of continuing this relationship.

It is our constant endeavor to partner you for the growth and success of

your business. This philosophy is reflected in our Mission statement

“To deliver value through Air & Power Quality solutions to achieve

customer delight”.

 Please do give us feedback to help us realize our

Mission.

Emerson Network Power (India) Private Limited

Содержание PB Series

Страница 1: ...If you already own and use a Liebert product we are doubly honoured by your decision of continuing this relationship It is our constant endeavor to partner you for the growth and success of your business This philosophy is reflected in our Mission statement To deliver value through Air Power Quality solutions to achieve customer delight Please do give us feedback to help us realize our Mission Eme...

Страница 2: ...assistance from Emerson Network Power India Pvt Ltd Sales Office from whom the equipment was purchased Alternatively contact the Emerson Network Power India Pvt Ltd Customer Service Support department at the address shown below EMERSONNETWORKPOWER INDIA PRIVATELIMITED Plot No C 20 Road No 19 Wagle Industrial Estate Thane 400 604 INDIA Phone 00 91 22 5807000 5828405 Fax 00 91 22 5800829 5828358 Eme...

Страница 3: ...5781071 5744774 5757601 Pager 9632 100 300 KOLKATA 77 A Raja Basant Roy Road KOLKATA 700 029 Tel 033 4646387 4647197 Fax 033 4667172 BANGALORE 15 17 19 Sri Lakshmi Complex 3rd floor St Mark s Road BANGALORE 560 001 Tel 080 55994543 5598825 5581448 Pager 080 96239888000 Fax 080 558 8546 EMERSON NETWORK POWER INDIA PRIVATE LIMITED Plot No C 20 Road No 19 Wagle Industrial Estate Thane 400 604 INDIA P...

Страница 4: ...o 0832 220 723 GUWAHATI South Savania Ashram Road Ulubari GUWAHATI 781 007 Tel 0361 543848 Fax 0361 543270 Mobile 9864023587 BRANCH OFFICES JAMSHEDPUR Kashi Kunj Road No 2 Gr Floor Contractor s area Bistupur JAMSHEDPUR 831 001 Tel 0657 437549 Fax 0657 437549 LUCKNOW 206 Sriram Tower Ashok Marg LUCKNOW Phone 0522 201467 Pager 9628 555091 Mobile 9839025563 NAGPUR 203 Ganga Apts 13 Giripeth NAGPUR 40...

Страница 5: ...Powerbank Online UPS PB Series 3kVA 6kVA UserManual EMERSON NETWORK POWER INDIA PRIVATE LIMITED ...

Страница 6: ... SAFETY 6 INSTRUCTIONS 2 INTRODUCTION 8 3 INSTALLATION 10 4 CONTROL INDICATION 13 5 OPERATING INSTRUCTIONS A DETAILED PROCEDURE 16 B STARTUP PROCEDURE 18 QUICK REFERENCE 6 TESTING THE UPS 20 7 OPERATION 21 8 MAINTENANCE 22 9 SPECIFICATION OF UPS 24 ...

Страница 7: ...alified service personnel 3 Risk of Electric shock Battery circuit is not isolated from ac input hazardous voltage may exist between battery terminals and ground Test before touching 4 Risk of electric shock Hazardous live parts inside this UPS are energized from the battery supply even when the input ac power is disconnected 5 To reduce the risk of fire replace only with same type and rating of f...

Страница 8: ...rnings and instructions marked on your UPS Do not overload the commercial ac outlet and or extension wires used with your UPS Never push objects of any kind into the UPS cabinet opening or spill liquid of any kind on your UPS Do not attempt to service the UPS yourself as there are no user serviceable components inside Refer all servicing to qualified service personal Turn off and disconnect your U...

Страница 9: ...y a load of 3000 5000 6000VA UPS from its external battery bank The UPS provides AC power protection allowing continued operating though most commercial power disturbances and an opportunity to secure data and safely shut down systems in the event of an extended outage 2 2 FEATURES OF THE UPS The UPS system is designed to provide commercial AC power protection for computers peripherals and equipme...

Страница 10: ... the UPS is 230 V single phase supply This is converted into DC power by the rectifier circuit for the inverter The inverter in turn converts this DC power into AC for the critical loads The batteries are independently charged from the input AC In the event of loss of input AC the batteries takes over and feeds the inverter The static switch serves as a dynamic bypass and connects the input bypass...

Страница 11: ...esigned to be a free standing unit and is intended to be located in a controlled environment Ensure that air flow through the openings is not hindered or obstructed Obstructing the free flow of air could cause the UPS to overheat CAUTION The UPS cabinet is not rated to support weight Never stock material or stand on the UPS Never position the UPS on its side or upside down 3 3 CONNECTING THE UPS T...

Страница 12: ...UPS to a 15 amp wall receptacle The input current requirements of the UPS exceed the current rating of the wall receptacle Connect the UPS to an utility panel whose current rating is suitable It is highly recommended that use of circuit breaker in the wiring system to gain better protection All wiring for the UPS should be done by an qualified electrical technician since high voltage may be presen...

Страница 13: ...12 L N N L U4 L N INPUT BYP OUTPUT BATTERY EXTERNAL CONNECTION APPANGMENT SHORTING LINKS FIG 1 COMMON BYPASS ARRANGEMENT L N N L U4 L N INPUT BYP OUTPUT BATTERY FIG 2 SEPARATE BYPASS ARRANGEMENT ...

Страница 14: ...F LOAD CAPACITY INDICATOR Each segment is indicating the load of 20 The red LED on the last indicates the overload on the UPS G ON OFF SWITCH After turning on the input circuit breaker and the battery breaker turning ON the ON OFF switch will cause the inverter to become ON and transfer of the load from bypass will take place Turning off the ON OFF switch will cause the load to be transferred from...

Страница 15: ...14 FHHGG FHHGG FHHGGGJHJHJKJKJIUHYGY FHHGG FHHGG FHHGGKJHJJ PS 3000 Liebert FIG 3 POWER BANK UPS SERIES 425 502 A B C D E F G AGS JHJKJK AGS JHJKJK 550 H I J K O P N M FRONT VIEW REAR VIEW ...

Страница 16: ...ER CONDUCTORS Temp Rating 65 C 104 F 75 C 167 F Wire Type TW FEPW THWE UF RE XHHW REW USE Wire Gauge AWG Allowable Current Amps 14 18 18 12 20 20 10 34 34 8 40 50 6 55 65 4 70 85 Ambient Temp C F Correction Factors above 30 86 to 35 95 0 91 0 94 above 35 95 to 40 104 0 82 0 87 Note For ambient temperature over 30 C multiply the current shown above by the appropriate correction factor to determine ...

Страница 17: ...g the UPS to the utility turn on the Input isolator on the back panel The LINE and BYPASS indicators should be lighted This indicates that the UPS is being connected to commercial AC power Turn on the battery circuit breaker This will commence the battery charging Press the on off switch on the front panel The inverter indicator will start illuminating Both BYPASS INVERTER indicator will remain ON...

Страница 18: ...batteries the main circuit breaker and the battery circuit breaker should be left in the ON position However the front panel ON OFF switch can be used as daily run standby switch Note that the output will still be connected to the bypass supply and inverter will be off STORAGE INSTRUCTIONS 1 Leave equipment connected to input power and turned on for 24 hours prior to storage 2 Turn off the main ci...

Страница 19: ...n the front panel should be ON Please check that two shorting liks BYP L U4 BYP N N4 are connected properly Otherwise the fans will not start 6 Check the DC voltage on the terminal BAT BAT above the last two terminals on the extreme right on the rear panel The reading on a DC voltmeter should be greater than or equal to 220 V DC a At this point the front panel ON OFF switch should be switched ON T...

Страница 20: ... red switch on the rear panel This is black start switch which is a push button switch This will initiate the internal circuitry of the UPS to start on batteries 4 The response seen from the UPS will be that the INVERTER LED will slowly start to glow The fans will not start at this instant Approximately 17 seconds after this operation a clicking sound of the relay will be heard The fan will start ...

Страница 21: ...ns as shown below The status of these microswitches decides the charging current for a set of battery bank A step of 1 5 A is available hence current setting of 1 5A 3A 4 5A 6 0A 7 5A is possible by setting these microswitches For example if a battery bank of 40 AH is being used the charging current will have to be set to 10 of 40 AH which is 4A Since the setting for 4 A is not available the next ...

Страница 22: ...rve power is at or near maximum If no fault indicator is lighted upon activating the UPS it is working normally If the FAULT indicator and continuous audible alarm is heard upon activating the UPS refer to the MAINTENANCE section of this manual 7 2 Powering Down the Load s and UPS CAUTION Verify the load s connected to the UPS have been powered down turned off according to their operating instruct...

Страница 23: ...follow the proper operation procedure 2 Is the input battery circuit breaker on the rear panel turned on 3 Is the voltage of the utility correct Are the input cables tightly connected to the input terminals and the utility panel Are the output cables and battery cables of the Powerbank UPS also properly connected 4 Did a power failure occur just after or before the malfunction was noted the UPS 5 ...

Страница 24: ...attery Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precaution Keep unauthorized personnel away from batteries CAUTION Do not dispose of battery in a fire The battery may explode CAUTION Do not open or mutilate the batteries Released electrolyte is harmful to the skin and eyes It may be toxic CAUTION A battery can present a risk ...

Страница 25: ...oltage Maintenance free Vdc 192 Float Charge Voltage Vdc 220 End of Discharge Voltage Vdc 170 Ripple voltage on DC with battery connected 1 RMS Voltage Volts 220 V 1 Phase Frequency Hz 50 Power rating at 0 7 power factor KVA 3kVA 5kVA 6kVA Power rating at unity power factor KW 2 1 3 5 4 2 Overload at 0 7 power factor 50 for 5 seconds Maximum non linear load permissible 100 with 3 1 Crest Factor Vo...

Страница 26: ... factor 3 5 Accoustic noise dBA 53 56 56 Operating temperature Degree C 0 to 40 Degree C Relative Humidity RH 0 to 95 RH noncondensing Storage temperature Degree C 20 to 70 Degree C Height mm 550 with castor wheel Width mm 425 Depth mm 730 Weight kgs 73 93 95 Colour Powder coated Structured moon light grey and dusky blue Cable entry From rear side bottom ...

Страница 27: ... encounter any problem with the procedures contained inthis manual you should seek immediate assistance from Emerson Network Power India Pvt Ltd Sales Office from whom the equipment was purchased Alternatively contact the Emerson Network Power India Pvt Ltd Customer Service Support department at the address shown below EMERSON NETWORK POWER INDIA PRIVATE LIMITED Plot No C 20 Road No 19 Wagle Indus...

Страница 28: ...r W MUMBAI 400 086 Tel 02205002318 5002294 5002437 Fax 022 5002415 Pager 9623 988 000 Mobile 9820030917 9820030915 NEW DELHI 18 14 WEA Pusa Lane Karol Baug NEW DELHI 110005 Tel 011 5724706 5781878 5781071 5744774 5757601 Pager 9632 100 300 KOLKATA 77 A Raja Basant Roy Road KOLKATA 700 029 Tel 033 4646387 4647197 Fax 033 4667172 BANGALORE 15 17 19 Shri Lakshmi Complex 3rd floor St Mark s Road BANGL...

Страница 29: ...oad 203 Ganga Apts T Nagar CHENNAI 600 017 13 Giripeth NAGPUR 400 010 Tel 044 8231742 8221063 8228996 Fax 044 8231742 Phone Fax 0712 540423 548551 COCHIN PUNE Lakshmini No 36 2684 B 6 Shri Dwarka co op Society Veluthamma House Azad Road 467 C1 Hare Krishna Mandir Path Kaloor COCHIN 682017 Model Colony Off University Road Tel 0484 341985 PUNE 411006 FAx 0484 341 986 Tel 020 5676975 5670709 GOA Fax ...

Отзывы: