Liebert GXT3-5000/6000RT208
SL-23188_REV1_08-10
6
Guide Specifications
1.4
ENVIRONMENTAL CONDITIONS
A.
Ambient Temperature
Operating:
32°F to 104°F (0°C to 40°C) for altitudes 0 to 5,000 feet (0 to 1500 meters) above sea level.
32°F to 95°F (0°C to 30°C) for altitudes 5,000 to 10,000 feet (1500 to 3000 meters) above
sea level.
Storage:
5°F to 122°F (-15°C to +50°C)
GXT3-144VBATT and GXT3-144BATKIT: 68°F (20°C) for optimum battery storage.
Battery systems should not be stored for extended periods above 77°F (25°C)
B.
Relative Humidity
Operating:
0 to 95% non-condensing.
Storage:
0 to 95% non-condensing.
C.
Altitude
10,000ft. (3,000m) max, without power derating when operated within the temperature specified in Section
1.4, Item A. Ambient temperature shall be derated by 9°F (5°C) for each additional 1600ft. (500m) above
10,000ft. (3,000m).
D.
Audible Noise
Noise generated by the UPS under normal operation shall not exceed 55dBA when measured at 3.2ft (1m)
from the surface of the UPS.
E.
Electrostatic Discharge
The UPS shall be able to withstand an electrostatic discharge compliant to EN61000-4-2, level 4, Criteria A,
without damage and shall not affect the connected load.
1.5
USER DOCUMENTATION
The specified UPS system shall be supplied with a Safety Warning Sheet. The UPS and Configuration Program
user manual shall be on an included CD. The user manual shall include installation drawings and instructions, a
functional description of the equipment with block diagrams, safety precautions, illustrations, step-by-step
operating procedures, general maintenance guidelines, troubleshooting information and product specifications.
1.6
WARRANTY
The UPS shall be warranted against defects in materials and workmanship for two (2) years. Optional one (1) and
three (3) year full coverage extended warranties shall be available from Emerson Network Power.
1.7
QUALITY ASSURANCE
1.7.1 Manufacturer
’s Qualifications
More than 30 years experience in the design, manufacture and testing of solid-state UPS systems. The
manufacturer shall be certified to ISO 9001:2008.
1.7.2 Factory Testing
Before shipment, the manufacturer shall fully and completely test the system to ensure compliance with the
specification. These tests shall include operational discharge and recharge tests on the internal battery to ensure
performance.