Specifications

25

8.0

S

PECIFICATIONS

Table 9

Liebert

®

 GXT3

 specifications

 

Model Rating, VA (W)

10,000 (9000)

Dimensions, in. (mm)

Unit, W x D x H

31.5 x 11.81 x 26.57 (800 x 300 x 675)

Shipping, W x D x H

41.8 x 16.7 x 34 (1062 x 426 x 866)

Weight, lb (kg)

Unit

308 (140)

Shipping

428 (194)

Input AC Parameters

Nominal Operating Frequency

50 or 60Hz (Factory Default = 60)

Factory Default VAC

120/208 at 120 degrees

User-Configurable VAC

120 / 208 / 220 / 240

Operating Voltage Range

Without Battery Operation

100 - 185 ±5VAC

Maximum Allowable VAC

280

Input Frequency

Without Battery Operation

 40 - 70Hz

Input Power Connection

BYP, L1, L2, GND

Output AC Parameters

Factory Default, VAC

 208

Output Connections

 Hardwire Terminal Block

 Output: (GEC, X1, X2, X3, X4, GND) Bypass: L1, L2, GND

Frequency

 50Hz or 60Hz, Nominal

Waveform

 Sinewave

Main Mode Overload

 >200% for 5 cycles; 151 - 200% for 1 second; 131-150% 10 seconds;

105 - 130% 1 minute

Battery Parameters

Type

 Valve-regulated, non-spillable, lead acid

Quantity x V

 20 x 12V

Battery Mfr. / Part #

CSB HR1234R or Panasonic UP-RW1245

Backup Time

 See 

Table 11

Recharge Time (Internal Batteries)

 3 hr. to 90% capacity after full discharge into 100% load

Bypass Protection Limits

Maximum Bypass Current

50A

Disable Bypass Operation

If input voltage exceeds ±10% of the nominal voltage

Re-Enable Bypass Operation

 If input voltage returns to within ±8% of nominal output voltage

Disable Bypass Operation

When the input frequency prevents synchronous operation

Environmental

Operating Temperature, °F (°C)

32 to 86 (0 to 30) with 0.9 pf

86 to 104 (30 to 40) with 0.8pf

Storage Temperature, °F (°C)

5 to 122 (-15 to 50)

Transportation, °F (°C)

Relative Humidity

0-95% non-condensing

Operating Elevation

Up to 3281 ft (1000m) at 80°F (27°C) without derating

Audible Noise

<55 dBA at 3.3ft (1m) from rear; <50 dBA at 3.3ft (1m) from front or sides

Agency

Safety

UL 1778, c-UL

RFI/EMI

FCC Part 15, Subpart B, Class A

Surge Immunity

IEC/EN 61000-4-5, ANSI C62.41 (for North America)

Transportation

ISTA Procedure 1B

Содержание GXT3-10000T220

Страница 1: ...More user manuals on ManualsBase com AC Power For Business Critical Continuity Liebert GXT3 10000T220 User Manual 10kVA 50 60 Hz 120 208 220V...

Страница 2: ...More user manuals on ManualsBase com...

Страница 3: ...nd Isolating Devices 8 3 4 External Electrical Connections 9 3 5 Connecting Utility and Load 9 3 6 Terminal Blocks for UPS 9 3 6 1 Input and Output Connection Requirements 10 3 7 Connecting Power Cabl...

Страница 4: ...packing 6 Figure 4 Side view 9 Figure 5 Single source input supply input and output connections 9 Figure 6 Dual source input supply input and output connections 10 Figure 7 Hardwire terminals 10 Figur...

Страница 5: ...do not electrically isolate internal parts Under no circumstances attempt to gain access internally due to the risk of electric shock or burn Do not continue to use the UPS if the front panel indicat...

Страница 6: ...3 0 Installation In emergencies e g damaged case controls or power cables penetration of liquids or for eign matter switch off the device and contact the appropriate customer service representa tive D...

Страница 7: ...nse The Liebert GXT3 series complies with the requirements of EMC Directive 2004 108 EC and the published technical standards Continued compliance requires installation in accordance with these instru...

Страница 8: ...onic equipment operates best from sinewave power The liquid crystal display is used for controlling operation of the UPS as well as monitoring its status condition alarm status and history For ease of...

Страница 9: ...wer UPS with Integrated Battery Liebert GXT3 10000T220 10000VA 90000W Battery Cabinet Liebert GXT3 240TBATTCE Control Panel Liquid Crystal Display Push Button Controls Ventilation Louvers Bypass Circu...

Страница 10: ...00T220 near its installation site 2 Unlock all the snaps securing the shipping case to the shipping pallet 3 Lift the shipping case off the UPS 4 Remove the EPE packing cushions from around the Lieber...

Страница 11: ...rea The area where the Liebert GXT3 10000T220 is to be placed must have sufficient space for installation procedures and for routine maintenance The UPS is narrow enough to pass through standard doorw...

Страница 12: ...osition output power is available immediately upon application of AC input Table 2 Connection data Description Units Liebert GXT3 10000T220 Connector size AWG mm2 6 10 Max input current Arms 56 Input...

Страница 13: ...0T220 is supplied by single phase utility connect the live phase to input L1 3 6 Terminal Blocks for UPS Figure 5 Single source input supply input and output connections WARNING Before removing electr...

Страница 14: ...e in the building grounding electrode system If the grounding electrode conductor must be protected non metallic conduit is recommended If metal conduit must be used bond both ends of the conduit to t...

Страница 15: ...iebert GXT3 10000T220 is supplied with each battery cabinet Open the breaker before making battery cable connections Plug one end of this cable into the UPS and the other end into the battery cabinet...

Страница 16: ...with separate breakers utility and bypass rectifier booster inverter and charger electronic bypass 2 position Maintenance Bypass Breaker UPS and BYPASS integrated battery Figure 9 System block diagram...

Страница 17: ...2 1 Controls and Messages Lighted LEDs UPS ON UPS is in normal online operation BYPASS Load is supplied by the utility via automatic bypass BATTERY Load is supported by the battery FAULT A problem has...

Страница 18: ...Main Setup Control Contrast Set Battery Test Alarm Control Turn UPS On Off Status Log About Version Language Tag Number UPS Address DC Start Battery Test Interval Battery Pack Audible Alarm Output Vol...

Страница 19: ...tup Menu Setting item Setting level 1 Audible alarm Disable Enable Output voltage 208 220 230 240V Battery pack 1 3 1 Battery Test interval DC start Disable Enable Tag Number 00000 99999 Language Engl...

Страница 20: ...ry Test Battery Test Report Contrast Darker Lighter Battery Test Report Test in progress Test to Low Battery Test OK Cancel Battery test Test fail Battery Test report Test stop by user Test unknown 1...

Страница 21: ...m of 4 fault events may be displayed in this window All fault displays include the nature of the fault event and the time it occurred the time is relative to the UPS operating time Display faults The...

Страница 22: ...ontrol and press the Enter key 2 Select Turn UPS On Off and press the Enter key The LCD displays Turn UPS to BYPASS 3 Press the Enter key to switch off the inverter 4 Open any external circuit breaker...

Страница 23: ...to Bypass mode 5 A single acoustic signal confirms the operation 6 Select Turn UPS On Off and press OK to place the UPS back in Normal Mode operation The UPS performs the test during Start up 4 8 2 Ba...

Страница 24: ...ient temperature of 25 C but is also dependent on the frequency and duration of utility failures The BATTERY TEST see 4 8 2 Battery Test should be run periodically 6 to 12 months to ascertain the gene...

Страница 25: ...Set 3 Remote Any Mode Shutdown can be performed using a switch connected to the pins in Set 3 and mounted at a remote location Activation of the Any Mode Shutdown will be logged as an event in the ev...

Страница 26: ...rd Liebert IntelliSlot 485 Card The Liebert IntelliSlot SNMP Card provides SNMP monitoring and control of the UPS across the network The Liebert IntelliSlot Relay Card provides dry contact relay outpu...

Страница 27: ...MultiLink software on four computers and coordinate shutdown in the event of a power failure The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom wired applications and de...

Страница 28: ...mains voltage present Have utility mains inspected by a qualified technician UPS on LED does not illuminate when utility mains voltage present acoustic alarm active at intervals Input fuse defective o...

Страница 29: ...0 seconds 105 130 1 minute Battery Parameters Type Valve regulated non spillable lead acid Quantity x V 20 x 12V Battery Mfr Part CSB HR1234R or Panasonic UP RW1245 Backup Time See Table 11 Recharge T...

Страница 30: ...able 11 Environmental Operating Temp F C 32 to 80 0 to 27 Storage Temp 5 to 104 15 to 40 Transportation Temp F C 5 to 122 15 to 50 Relative Humidity 0 95 non condensing Operating Elevation Up to 3281...

Страница 31: ...RATION To register for warranty protection Visit the Quick Links section of Liebert s Web site at http www liebert com Click on Product Warranty Registration and fill in the form If you have any quest...

Страница 32: ...change without notice Liebert is a registered trademark of Liebert Corporation All names referred to are trademarks or registered trademarks of their respective owners Technical Support Service Web Si...

Отзывы: