Appendix 3  Product Specification      39 

E1-20010329-C-1.0 

Appendix 2  Product Specification 

Capacity 10kVA 

15kVA 

20kVA 

Model GXT2-3X1 

-0100L 

GXT2-3X1 
-0150L 

GXT2-3X1 -0200L 

Input 

Input Mode 

Three-phase/four-line input 

 

rated voltage 

400 Vac( line to line) 

 

voltage range 

1. If  the Phase to neutral voltage is in the range of 176-276Vac, the UPS 
can work normally with full load; 
2. If the phase voltage is in the range of 120-176Vac, the ability of the 
UPS to supply the load will decrease linearly with the decreasing of the 
input voltage, it can work with half load when the voltage is 120Vac. 

 

 

3. Working under Phase failure condition: 
1

if   one Phase failure, the other two phases are normal, the UPS can 

supply 50 % rated  load at most; 
2

if input two phases failure, the other one phase is normal, the UPS can 

supply 25 % rated  load at most 

 Frequency 

45~55Hz 

 Power 

Factor 

0.95    At rated load and rated voltage 

Output Power 

Factor  0.7 

 Voltage  230Vac

±

3% 

 Line 

regulation 

±

 1% 

0~100% Linear Load

 

 Load 

regulation 

±

 2% 

0~100% Linear Load

 

 Voltage 

Distortion 

< 4%

0-100% Linear Load

;< 5%

0-100% nonlinear Load

 

Output 

Frequency 

In normal mode, when the Bypass frequency is in the tracking range

50Hz

±

10%, 6%, 4%, 2% and 1% optional, defailure value is 

±

4%

,the inverter Output will track Bypass frequency;when the Bypass 

frequency is beyond the limit, the inverter Output frequency is 50Hz

±

0.2%;in battery mode, the inverter Output frequency is 50Hz

±

0.2% 

 Frequency 

slew 

rate 

 1 Hz/s 

 

Inverter Overload 
Capability 

Utility or 

Battery

 

be able to withstand 105~125% rated load for 10min;then the UPS 
transfers to bypass output; 
be able to withstand 125~150% rated load for 1min,then the UPS transfers 
to bypass output; 
When Load Power> 150%,the inverter can work for longer than 
200ms,then the UPS transfers to bypass output; 

 

Bypass Overload 
Ability 

If the load current is in the range of 135%-155% rated output current,the 
UPS will be disconnected from the load after 15min; 
If the load current is more than 155% rated current,the UPS will be 
disconnected from the load after 3min

if extreme big current occurs in 

3min,the disconnection time is decided by the release time of bypass  
breaker

 

 

Crest Factor 

3:1 

Содержание GXT2 - 3X1

Страница 1: ...GXT2 3X1 Intelligent High Frequency Online UPS 10 15 20kVA USER MANUAL E1 20010329 C 1 0 Liebert Corporation...

Страница 2: ...ebert distributor or agent from whom you purchased the equipment Do not attempt to service this product yourself It contains no user serviceable parts All servicing must be referred to qualified perso...

Страница 3: ...ING This is a Class A UPS product In a domestic environment this product may cause radio interference in which case the user may be required to take additional measures Limits on use WARNING This UPS...

Страница 4: ...tallation 8 2 3 1 Important Note 8 2 3 2 Installation Procedure 10 2 4 Connection of External Batteries 13 Chapter 3 Operation 17 3 1 Operating Mode 17 3 1 1 Normal Mode 17 3 1 2 Bypass Mode 18 3 1 3...

Страница 5: ...ate Check 28 IV Function Inspection 28 Chapter 5 Troubleshooting 31 Appendix 1 LCD Panel Displays and Operation 35 1 Constitution of Display Panel 35 2 Function of display Panel 36 3 Menu Operation 39...

Страница 6: ...hown in the following table Capacity 10kVA 15kVA 20kVA Model GXT2 3X1 0100L GXT2 3X1 0150L GXT2 3X1 0200L Description Extended Battery Cabinet is required Extended Battery Cabinet is required Extended...

Страница 7: ...cture with high input power factor wide input voltage range with the following Key features UPS can operate with loss of input phases up to 2 phases Digital Signal Processing DSP Controlled Self diagn...

Страница 8: ......

Страница 9: ...the UPS to position be careful not to drop it as it is heavy 2 In the event of product damage due to transportation please notify Liebert or its authorized agent 2 2 Outline and Panel Description 2 2...

Страница 10: ...0 Figure 2 2 Front view without panel Figure 2 3 LCD display Panel Air inlet holes on Front Panel Utility Switch Bypass Switch Maintenance Switch Off Key Utility On Silence Key Fault Enter Key Bypass...

Страница 11: ...aintenance switch For switching UPS to maintenance bypass Note To be operated by trained technical Personnel only Front Panel air inlet hole for ventilation of UPS LCD Panel and Description is in Appe...

Страница 12: ...using the UPS in dusty or corrosive environment 5 Even if the UPS is shutdown there could be high voltage inside untrained personnel must not open the UPS as there may be danger of electric shock 6 In...

Страница 13: ...the correspondent terminals and secure the screw Note Please do not reverse connection of the input hot line and neutral line Because the input default configuration of system s U phase is bypass inp...

Страница 14: ...Output Neutral line Output phase line Input Neutral line Input U phase line N U V W L N Output GND Input GND Input V phase line Input W phase line L1 B_L B_N Hot standby L1 End Battery 1 Terminal Hot...

Страница 15: ...contact closure port at the rear of the UPS Follow installation procedure of OS shutdown software Liebert s multiLink for proper installation 2 4 Connection of External Batteries 1 The system needs t...

Страница 16: ...laced while UPS is ON hot swappable pay attention not to reverse battery polarity 2 5 Wire Connection for Hot Standby UPS 1 Confirm the input circuit breakers of the master UPS and slave UPS are in OF...

Страница 17: ...U phese line in Parallel Input Neutral line in Parallel Input GND in Parallel Output GND in Parallel Output phase line of Backup UPS is connected to the L terminal of Master s bypass Output neutral li...

Страница 18: ...and slave UPS must be connected separately N U V W L N B_L L1 B_N N U V W L N B_L L1 B_N Input GND Backup UPS Input W phase line in parallel Input V phase line in Parallel Input U phese line in Paral...

Страница 19: ...on the loads one by one till the generator operates stably to ensure reliable operation of the generator it is recommended that the UPS load be less than 30 of generator capacity 2 It is recommended...

Страница 20: ...charger will turn off the battery begins to discharge and supply the load through inverter When the UPS operates in Battery mode the battery indicator and inverter indicator on the LCD panel turns gr...

Страница 21: ...en as shown in Figure 3 4 Figure 3 4 Note Under ECO mode if bypass power falls out of the bypass voltage range and there is no overload the UPS will switch into inverter mode however if there is an ov...

Страница 22: ...s to run and the system begins to conduct self test After system self test the buzzer beeps twice indicating normal startup the system enters in Bypass mode the Utility indicator and bypass indicator...

Страница 23: ...as shown in Figure 3 8 Figure 3 8 3 In the event of load exceeding the rated capacity of the UPS of 105 load the buzzer will beep every 0 5 second with corresponding load percentage indication Remove...

Страница 24: ...ity voltage is normal no overload exists and the battery voltage is not lower than 240V battery test can be conducted by pressing button on the LCD panel press and hold the ON SILENCE button for 4 sec...

Страница 25: ...he system has no Utility input in Battery mode press and hold the OFF button for about 1 second then a beep is heard the UPS will have no output and the LCD screen displays UPS SHUTDOWN About 30 secon...

Страница 26: ......

Страница 27: ...y discharge time exceeding 24 hours is must be avoided When the UPS hasn t been used for a long time and the battery hasn t been charged for 3 months at specified ambient temperature or 2 months at hi...

Страница 28: ...if it is operating in Bypass mode please find out the reason for instance operator intervention overload internal fault etc 3 Is the battery discharging when the Utility is normal the battery shouldn...

Страница 29: ...operly connected Make sure that the output power line is properly connected 4 No panel display and system self test when the Utility switch is in the ON position A Utility hasn t been introduced into...

Страница 30: ...king the vent or widen the distance from the wall C Wait for 10 minutes for the UPS cools down then restart it 11 The buzzer beeps the fault indicator is on and the LCD displays OUTPUT SHORT UPS outpu...

Страница 31: ...display double row Chinese information or 4 row English information 3 The keys are On Silence key Off key scroll key and Enter key 2 Function of display Panel 1 Displaying information of LED 1 failur...

Страница 32: ...TEMPERATURE 3 alarm information According to priority from the highest to the lowest UPS SHUTDOWN AUX SUPPLY failure OUTPUT SHORT CIRCUIT INVERTER FAIL RECTIFIER FAIL OVER TEMP OVERLOAD CHARGER FAIL...

Страница 33: ...00Ah so the battery Capacity should be set up as 100Ah includes 6 Master Slave Single setup includes Master Slave Single UPS No modification of the settings 7 The master slave alternated time can only...

Страница 34: ...S is in off state pressing this key for 1 second switch on the inverter When the UPS is in alarm mode pressing this key for 1 second can silence the alarm When the UPS is on with no alarm pressing thi...

Страница 35: ...operating parameters information can be viewed when the screen displays Return to main menu press enter key to return to main menu Operating Parameters Alarm Infor Fuction Setup Present Second Alarm...

Страница 36: ...verse contrast to normal text mode Note When the equipment s address is changed the charging between 3 bit digits are done through auto shifting when no key is pressed for 3 seconds D When it is in al...

Страница 37: ...ion Mode can perform the following functions When the Utility fails the Utility failure information is provided When the battery capacity is going to be used up battery low information will be provide...

Страница 38: ...of relays alarm Signal Relay In normal state Pin 2 3 are short circuited Pin 1 2 pins are short circuited when alarm is activated failure Signal Relay In normal state Pin 5 6 are short circuited No 4...

Страница 39: ...ad e regulation 2 0 100 Linear Load Voltage Distortion 4 0 100 Linear Load 5 0 100 nonlinear Load Output Frequency In normal mode when the Bypass frequency is in the tracking range 50Hz 10 6 4 2 and 1...

Страница 40: ...Passed CCEE certification complied with EN60950 and EN50091 1 Highest Input Voltage Line Voltage 554Vac 1 hour static EMC Conduction EN55022 Class A Radiation EN55022 Class A Harmonic current THD 25 W...

Страница 41: ...Appendix 3 Product Specification 41 E1 20010329 C 1 0 Capacity 10kVA 15kVA 20kVA Model GXT2 3X1 0100L GXT2 3X1 0150L GXT2 3X1 0200L Environment Condition...

Страница 42: ...4 Accessories E1 669001 20010230 C 1 0 Appendix 3 Accessories Optional Product name Product Model Remark battery cabinet UF B0100 38 20 38Ah batteries UF B0100 65 20 65Ah batteries UF B0100 100 20 100...

Отзывы: