Specifications
46
Table 10
Optional output distribution specifications—PD-102
Model Number
PD-102
DIMENSIONS, W x D x H
Shipping, in. (mm)
8.86 x 10.43 x 7.87 (225 x 265 x 200)
WEIGHT lb (kg)
Unit
4.6 (2.1)
Shipping
6.0 (2.7)
ELECTRICAL SPECIFICATIONS
Amp Rating
60 Amps
Input Power Connections
Internal Anderson connectors
Output Power Connection
L1-L2-G
(4) L6-20R on a 300mm cord
L1-N-G
(2) 5-15/20R, T-type, receptacles with (1) 20A circuit breaker
L2-N-G
(2) 5-15/20R, T-type, receptacles with (1) 20A circuit breaker
Table 11
External battery cabinet specifications
Model Number
GXT2-288RTVBATT
Used w/ UPS Model
GXT2-10000RT208
DIMENSIONS, Rack Mount, W x D x H
Unit (with bezel), in (mm)
16.93 x 25.98 x 7 (430 x 660 x 178); 4U
Shipping, in (mm)
22.64 x 33.46 x 12.40 (575 x 850 x 315)
WEIGHT lb (kg)
Unit
41.6 (18.9)
Shipping
50.6 (23)
BATTERY PARAMETERS
Type
Valve-regulated, non-spillable, flame retardant, lead acid
Qty x V x Rating
(2) x 12 x 12V x 9.0 AH
Battery Manufacturer / Part #
Yuasa / REW 45-12 FR
Back-Up Time
See
Table 6 - Battery run times
ENVIRONMENTAL
Operating Temp
+32°F to +104°F (0°C to +40°C)
Storage Temp
+5°F to +122°F (-15°C to +50°C)
Relative Humidity
0% to 95%, non-condensing
Operating Elevation
Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
Storage Elevation
50,000 ft. (15,000m) maximum
AGENCY
Safety
UL 1778, c-UL Listed (Suitable for computer room applications)
RFI/EMI
FCC Part 15, Subpart B, Class A
Transportation
ISTA Procedure 1A
Содержание GXT2-10000RT208