3. Operating Instruction 

3-1. Button operation 

    Button View 

Button 

Function   

ON/MUTE Button   

  Turn on the UPS: Press and hold ON/MUTE button for at least 2 

seconds to turn on the UPS. 

  Mute the alarm: When the UPS is on battery mode, press and hold this 

button for at least 5 seconds to disable or enable the alarm system. But 
it’s not applied to the situations when warnings or errors occur.   

  Down key: Press this button to display previous selection in UPS 

setting mode. 

  Switch to UPS self-test mode: Press ON/MUTE buttons simultaneously 

for 5 seconds to enter UPS self-testing while in AC mode, ECO mode, 
or converter mode. 

OFF/ENTER 

Button   

  Turn off the UPS: Press and hold this button at least 2 seconds to turn 

off the UPS in battery mode. UPS will be in standby mode under power 
normal or transfer to Bypass mode if the Bypass enable setting by 
pressing this button.   

  Confirm selection key: Press this button to confirm selection in UPS 

setting mode.   

SELECT Button   

  Switch LCD message: Press this button to change the LCD message 

for input voltage, input frequency, battery voltage, output voltage and 
output frequency. It will return back to default display when pausing for 
10 seconds.   

  Setting mode: Press and hold this button for 5 seconds to enter UPS 

setting mode when UPS is in standby mode or bypass mode.   

  Up key: Press this button to display next selection in UPS setting mode. 

ON/MUTE + 

SELECT Button 

  Switch to bypass mode: When the main power is normal, press 

ON/MUTE and SELECT buttons simultaneously for 5 seconds. Then 
UPS will enter to bypass mode. This action will be ineffective when the 
input voltage is out of acceptable range.   

 

Содержание GHT MT+

Страница 1: ...Single Phase Online UPS Liebert GXT MT User Manual 1000 3000 VA...

Страница 2: ...ion and setup 3 2 1 Rear view 3 2 2 Setup the UPS 4 3 Operations 6 3 1 Button operation 6 3 2 LCD Panel 7 3 3 Audible Alarm 8 3 4 LCD display wordings index 8 3 5 UPS Setting 9 3 6 Operating Mode Desc...

Страница 3: ...er them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed sh...

Страница 4: ...must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Страница 5: ...tandard 1000L Long run 2000 2000L 3000 3000L 2 1 Rear View 1000 L TOWER 2000 L TOWER 3000 L TOWER 1000 L RACK 2000 L RACK 3000 L RACK 1 Programmable outlets connect to non critical loads 2 Output rece...

Страница 6: ...l devices by setting shorter backup time for non critical devices For terminal type input or outputs please follow below steps for the wiring configuration a Remove the small cover of the terminal blo...

Страница 7: ...g this initial charge period Step 7 Install software For optimal computer system protection install UPS monitoring software to fully configure UPS shutdown You may insert provided CD into CD ROM to in...

Страница 8: ...UPS in battery mode UPS will be in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm se...

Страница 9: ...section Mute operation Indicates that the UPS alarm is disabled UPS information Indicates the input and output voltage frequency battery voltage load information and internal temperature Vac input ou...

Страница 10: ...ery level and low battery voltage 3 3 Audible Alarm Battery Mode Sounding every 4 seconds Low Battery Sounding every second Overload Sounding twice every second Fault Continuously sounding Bypass Mode...

Страница 11: ...ut voltage is 208Vac 220 presents output voltage is 220Vac 230 presents output voltage is 230Vac 240 presents output voltage is 240Vac For 110 150 120 127 VAC models you may choose the following outpu...

Страница 12: ...frequency is 60Hz 04 ECO enable disable Interface Setting Parameter 2 Enable or disable ECO function You may choose the following two options ENA ECO mode enable DIS ECO mode disable 05 Bypass enable...

Страница 13: ...meter 3 Set up backup time limits for programmable outlets 0 999 setting the backup time limits in minutes from 0 999 for programmable outlets which connect to non critical devices on battery mode 00...

Страница 14: ...ll bypass voltage to output for energy saving Frequency Converter mode When input frequency is within 40 Hz to 70 Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still...

Страница 15: ...ge too low 28 Inverter soft start fail 11 x Over temperature 41 x Inverter voltage high 12 x Over load 43 3 8 Warning indicator Warning Indicator Alarm Word Icon flashing Low battery B L Sounding ever...

Страница 16: ...cted Check if all batteries are connected well Fault code is shown as 27 and the icon is lighting on LCD display and alarm is continuously sounding Battery voltage is too high or the charger is fault...

Страница 17: ...s occurred There are two possible results 1 The load is still supplied but directly from AC power via bypass 2 The load is no longer supplied by power Contact your dealer Battery backup time is shorte...

Страница 18: ...ealer Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperat...

Страница 19: ...HD Non linear Load Transfer Time AC Mode to Batt Mode Zero Inverter to Bypass 4 ms Typical Waveform Batt Mode Pure Sinewave EFFICIENCY AC Mode 85 88 Battery Mode 83 BATTERY Standard Model Battery Type...

Страница 20: ...perature range of 0 C to 45 C for UPS optimal operation For every 5 C above 45 C the UPS will derate 12 of nominal capacity at full load The highest working temperature requirement for UPS operation i...

Страница 21: ...des of the UPS for heat dissipation and easy maintenance 6 Connect To Transformer Please do NOT connect transformer to output of the UPS Otherwise it will cause UPS internal fault and force UPS to ent...

Страница 22: ...add one breaker between positive pole of battery pack and positive pole of external battery connector in UPS to prevent damage to battery packs from internal fault The required specification of breake...

Страница 23: ...21...

Отзывы: