52 Appendix 2 Technical Data Tables
Liebert.CRV Series Air Conditioner User Manual
Appendix 2 Technical Data Tables
Table 2 Electrical data of the unit (compliant with CE)
Configuration
Model
Power supply
FLA (A)
LRA (A)
Residual current
circuit breakers
I
△
n = 0.3A (400V)
Cooling
Fan + compressor
CR020
380V ~ 415V/3N/50Hz
22.3
107
40A Curve C
CR035
28.0
121
50A Curve C
C electrical heating
(dehumidification)
Fan + comp
electrical heaters
CR020
380V ~ 415V/3N/50Hz
31.0
116
50A Curve C
CR035
36.7
130
63A Curve C
C humidification
Fan + comp
humidifier
CR020
380V ~ 415V/3N/50Hz
31.0
116
50A Curve C
CR035
36.7
130
63A Curve C
Cooling
Fan
CR040
380V ~ 415V/3N/50Hz
3
3
10A Curve C
C electrical heating
Fan + electrical heaters
CR040
380V ~ 415V/3N/50Hz
11.7
11.7
20A Curve C
C Humidification
Fan + humidifier
CR040
380V ~ 415V/3N/50Hz
9.5
9.5
20A Curve C
Note:
1. Without condensate pump option.
2. The cables have to be sized in compliance with local standards and according to the type and characteristics (e.g. Amperes)
of installation
Table 3 Electrical data of components (compliant with CE)
Component
Unit power supply
Model
OA
1
(A)
FLA
2
(A)
LRA
2
(A)
Nominal
power (kW)
Fan
380V ~ 415V/3N/50Hz
CR020
2 × 1.95
2 × 3.1
2 × 0.1
2 × 0.30
CR035
2 × 0.85
2 × 1.5
2 × 0.1
2 × 0.53
CR040
2 × 1
2 × 1.5
2 × 0.1
2 × 0.63
Compressor
380V ~ 415V/3N/50Hz
CR020
11.13
16.1
101
5.99
CR035
16.70
25.0
118
9.34
Humidifier
380V ~ 415V/3N/50Hz
CR020
6.5
6.5
-
1.50
CR035
6.5
6.5
-
1.50
CR040
6.5
6.5
-
1.50
Electrical
heater
380V ~ 415V/3N/50Hz
CR020
8.7
8.7
-
6
CR035
8.7
8.7
-
6
CR040
8.7
8.7
-
6
Condensate
pump
380V ~ 415V/3N/50Hz
CR020
-
1.2
-
-
CR035
-
1.2
-
-
CR040
-
1.2
-
-
Note*:
1: At nominal operating condition: condensing temperature is 48.9°C, inlet air temperature is 37.8°C, inlet air relative humidity is
20%RH.
2: FLA: Max operating current; LRA: locked rotor Amps