Chapter 10 Maintenance & Spare Parts 41
Liebert.CRV Series Air Conditioner User Manual
Table 10-1 Maintenance schedule
Components
Maintenance period
Monthly quarterly biannual
annual
General
Check unit display for clogged-filter warning
×
Check for irregular noise from unit fans
×
Check for irregular noise from compressor
×
Check for irregular noise from remote condenser fan/s (if
applicable)
×
Filters
Check state of filters
×
Replace air filter whether necessary
×
Filter switch functionality check
×
Blowers
Verify impellers move freely
×
Check bearings
×
Check motor mounts for tightness
×
Check fan safety switch
×
Electrics/electronics
Check condition of contactors
×
Check electrical connections
×
Check operation of controller
×
Check unit operation sequence
×
Steam generating
humidifier
Check cylinder & pan
×
Check steam hoses conditions
×
Verify filling solenoid valve proper operation
×
Cooling water circuit
(W and C units)
Circuit leakage/general condition check
×
Check water(-glycol) inlet temperature
×
Check water regulating valve operation
×
Check in/out water(-glycol)
t
×
Check mixture glycol level (if applicable)
×
Refrigerating circuit
Check compressor noise/vibrations
×
Check oil level through compressor sight glass
×
Adjust/tighten compressor/functional elements
×
Check sight glass for problem detection
×
Check starting/running amps
×
Check refrigerating circuit main pressures
×
Check compressor suction superheat
×
Check discharge temperature
×
Check sub cooling
×
Air cooled
condenser/dry cooler
(if applicable)
Check fan/s bearings
×
Check fan/s motor mounts for tightness
×
Check coil condition
×
Check pipelines supports
×
Check fan/s speed controller operation
×
Water/glycol pump
(if applicable)
See relevant manual
10.4 Air Filter Check Or Substitution
Every month it’s important to check the state of air filter to maintain a good efficiency of air distribution throw the
evaporator coil.
First switch off the CRV, then open the rear panel with the key, access to the fan panel rotating the three locks with
the black key. Wait until fans are stopped (when you open the first lock, you also open a security switch that cut the
current, see Figure 10-1).