RACK-MOUNT CONVERSION DIAGRAMS

RACK-MOUNT UPS CONVERSION AND INSTALLATION
1. 
Unpack the UPS carefully noting the packing method.  Retain the box and

packing material for possible future shipment.

 

2. CAUTION:  The UPS is heavy (see specifications).  Take proper precautions

when lifting or moving it.

 

3. Visually inspect the UPS for freight damage.  Report damage to the carrier

and your dealer.

 

4. Remove the two screws located at the rear of the top cover with a Phillips

(cross head) screwdriver.  Push the top cover towards back of UPS and lift
off.  Remove and retain the two flange screws located at the front of UPS.

 

5. Gently lay unit on its right side and remove the six rubber feet with the

screwdriver.  Remove and retain screws from the two front feet.

 

NOTE:  The rubber feet are not used for rack-mount installations.

 

6. Locate securing flanges in the top of packing material and fasten to the UPS

using the flange screws from steps 4 and 5.

 

7. Remove display template to change the orientation of the display.  You may

also rotate the “Liebert UPStation GXT™” plate located at left of display
area.

 

8. NOTE:  UPS unit MUST be supported by a shelf, brackets or slide rails on

each side.  The securing flanges WILL NOT support the weight of the UPS.

 

9. For slide rail installations, securing hardware is provided with the UPS and is

located in the packing material (slide rails sold separately).  Fasten the
slides into position with the screws per the instructions included with the
slide rails.

 

10. The UPS automatically starts up in the bypass mode once the UPS is

plugged into the mains socket.  The UPS is now ready to be placed into the
equipment rack.

Содержание 700-3000 VA

Страница 1: ...USER MANUAL English Deutsch Fran ais Italiano Espa ol R 700 3000 VA 230V UPStation GXT...

Страница 2: ...ed service personnel 5 CAUTION Do not open or mutilate the batteries Released electrolyte is harmful to skin and eyes and may be toxic 6 The mains supply socket or means of isolation must be within 2...

Страница 3: ...ded cable for the external communications interface 12 Operate UPS only from a properly earthed 50 Hz or 60 Hz 208 240 VAC mains supply Models are available for 100 127 VAC supply voltages 13 Route po...

Страница 4: ...ctronic equipment operates best from sinewave power For ease of use the UPStation GXT contains a light emitting diode LED display to indicate either load percentage or battery capacity depending upon...

Страница 5: ...ting this sinewave input current achieves two objectives the mains power is used as efficiently as possible by the UPS and the amount of distortion reflected on the mains is reduced This results in cl...

Страница 6: ...ated to indicate the diagnosed problem To manually transfer the connected load from the inverter to bypass power press the Off button once NOTE The bypass power path does NOT protect the connected equ...

Страница 7: ...ins lead are colored with the following code Green and Yellow Earth Blue Neutral Brown Live As the color of the wires in the mains lead may not correspond with the colored marking identifying the term...

Страница 8: ...screws from the two front feet NOTE The rubber feet are not used for rack mount installations 6 Locate securing flanges in the top of packing material and fasten to the UPS using the flange screws fro...

Страница 9: ...arts To isolate the UPS provide an isolator that is accessible to the operator and located within two meters of the UPS The wires in the mains lead are colored with the following code Green and Yellow...

Страница 10: ...attery cabinet s are heavy see specifications Take proper precautions when lifting or moving them 3 Visually inspect the UPS for freight damage Report damage to the carrier and your dealer 4 Follow th...

Страница 11: ...the ferrite bead so that the ferrite bead s case snaps closed with the cable routed inside the ferrite bead s case SNMP Installation Attach the larger enclosed ferrite bead clamp to the network cable...

Страница 12: ...Indicator Load Battery Level Indicators 700 1000 VA Mini Tower 1000 1500 VA Rack Tower 2000 VA Rack Tower 3000 VA Rack Tower 2 6 4 5 3 1 1 6 2 4 6 6 2 2 4 4 3 5 7 7 7 3 5 3 3 1 Output Receptacles 2 DB...

Страница 13: ...nds will result in loss of power to the output sockets and connected loads Perform all necessary shutdown procedures on connected loads before pressing this button twice Load Battery Level Indicators...

Страница 14: ...powering connected loads Switch positions for voltages 208 VAC 220 VAC 230 VAC 240 VAC NOTE Setting output voltage to 208 VAC will cause UPS unit to be derated to 90 of the VA and Watt rating listed...

Страница 15: ...ses fewer indicators remain illuminated Refer to the Troubleshooting Guide For battery run times refer to the Typical Battery Discharge Curves To increase this time turn off non essential pieces of eq...

Страница 16: ...NG The UPStation GXT UPS has the capability of being monitored with stand alone computers network workstations network servers or UNIX hosts via the DB 9 female connector located on the rear of the UP...

Страница 17: ...the optional internal Ethernet SNMP card Optional SiteNet SNMP Manager software is available to allow communication through several network management systems Contact your local Liebert representative...

Страница 18: ...attery door screws FOR 700 1000 VA MINI TOWER MODELS 1 Gently lay the UPS on its right side 2 Loosen and remove the five screws on the battery door Remove the door by sliding it toward the rear of UPS...

Страница 19: ...reassembly 4 Pull battery assembly out approximately 50mm 2 in Gently pull the battery wiring out and disconnect the battery connector 5 Completely remove battery assembly from the UPS 6 Unpack the n...

Страница 20: ...EMENT Large battery door Battery connector Large battery door Screw hidden by small battery door Small battery door Two front rubber feet Front bezel cover Rear View Aerial View w top cover removed Fl...

Страница 21: ...00RT 10 N A N A 479 552 408 343 273 20 N A N A 255 335 215 204 140 30 N A N A 150 210 126 133 78 40 N A N A 110 152 95 100 57 50 N A N A 85 115 75 77 44 60 N A N A 66 88 57 60 35 70 N A N A 56 72 48 5...

Страница 22: ...ocks into position 5 Reconnect the input power lead to the UPS and the input power lead to the input AC supply 6 Restart the UPS The UPS is ready for normal operation NOTE For 1500 VA 2000 VA and 3000...

Страница 23: ...All On bypass due to output overload beep every half second A On bypass due to over temperature condition beep every 4 seconds B On bypass due to DC bus overvoltage beep every 4 seconds C On bypass d...

Страница 24: ...l display and remove non essential loads Recalculate load VA and reduce number of loads connected to UPS Check load equipment for faults Fault and Bypass indicators and diagnostic LED A are illuminate...

Страница 25: ...t Sockets 4 IEC320 10A 4 IEC320 10A Voltage 208 220 230 240 switch selectable VAC 3 Frequency 50 Hz or 60Hz Waveform Sinewave Main Mode Overload 200 for 8 cycles 130 for 10 seconds with transfer to by...

Страница 26: ...Output Sockets 4 IEC320 10A 4 IEC320 10A Voltage 208 220 230 240 switch selectable VAC 3 Frequency 50 Hz or 60Hz Waveform Sinewave Main Mode Overload 200 for 8 cycles 130 for 10 seconds with transfer...

Страница 27: ...r IEC320 10A IEC320 10A IEC320 16A OUTPUT AC PARAMETERS Output Sockets 4 IEC320 10A 4 IEC320 10A 4 IEC320 10A 1 IEC320 16A Voltage 208 220 230 240 switch selectable VAC 3 Frequency 50 Hz or 60Hz Wavef...

Страница 28: ...tr x Batt Voltage x Batt Rating 2x3x12Vx7 0 or 7 2 AH 2x4x12Vx7 0 or 7 2 AH 1x8x12Vx7 0 or 7 2 AH Batt Mfg Part CSB GP1270F2 or Panasonic LC R127R2CH1 Back up Time See Typical Battery Discharge Curves...