Liebert 1400 VA Скачать руководство пользователя страница 22

22

AUDIBLE ALARM CONDITIONS

CONDITION

ALARM

Battery mode

(utility failure)

One short beep every ten seconds;  more than two

minutes of run time remaining

Low battery

Two short beeps every five seconds; less than two

minutes of run time remaining

Battery replacement

Two second beep every minute

UPS output overload

One short beep every second

UPS fault

Continuous tone

FUSE REPLACEMENT PROCEDURES

FOR 700 VA MODELS

CAUTION:

  Before changing the supply fuse, turn off the UPS, and unplug the

input cord from the AC input power supply and from the UPS.
1.  Remove the fuse holder by inserting a flat blade screwdriver into the slot and

pulling out as indicated in the figure above.

2.  Remove the input fuse.
3.  Remove the spare fuse from its position by using the screwdriver to push it out.
4.  Place spare fuse in the input fuse position, and replace the fuse holder.  The

fuse holder will lock into position.

5.  Reconnect the input power lead to the UPS, and the input power lead to the

input AC supply.

6.  Restart the UPS.  The UPS is ready for normal operation.

NOTE:

 For 1000, 1400, and 2200 VA units press the reset circuit protector button.

Insert flat blade screw

driver into slot and pull

fuse holder out to remove

AC Inlet

Fuse Holder

Input Fuse
Spare Fuse

DISCONTINUED 

PRODUCT

Содержание 1400 VA

Страница 1: ...POWER PROTECTION USER MANUAL English 700 2200 VA 120 V PowerSure Interactive R DISCONTINUED PRODUCT...

Страница 2: ...ESQUE DE CHOC LECTRIQUE OU DE BR LURE PAR TRANSFERT D NERGIE SUIVRE LES PR CAUTIONS QUI S IMPOSENT 4 WHEN REPLACING THE BATTERIES USE THE SAME NUMBER AND TYPE OF BATTERIES PROPER DISPOSAL OF BATTERIES...

Страница 3: ...ventilation holes or other openings Maintain a clearance of four 4 inches 102 mm around the UPS for proper air flow and cooling 12 Always turn off the UPS and unplug it before starting the battery rep...

Страница 4: ...eractive contains a light emitting diode LED bar display to indicate load percentage or battery capacity depending upon the mode of operation It also provides self diagnostics a combination alarm sile...

Страница 5: ...ctuations without utilizing battery power BI DIRECTIONAL CONVERTER In normal operation the bi directional converter converts utility AC power into regulated DC power to float charge the battery system...

Страница 6: ...minimum of four 4 inches 102 mm clearance around the UPS Maintain an ambient temperature range of 32 to 104 F 0 to 40 C NOTE UPS operation in temperatures above 77 F 25 C reduces battery life 4 Ensuri...

Страница 7: ...e so that the front bezel is facing you 5 The Rackmount UPS must be supported by a shelf or rails The front bezel will not support the weight of the UPS CAUTION To increase the stability of the rack e...

Страница 8: ...cator is the second uppermost LED contained in load battery level indicators A flashing LED indicates the UPS has detected a problem An alarm sounds to alert that the UPS requires attention Refer to T...

Страница 9: ...cator Load Battery Level Indicators Alarm Silence Battery Test Button On Off Button Utility High Low Indicator Utility Battery Status Indicator 1 Output Receptacles 2 DB 9 Interface Port 3 AC Inlet 4...

Страница 10: ...ace Port 3 AC Inlet 4 Intellislot Communications Port 5 Circuit Protector or Fuse 6 Site Wiring Fault Indicator On Off Alarm Silence Load Battery Utility High Low Utility R On Off Button Alarm Silence...

Страница 11: ...voltage conditions occur the PowerSure Interactive UPS will automatically correct the utility voltage by either lowering or raising the input voltage condition The UPS will continue to correct these c...

Страница 12: ...attery mode Battery mode supports a full rated load for approximately 5 minutes before it shuts down To increase this time turn off non essential pieces of equipment such as idle computers and monitor...

Страница 13: ...nd alone computers network workstations network servers or UNIX hosts via the DB 9 female connector located on the rear of the UPS This capability is used in applications requiring the UPS to provide...

Страница 14: ...net SNMP card Optional SiteNet SNMP Manager software is available to allow communication through several network management systems Contact your local Liebert representative dealer or reseller CAUTION...

Страница 15: ...bly 4 700 1000 1400 VA models gently pull battery wiring out and disconnect the two wires one red and one black 2200 VA models pull apart connectors A and B 5 Grasp white pull tabs located on sides of...

Страница 16: ...towards connector 1000 1400 VA Model To Disconnect Gently pull wiring away To Connect Connect red wire to red terminal then black wire to black terminal by pushing upward 2200 VA Model To Disconnect...

Страница 17: ...re 2 Carefully remove the battery retaining plate by pulling it forward Lay the battery retaining plate and screws aside for reassembly 3 700 1000 1400 VA models Gently pull on the white tabs located...

Страница 18: ...18 Figure 3 Figure 5 Figure 4 Figure 1 Figure 2 Figure 6 Figure 7 DISCONTINUED PRODUCT...

Страница 19: ...fan operates intermittently as needed B UPS failed battery test D UPS shutdown due to output overload time out A B UPS shutdown due to main input relay failure output short circuit A D UPS shutdown du...

Страница 20: ...tor and diagnostic LED A are illuminated UPS fan failure or battery overcharge UPS requires service Contact your dealer or LTS Fault indicator and diagnostic LED B are illuminated UPS failed the batte...

Страница 21: ...ambient 0 25 50 75 100 0 20 40 60 80 Percent Load Run Time Mins 0 25 50 75 100 0 20 40 60 80 Percent Load Run Time Mins 0 25 50 75 100 0 20 40 60 80 Percent Load Run Time Mins 0 25 50 75 100 0 20 40...

Страница 22: ...d from the UPS 1 Remove the fuse holder by inserting a flat blade screwdriver into the slot and pulling out as indicated in the figure above 2 Remove the input fuse 3 Remove the spare fuse from its po...

Страница 23: ...ut Receptacles 4 5 15R 6 5 15R 6 5 15R 6 5 15R 2 5 20R Voltage 103 VAC to 132 VAC Max Current Rating 5 8 A 8 3 A 11 67 A 18 3 A Frequency 50 Hz or 60 Hz Waveform Sinewave Utility Mode Overload 200 for...

Страница 24: ...es 6 5 15R 6 5 15R 6 5 15R 6 5 15R 2 5 20R Voltage 103 VAC to 132 VAC Max Current Rating 5 8 A 8 3 A 11 67 A 18 3 A Frequency 50 Hz or 60 Hz Waveform Sinewave Utility Mode Overload 200 for 2 cycles 11...

Страница 25: ...25 DISCONTINUED PRODUCT...

Страница 26: ...with power ranges from 250 VA to more than 1000 kVA Integrated systems that provide both environmental and power protection in a single flexible package Monitoring and control on site or remote from s...