COMMUNICATIONS INTERFACE PORT

The PowerSure™ Interactive UPS contains a standard DB-9F recepticle located on

the rear of the UPS unit.  Several signals are provided on this port and are

assigned as follows:

PIN

ASSIGNMENT DESCRIPTION

1

Low Battery (open collector)

2

UPS TxD (typical RS-232 levels)

3

UPS RxD (typical RS-232 levels)

4

Remote Shutdown (5-12V DC, 1.0 mA. max.); battery operation

5

Common

6

No connection

7

Low Battery (open emitter)

8

Utility Fail (open emitter)

9

Utility Fail (open collector)

*Maximum voltage and current on pins 1, 7, 8, 9 is 80V DC; 10.0 mA.

UPS MONITORING

The PowerSure™ Interactive UPS has the capability of being monitored with stand

alone computers, network workstations, network servers, or UNIX hosts via the DB-

9 female connector located on the rear of the UPS.
This capability is used in applications requiring the UPS to provide status and

power monitoring information to the computer system.  For example, during a utility

power failure, the information can be used by the computer’s operating system or

application program to automatically save information in buffers, to close files, and

shut down operations prior to battery capacity depletion.
Monitoring of the UPS via a computer system is easily made with a Liebert

SiteNet® 1 shutdown kit (sold separately).  Consult your local Liebert

representative to determine the correct software kit for your application.  The kit

includes special purpose cable and shutdown software.

Collector to Emitter*

Pin  Assignment

DISCONTINUED 

PRODUCT

Содержание 1400 VA

Страница 1: ...POWER PROTECTION USER MANUAL English 700 2200 VA 120 V PowerSure Interactive R DISCONTINUED PRODUCT...

Страница 2: ...ESQUE DE CHOC LECTRIQUE OU DE BR LURE PAR TRANSFERT D NERGIE SUIVRE LES PR CAUTIONS QUI S IMPOSENT 4 WHEN REPLACING THE BATTERIES USE THE SAME NUMBER AND TYPE OF BATTERIES PROPER DISPOSAL OF BATTERIES...

Страница 3: ...ventilation holes or other openings Maintain a clearance of four 4 inches 102 mm around the UPS for proper air flow and cooling 12 Always turn off the UPS and unplug it before starting the battery rep...

Страница 4: ...eractive contains a light emitting diode LED bar display to indicate load percentage or battery capacity depending upon the mode of operation It also provides self diagnostics a combination alarm sile...

Страница 5: ...ctuations without utilizing battery power BI DIRECTIONAL CONVERTER In normal operation the bi directional converter converts utility AC power into regulated DC power to float charge the battery system...

Страница 6: ...minimum of four 4 inches 102 mm clearance around the UPS Maintain an ambient temperature range of 32 to 104 F 0 to 40 C NOTE UPS operation in temperatures above 77 F 25 C reduces battery life 4 Ensuri...

Страница 7: ...e so that the front bezel is facing you 5 The Rackmount UPS must be supported by a shelf or rails The front bezel will not support the weight of the UPS CAUTION To increase the stability of the rack e...

Страница 8: ...cator is the second uppermost LED contained in load battery level indicators A flashing LED indicates the UPS has detected a problem An alarm sounds to alert that the UPS requires attention Refer to T...

Страница 9: ...cator Load Battery Level Indicators Alarm Silence Battery Test Button On Off Button Utility High Low Indicator Utility Battery Status Indicator 1 Output Receptacles 2 DB 9 Interface Port 3 AC Inlet 4...

Страница 10: ...ace Port 3 AC Inlet 4 Intellislot Communications Port 5 Circuit Protector or Fuse 6 Site Wiring Fault Indicator On Off Alarm Silence Load Battery Utility High Low Utility R On Off Button Alarm Silence...

Страница 11: ...voltage conditions occur the PowerSure Interactive UPS will automatically correct the utility voltage by either lowering or raising the input voltage condition The UPS will continue to correct these c...

Страница 12: ...attery mode Battery mode supports a full rated load for approximately 5 minutes before it shuts down To increase this time turn off non essential pieces of equipment such as idle computers and monitor...

Страница 13: ...nd alone computers network workstations network servers or UNIX hosts via the DB 9 female connector located on the rear of the UPS This capability is used in applications requiring the UPS to provide...

Страница 14: ...net SNMP card Optional SiteNet SNMP Manager software is available to allow communication through several network management systems Contact your local Liebert representative dealer or reseller CAUTION...

Страница 15: ...bly 4 700 1000 1400 VA models gently pull battery wiring out and disconnect the two wires one red and one black 2200 VA models pull apart connectors A and B 5 Grasp white pull tabs located on sides of...

Страница 16: ...towards connector 1000 1400 VA Model To Disconnect Gently pull wiring away To Connect Connect red wire to red terminal then black wire to black terminal by pushing upward 2200 VA Model To Disconnect...

Страница 17: ...re 2 Carefully remove the battery retaining plate by pulling it forward Lay the battery retaining plate and screws aside for reassembly 3 700 1000 1400 VA models Gently pull on the white tabs located...

Страница 18: ...18 Figure 3 Figure 5 Figure 4 Figure 1 Figure 2 Figure 6 Figure 7 DISCONTINUED PRODUCT...

Страница 19: ...fan operates intermittently as needed B UPS failed battery test D UPS shutdown due to output overload time out A B UPS shutdown due to main input relay failure output short circuit A D UPS shutdown du...

Страница 20: ...tor and diagnostic LED A are illuminated UPS fan failure or battery overcharge UPS requires service Contact your dealer or LTS Fault indicator and diagnostic LED B are illuminated UPS failed the batte...

Страница 21: ...ambient 0 25 50 75 100 0 20 40 60 80 Percent Load Run Time Mins 0 25 50 75 100 0 20 40 60 80 Percent Load Run Time Mins 0 25 50 75 100 0 20 40 60 80 Percent Load Run Time Mins 0 25 50 75 100 0 20 40...

Страница 22: ...d from the UPS 1 Remove the fuse holder by inserting a flat blade screwdriver into the slot and pulling out as indicated in the figure above 2 Remove the input fuse 3 Remove the spare fuse from its po...

Страница 23: ...ut Receptacles 4 5 15R 6 5 15R 6 5 15R 6 5 15R 2 5 20R Voltage 103 VAC to 132 VAC Max Current Rating 5 8 A 8 3 A 11 67 A 18 3 A Frequency 50 Hz or 60 Hz Waveform Sinewave Utility Mode Overload 200 for...

Страница 24: ...es 6 5 15R 6 5 15R 6 5 15R 6 5 15R 2 5 20R Voltage 103 VAC to 132 VAC Max Current Rating 5 8 A 8 3 A 11 67 A 18 3 A Frequency 50 Hz or 60 Hz Waveform Sinewave Utility Mode Overload 200 for 2 cycles 11...

Страница 25: ...25 DISCONTINUED PRODUCT...

Страница 26: ...with power ranges from 250 VA to more than 1000 kVA Integrated systems that provide both environmental and power protection in a single flexible package Monitoring and control on site or remote from s...

Отзывы: