Rev. A1 (20–05–09) MFC-400/I-IAC and I-IDC Technical Manual
4
3 Configuration
Parameterization
The MFC-400/I-IAC and MFC-400/I-IDC feature 4 keys to access their functions. The
procedure to configure any parameter is as follows:
1. Press the
P
key to enter the parameters menu.
2. Enter the currently configured 4 letter password one letter at a time, using the
↑
and
↓
keys to select each letter and
P
to advance between letters. The default
password is
AAAA
.
3. Using the
↑
and
↓
keys, choose the desired parameter.
4. Press
P
to confirm the parameter’s selection.
5. Choose the desired value with the
↑
and
↓
keys.
6. Confirm pressing
P
.
By holding down the
↑
or
↓
keys it is possible to advance through the options faster.
The configuration sequence can be cancelled at any time by pressing
C
.
3.1 Parameter reset
The MFC-400/I-IAC and MFC-400/I-IDC can be reset to factory settings. This procedure
also resets its password to
AAAA
. To do so, power up the device while pressing
C
.