Important considerations

The installation of electronic devices in substations should conform with the recommen-

dations given by recent international standards. The most recent and detailed guide for

installations is IEC 61000-5-2:1997, which was based on decades of laboratory and field

research. We summarize below some of the guidelines contained in IEC 61000-5-2:1997.

For further reading, we recommend the articles and application notes available on our

web site.

a. Shielded cables must be used for connecting potentiometric sensors, current loop

outputs, RS-485 links and the auxiliary supply.

b. Cables must be segregated in trays, ducts or conduits according to their functions.

In particular, power cables must never be routed in the proximity of signal cables,

even if these are shielded. The minimum distances which must be observed are

described in IEC 61000-5-2:1997 and in articles available on-line at this product’s

web page.

c. The electrical continuity of cables, ducts, trays and conduits must be preserved up

to frequencies in the order of MHz, over all their extension, including curves and

junctions. In order to guarantee this continuity, joints and bonds should present

electrical contact along each cable, duct or tray’s transversal section. In particular,

trays should be bonded with seam-welded joints (best), U-brackets with multiple

fixings (ok) and never with wires.

d. Shielded cables should present no gaps in their screens along their lengths. 360

bond-

ing should be performed instead.

e. Should there be unshielded sections (for example, near terminal block connections),

these should be short as possible.

f.

Trays, ducts and conduits must be electrically continuous, and must be grounded

at both ends. In this configuration, trays, ducts and conduits provide shielding

and also perform as parallel earth conductors.

g. Shielded cables should also have their screens bonded at both ends. It is extremely

important that the tray, duct or conduit which contains each cable is also grounded

at both ends, allowing it to perform as a parallel earth conductor. In the absence

of a parallel earth condutor, the cable screens will be exposed to extremely high

currents which will severely compromise their operation.

h. RS-485 pairs must be terminated at both ends by 120 Ω resistors.

Содержание MFC-400/I-IAC

Страница 1: ...Current Indicator Transducer model MFC 400 I IAC and I IDC Technical Manual Licht...

Страница 2: ...n 2 2 Front panel indication 3 3 Configuration 4 3 1 Parameter reset 4 4 Programmable parameters 5 4 1 General parameters 5 4 2 Current outputs option 5 4 3 MODBUS protocol 5 4 4 DNP3 protocol option...

Страница 3: ...designed to read display and retransmit AC or DC current values They feature one isolated RS 485 port which can be used for communication using the MODBUS or DNP3 protocols Signals that enter and exi...

Страница 4: ...presented value is equal to the measured current multiplied by the Sampling Factor parameter If more than 2 inputs are used a timer automatically changes the channels on display The user may manually...

Страница 5: ...ng the and keys to select each letter and P to advance between letters The default password is AAAA 3 Using the and keys choose the desired parameter 4 Press P to confirm the parameter s selection 5 C...

Страница 6: ...MFC 400 I IAC or MFC 400 I IDC and the sampled current Parameter AC frequency Options 60 Hz 50 Hz Description input current frequency only applicable to the MFC 400 I IAC 4 2 Current outputs option P...

Страница 7: ...te Options 9600 19200 38400 57600 115200 bps Description baud rate for the RS 485 link Parameter Format Options 8N1 8E1 8O1 8N2 Description symbol transmission format where 8N1 8 data bits no parity 1...

Страница 8: ...sion avoidance a backoff scheme is implemented Before transmitting the MFC 400 always waits for the line to become idle Once that happens it waits for Tdelay Tfixed Trandom ms where Tfixed is the fixe...

Страница 9: ...t 500 g DC Input Scale specifiable Error Non linearity 0 2 0 1 10 C AC Input Scale specifiable Error Non linearity 0 5 0 1 10 C Current Output Scales 0 1 0 5 0 10 0 20 4 20 mA Error Non linearity 0 2...

Страница 10: ...Licht http www licht labs com info licht labs com Rev A1 20 05 09 MFC 400 I IAC and I IDC Technical Manual 9 B Connection diagrams...

Страница 11: ...Licht http www licht labs com info licht labs com Rev A1 20 05 09 MFC 400 I IAC and I IDC Technical Manual 10...

Страница 12: ...ays and conduits must be preserved up to frequencies in the order of MHz over all their extension including curves and junctions In order to guarantee this continuity joints and bonds should present e...

Страница 13: ...labs com Rev A1 20 05 09 MFC 400 I IAC and I IDC Technical Manual 12 i RS 485 devices must be connected in a bus topology No other network topology tree star ring etc is acceptable j Dry contact inpu...

Страница 14: ...ccessible registers considering a device with 6 input channels Not all registers may be accessible in some devices given that not all channels or relays may be installed For example a device with 4 ch...

Страница 15: ...Licht http www licht labs com info licht labs com Rev A1 20 05 09 MFC 400 I IAC and I IDC Technical Manual 14...

Отзывы: