Liberty Pumps LSG202M Скачать руководство пользователя страница 4

                            

©Copyright 2016 Liberty Pumps Inc.    All rights reserved                                                             4 

 

4. 

Control Panel:

 

 

                              Risk of Electric shock:

 This pump is supplied with a grounding conductor.  To reduce the risk of 

electric shock, be certain that it is connected only to a properly grounded earth wire.  All electrical circuitry should be 
installed in accordance all applicable national (NEC, IEC, EN, etc.) and local electrical codes and ordinances. 

 

                        

The control panel that is an integral part of this complete unit is supplied with its own separate 

Installation/Operation/Maintenance manual.  Ensure that you have received this manual, and that you read and 
understand it prior to installing this unit.  Your familiarity with the control panel manual is critical. 

A separate electrical circuit should be installed for the control circuit.   We do not recommend splitting the incoming 
pump power circuit to power the control circuit.  Connect the grinder pump leads and the float switch leads to the 
control panel in accordance with the instructions included with those units.   

5. 

Float Switches

The float switches are pre-mounted on a float bracket. The pump cycle is pre-set at the factory 

according to the depth of the basin, see chart below.  

The pump cycle can be adjusted by loosening the cord 

clamp and moving the “on” float up or down

.  We do not recommend adjustments of more than 3” in either 

direction 

– please call the factory if you need to adjust the pump cycle beyond this recommended level. 

 

6. 

Testing and Startup:

  Follow the testing and startup procedures found in the grinder pump and control panel 

manual.  For three phase models, remember to check for proper rotation.

 

4

 

QE-Series Quadplex Control Panel 

 

The Q4800 Quadplex system will include a QE-Series Quadplex control panel, properly sized for the pumps and Voltage.  
This control panel is designed to be used in multiple configurations to meet the needs of the application.  The panel is 
capable of operating up to four pumps at once, and make use of between (3) three and (6) six float switches.  The Q4800 
Package will come with six (6) float switches pre-installed at the heights shown in the table on page 5. 
 
A three-float system will have a pump(s) off switch, a lead pumps switch, and lag/alarm switch.  The off switch controls the 
water level the pumps will turn off.  The lead pumps switch will turn on two (2) of the four (4) grinder pumps, and continue 
to the run the pumps until the water level falls to the off switch level.  The lag/alarm switch will turn on the other two (2) 
grinder pumps that were not running, and trigger a high level alarm.  Jumper wires must be added to the terminal blocks in 
order to run the system with three floats.  See wiring instructions on page 6.  
 
A four-float system will have a pump(s) off switch, a lead pumps switch, a lag pumps switch, and an alarm switch.  The off 
switch controls at what water level the pumps will turn off.  The lead pumps switch will turn on two (2) of the four (4) 
grinder pumps, and continue to the run the pumps until the water level falls to the off switch level.  The lag pumps switch 
will turn on the other two (2) grinder pumps that were not running.  The alarm switch will trigger a high level alarm.  
Jumper wires must be added to the terminal blocks in order to run the system with three floats.  See wiring instructions on 
page 6.  
 
A five-float system will have a pump(s) off switch, a lead pump switch, a lag1 pump switch, a lag2 pump switch, and a 
lag3/alarm switch.  The off switch controls at what water level the pumps will turn off.  The lead pump switch will turn on 
one (1) of the four (4) grinder pumps, and continue to the run the pump until the water level falls to the off switch level.  
The lag1 pump switch will turn on a second grinder pump that was not running.  The lag2 switch will turn on a third grinder 
pump that was not running. The lag3/alarm switch will turn on the final grinder pump and trigger a high level alarm.  
Jumper wires must be added to the terminal blocks in order to run the system with three floats.  See wiring instructions on 
page 6.  
 
A six-float system will have a pump(s) off switch, a lead pump switch, a lag1 pump switch, a lag2 pump switch, a lag3 
pump switch, and an alarm switch.  The off switch controls at what water level the pumps will turn off.  The lead pump 
switch will turn on one (1) of the four (4) grinder pumps, and continue to the run the pump until the water level falls to the 
off switch level.  The lag1 pump switch will turn on a second grinder pump that was not running.  The lag2 switch will turn 
on a third grinder pump that was not running. The lag3 switch will turn on the final grinder pump.  The alarm switch will 
trigger a high level alarm.  The panel comes preset for six-float operation and no jumper wires are required.  

Содержание LSG202M

Страница 1: ...oting 7 Installation Manual 7759000A Q4800 Series Quadplex Grinder Systems 7000 Apple Tree Avenue Bergen NY 14416 Phone 800 543 2550 Fax 585 494 1839 www libertypumps com Features 48 Diameter Fibergla...

Страница 2: ...d with a grounding type plug that it is connected to a properly grounded grounding type receptacle Do not bypass grounding wires or remove ground prong from attachment plugs Do not remove cord and str...

Страница 3: ...asin to provide a solid level base that can support the weight of the filled basin If a concrete pad will be used under the basin the compacted stone sub base can be reduced to 6 inches 2 Connections...

Страница 4: ...will turn off The lead pumps switch will turn on two 2 of the four 4 grinder pumps and continue to the run the pumps until the water level falls to the off switch level The lag alarm switch will turn...

Страница 5: ...level Lag 3 level Alarm level Volume per pump cycle Total Basin capacity Q4884 13 33 cm 34 86 cm 40 102 cm 46 117 cm 52 132 cm 54 137 cm 164 5 gal 658 gal Q4896 13 33 cm 37 94 cm 43 109 cm 49 124 cm 5...

Страница 6: ...nnect terminals 6 and 8 to always operate two pumps when the lead pump is triggered Use another jumper wire to connect terminals 10 and 12 to always operate a separate pare of pumps when a lag pump is...

Страница 7: ...tly it will seal and provide a means to lift the pump without disconnecting any of the discharge piping Please ensure that installation is done as per the diagrams below DISCONNECTED POSITION PIPE GUI...

Страница 8: ...fective provided the part or assembly is returned freight prepaid to the manufacturer or its authorized service center and provided that none of the following warranty voiding characteristics are evid...

Отзывы: