Single CAC
Outdoor Unit
9. Electric Characteristics
94
Standard Inverter
Outdoor Unit
Combined Indoor Unit
Unit
Power
Comp
OFM
IFM
Model names
Model Name
No. of
Unit
Phase
Hz
Volts
Voltage
range
MCA MFA MSC
RLA
kW
FLA
kW
FLA
AUUW09GA0
[UU09W UL0]
ATNH09GRLE2
[CT09 NR2]
1
1
50
220-240
Min. : 198
Max. : 264
6.9
15
-
5.00
0.043
0.25
0.020
0.40
ABNW09GL2A2
[CB09L N22]
7.3
15
-
5.00
0.043
0.25
0.095
0.80
AVNH09GELA2
[CV09 NE2]
6.9
15
-
5.00
0.043
0.25
0.030
0.40
AQNH09GALA0
[CQ09 NA0]
7.1
15
-
5.00
0.043
0.25
0.020
0.60
AUUW12GA0
[UU12W UL0]
ATNH12GRLE2
[CT12 NR2]
7.9
15
-
5.80
0.043
0.25
0.020
0.40
ABNH12GL2A2
[CB12L N22]
8.3
15
-
5.80
0.043
0.25
0.095
0.80
AVNH12GELA2
[CV12 NE2]
7.9
15
-
5.80
0.043
0.25
0.040
0.40
AQNH12GALA0
[CQ12 NA0]
8.1
15
-
5.80
0.043
0.25
0.030
0.60
AUUW18GAE
[UU18W UE4]
ATNW18GQLA0
[CT18 NQ4]
16.2
20
-
12.40
0.085
0.33
0.040
0.40
ABNW18GM1A0
[CM18 N14]
16.2
20
-
12.40
0.085
0.33
0.080
0.40
ABNH18GL2A2
[CB18 N22]
16.6
20
-
12.40
0.085
0.33
0.120
0.80
UVNH18GJLA2
[CV18 NJ2]
16.2
20
-
12.40
0.085
0.33
0.050
0.40
AQNH18GALA0
[CQ18 NA0]
16.5
20
-
12.40
0.085
0.33
0.040
0.70
AUUW24GAE
[UU24W U44]
ATNW24GPLA0
[CT24 NP4]
22.3
30
-
17.00
0.124
0.48
0.060
0.60
ABNW24GM1A0
[CM24 N14]
22.2
30
-
17.00
0.124
0.48
0.090
0.50
ABNH24GL3A2
[CB24L N32]
22.7
30
-
17.00
0.124
0.48
0.150
1.00
UVNH24GJLA2
[CV24 NJ2]
22.3
30
-
17.00
0.124
0.48
0.060
0.60
AUUW30GAE
[UU30W U44]
ATNW30GPLA0
[UT30 NP4]
22.3
30
-
17.00
0.124
0.48
0.080
0.60
ABNW30GM1A0
[UM30 N14]
22.5
30
-
17.00
0.124
0.48
0.150
0.80
UVNH30GJLA2
[UV30 NJ2]
22.3
30
-
17.00
0.124
0.48
0.060
0.60
AJNW30GVLA0
[UJ30 NV2]
22.3
30
-
17.00
0.124
0.48
0.160
0.60
AUUW366D2
[UU36W UO2]
ATNH36GNLE2
[UT36 NN2]
22.4
40
-
16.93
0.171
0.65
0.140
0.60
ABNW36GM2A0
[UM36 N24]
23.1
40
-
16.93
0.171
0.65
0.210
1.30
UVNH36GKLA2
[UV36 NK2]
22.5
40
-
16.93
0.171
0.65
0.090
0.70
AJNW36GVLA1
[UJ36 NV3]
22.4
40
-
16.93
0.171
0.65
0.160
0.60
Note
1. Voltage supplied to the unit terminals should be within the minimum and
maximum range.
2. Maximum allowable voltage unbalance between phase is 2%.
3. MSC means the Max. current during the starting of compressor.
4. MSC and RLA are measured as the compressor only test condition.
5. OFM and IFM are measured as the outdoor unit test condition.
6. Select the wire size based on the MCA.
7. MFA is used to select the circuit breaker and ground fault circuit
interrupter, and recommended circuit breaker type is ELCB(Earth Leakage
Circuit Breaker).
MCA :
Minimum Circuit Amperes (A)
MFA :
Maximum Fuse Amperes (A)
MSC :
Maximum Starting Current
RLA :
Rated Load Amperes (A)
OFM :
Outdoor Fan Motor
IFM :
Indoor Fan Motor
kW :
Fan Motor rated output (kW)
FLA :
Full Load Amperes (A)
Содержание UU48W U32
Страница 1: ...FDF Heat Pump 50Hz 410A 5CSL0 02C Replaces 5CSL0 02B P No MFL67502810 ...
Страница 3: ...General Information Single CAC Outdoor Unit FDF 1 Model Line Up 2 Nomenclature ...
Страница 8: ...Product Data Single CAC Outdoor Unit FDF Standard Inverter Standard Inverter Synchro Compact Inverter ...
Страница 37: ...Single CAC Outdoor Unit 3 Dimensions 30 Standard Inverter AUUW 18GAE UU18W UE4 Chassis code UE ...
Страница 41: ...Single CAC Outdoor Unit 3 Dimensions 34 Standard Inverter AUUW85LAE UU85W U74 Chassis code U7 ...
Страница 50: ...43 Single CAC Outdoor Unit Standard Inverter 5 Wiring Diagrams AUUW09GA0 UU09W UL0 AUUW12GA0 UU12W UL0 ...
Страница 51: ...Single CAC Outdoor Unit 5 Wiring Diagrams 44 Standard Inverter AUUW18GAE UU18W UE4 ...
Страница 52: ...5 Wiring Diagrams 45 Single CAC Outdoor Unit Standard Inverter AUUW24GAE UU24W U44 AUUW30GAE UU30W U44 ...
Страница 53: ...Single CAC Outdoor Unit 5 Wiring Diagrams 46 Standard Inverter AUUW366D2 UU36W UO2 ...
Страница 55: ...Single CAC Outdoor Unit 5 Wiring Diagrams 48 Standard Inverter AUUW368D2 UU37W UO2 ...
Страница 57: ...Single CAC Outdoor Unit 5 Wiring Diagrams 50 Standard Inverter AUUW70LAE UU70W U34 ...
Страница 58: ...5 Wiring Diagrams 51 Single CAC Outdoor Unit Standard Inverter AUUW85LAE UU85W U74 ...
Страница 126: ...6 Single CAC Outdoor Unit Compact Inverter 3 Dimensions AUUW18GC0 UU18WC UL0 Chassis code UL2 ...
Страница 127: ...3 Dimensions 7 Single CAC Outdoor Unit Compact Inverter AUUW24GC0 UU24WC UE0 AUUW30GC0 UU30WC UE0 Chassis code UE ...
Страница 128: ...Single CAC Outdoor Unit 3 Dimensions 8 Compact Inverter AUUW36GC0 UU36WC U40 Chassis code U4 ...
Страница 130: ...10 Single CAC Outdoor Unit Compact Inverter 5 Wiring Diagrams Models AUUW18GC0 UU18WC UL0 ...
Страница 131: ...5 Wiring Diagrams 11 Single CAC Outdoor Unit Compact Inverter Models AUUW24GC0 UU24WC UE0 AUUW30GC0 UU30WC UE0 ...
Страница 132: ...Single CAC Outdoor Unit 5 Wiring Diagrams 12 Compact Inverter Models AUUW36GC0 UU36WC U40 ...