The Indoor Unit Installation
Ceiling
CAUTION
1~3mm
Drainage hole
Drainage hole
U-Trap
B
C
A
70mm
B
2C
C 2 x SP
SP = External Pressure
(mmAq)
Ex) External Pressure
= 10mmAq
A
70mm
B
40mm
C
20mm
A
Make sure to be closed.
Unit
Drainage pipe
(Local supply)
Thermal insulator
(Local supply)
Drainage hole
CAUTION FOR GRADIENT OF
UNIT AND DRAIN PIPING
Lay the drain hose with a downward
inclination so water will drain out.
Front of view
• Always lay the drain with downward
inclination (1/50 to 1/100).
Prevent any upward flow or reverse flow
in any part.
• 10mm or thicker formed thermal insulator
shall always be provided for the drain
pipe.
• Install the P-Trap (or U-Trap) to prevent
a water leakage caused by the blocking
of intake air filter.
Applied U-Trap Dimension
1.
Install declination
of the indoor unit is very
important for the drain
of the duct type air
conditioner.
2. Minimum thickness of the insulation for the connecting pipe shall be 5mm.
• The unit must be declined to the drain hose connected when finished installation.
CORRECT
CORRECT
INCORRECT
INCORRECT
• Upward routing not
allowed
≥
≥
≥
≥
≥
≥