26
PIPING LENGTH AND THE ELEVATION
ENGLISH
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
• Capacity is based on standard length and maximun allowance length is on the basis of
reliability.
• Improper refrigerant charge may result in abnormal cycle.
PIPING LENGTH AND THE ELEVATION
Capacity
(kBtu/h)
Pipe Size
mm(inch)
Length A(m)
Elevation B(m)
*Additional
refrigerant
(g/m)
Gas
Liquid
Standard
Max.
Standard
Max.
24
Ø 15.88 (5/8)
Ø 9.52 (3/8)
7.5
50
5
30
35
36
Ø 15.88 (5/8)
Ø 9.52 (3/8)
7.5
85
5
30
40
48
Ø 15.88 (5/8)
Ø 9.52 (3/8)
7.5
85
5
30
40
If installed tube is shorter than 7.5 m, additional charging is not necessary
Additional Refrigerant = (A - 7.5) x Additional refrigerant (g)
CAUTION
!