HOW TO SET E.S.P?
ENGLISH
Installer Setting -E.S.P.
This is the function that decides the strength of the wind for each wind level and because this
function is to make the installation easier.
- If you set ESP incorrectly, the air conditioner may malfunction.
- This setting must be carried out by a certificated-technician.
- When setting ESP value on the product without very weak wind or power wind function, it may
not work.
If entering into ESP setup mode by using
button, it indicates as the picture below.
2
Select ESP fan step by pressing
button. (01: very low, 02: low, 03:
medium, 04: high, 05: power)
3
Move to ESP value setting by pressing
button.
(It is 000 when delivering
from the warehouse.)
4
Press button to setup ESP value.
(It is possible to setup ESP
value from 1 to 255, and 1 is the
smallest and 255 is the biggest.)
5
Function code,
ESP code
ESP value
If pressing button long for 3
seconds, it enters into remote controller
setter setup mode.
- If pressing once shortly, it enters into
user setup mode. Please press more
than 3 seconds for sure.
1
Function Code
ESP value
ESP step
HOW TO SET E.S.P?