COMPREHENSIVE APPLICATION AND INSTALLATION MANUAL
LG Electronics
Installation check list
Configuration
System Design
Applications
Introduction
2.3 LG MV
Heating Mode
Mode
Item
Unit
R32
Cause & Check Point
Normal
Condition
Abnormal
Condition
Heating
Operation
High Pres-
sure
kPa
2300~4000
Above
4100
Overcharging, Heat exchanger fault,
Water flow rate shortage, Check that
the water inlet temperature is within the
operation range.
(
△
T=5 °C @ Water outlet temp.35
°C/45 °C,
△
T=8 °C @ Water outlet temp.55 °C)
Below
2200
Ref. shortage, Over water flow rate,
Check that the water inlet temperature
is within the operation range.
(
△
T=5°C @Water outlet temp.35
°C/45 °C,
△
T=8°C @ Water outlet temp.55 °C)
Low Pres-
sure
kPa
200~1200
Above
1300
Overcharging, Check that the outdoor
air temperature is within the operating
range.
Below
200
Ref. shortage, Outdoor Unit Fan lock,
Poor airflow in outdoor unit heat-
exchanger, Check that the outdoor air
temperature is within the operating
range.
Indoor
Water dT
(Water out
- Water in)
°C
-
Below
1 °C
Ref. shortage, Over water flow rate,
Check that the water inlet temperature
is within the operation range.
(
△
T=5 °C @ Water outlet temp.35
°C/45 °C,
△
T=8 °C @ Water outlet temp.55 °C)
Outdoor
Ref.
Discharge
Temp.
°C
-
Above
95 °C
Ref. Shortage, EEV clogging, Pipe
clogging
Outdoor
Discharge
Superheat
°C
-
Below
5 °C
Overcharging, EEV malfunction(Full
open)
Cooling Mode
Mode
Item
Unit
R32
Cause & Check Point
Normal
Condition
Abnormal
Condition
Cooling
Operation
High Pressure
kPa
1800~3600
Above
3800
Overcharging, Outdoor Unit Fan lock,
Poor airflow in outdoor unit heat-exchang-
er, Check that the outdoor air temperature
is within the operating range.
Below
1600
Ref. Leakage or Ref. Shortage, Check
that the outdoor air temperature is within
the operating range.
Low Pressure
kPa
600~1000
Above
1300
Overcharging, Over Water flow rate,
Check that the water inlet temperature is
within the operation range.
(
△
T=5 °C @ Water outlet temp.35 °C/45 °C,
△
T=8 °C @ Water outlet temp.55 °C)
Below
500
Ref. Shortage, Water flow rate shortage,
Check that the water inlet temperature is
within the operation range.
(
△
T=5
°C @
Water outlet temp.35
°C/45
°C,
△
T=8
°C @
Water outlet temp.55
°C)
Indoor Ref.
dT
(Pipe in –
Pipe out)
°C
0~10 °C
Above
12 °C
Ref. Shortage, EEV clogging, Pipe
clogging
Indoor Water
dT (Water out
– Water in)
°C
-
Below
1 °C
Ref. Shortage, Over water flow rate,
Check that the water inlet
temperature is within the operation range.
(
△
T=5 °C @ Water outlet temp.35 °C/45 °C,
△
T=8 °C @ Water outlet temp.55 °C)
Outdoor Ref.
Discharge
Temp.
°C
-
Above
95 °C
Ref. Shortage, EEV clogging, Pipe
clogging
Outdoor
Discharge
Superheat
°C
-
Below
5 °C
Overcharging, EEV malfunction(Full
open)