Remove the terminal block access cover
on the upper back of the dryer. Install a
UL-listed strain relief into the power cord
through-hole; then thread a UL-listed, 30A,
240V, 4-wire, #10 AWG-minimum copper
conductor power cord through the
strain relief.
1
Transfer the dryer’s ground wire from behind
the green ground screw to the center screw
of the terminal block. Attach the two hot
leads of the power cord to the outer terminal
block screws. Attach the white neutral wire
to the center terminal block screw. Attach the
power cord ground wire to the green ground
screw. TIGHTEN ALL SCREWS SECURELY.
Reinstall the terminal block access cover.
2
UL-Listed
Strain Relief
UL-Listed
4-Wire
Power Cord
Terminal
Block
Ground Screw
Neutral
(White)
Hot
(Black)
Power Cord
Ground Wire
Hot
(Red)
CONNECTING ELECTRIC DRYERS
Four-Wire Connection for Electric Dryers: Power Cord
• A 4-wire connection is required for all mobile
and manufactured home installations, as well
as all new construction after January 1, 1996.
• A UL-listed strain relief is required.
• Use a 30-amp, 240V, UL-listed power cord
with #10 AWG-minimum copper conductor
and closed loop or forked terminals with
upturned ends.
w
WARNING:
•Connectthepowercordtotheterminalblock.Eachcoloredwireshouldbeconnectedto
same color screw. Wire color indicated on manual is connected to the same color screw
in block. Failure to follow these instructions may result in a short or overload.
•Groundingthroughtheneutralconductorisprohibitedfor:(1)newbranch-circuit
installations, (2) mobile homes, (3) recreational vehicles, and (4) areas where local
codes prohibit grounding through the neutral conductor.
MFL62512825_EN_100524.indd 19
5/24/10 9:38:32 AM
Содержание TDD15515S
Страница 81: ...MFL62512825_SP_100520 indd 41 5 24 10 9 37 16 AM ...
Страница 82: ...MFL62512825_SP_100520 indd 42 5 24 10 9 37 16 AM ...
Страница 83: ...MFL62512825_SP_100520 indd 43 5 24 10 9 37 16 AM ...
Страница 84: ...MFL62512825_SP_100520 indd 44 5 24 10 9 37 16 AM ...