ENGLISH
68
5.2.4 Timer
This is to set values related the timer needed for operation of the Chiller.
Figure 49. Timer
Table 30. Timer Items
Item name
Setting
availability
Setting
UI
Unit
Minimum
value
Maximum
value
Adjustment
Unit
Notes
Evaporator Water
Pump Stop
●
Select
a number
Seconds
1
1800
1
Condenser Water
Pump Stop
●
Select
a number
Seconds
1
1800
1
Ignore Flow
●
Select
a number
Seconds
1
60
1
Oil Circulation
●
Select
a number
Seconds
30
600
1
Check Compressor
Run
●
Select
a number
Seconds
5
60
1
Block Restart
●
Select
a number
Seconds
5
3600
1
Содержание RCWFH Series
Страница 82: ...ENGLISH 82 Figure 64 Language Setting English Figure 65 Language Setting Chinese ...
Страница 140: ......