ENGLISH
18
Oil reclaim system
Oil reclaim system provides the system to reclaim the oil from the heat exchanger and let it come back to the oil
tank. Normally, it is reclaimed at the evaporator, and the vane housing. Refrigerant which came back into the oil tank
will then be evaporated to the gas and flow through the Oil Seperator line which is located at the upper part of the
casing, and then it will be sent to the inlet of the compressor. Oil that is contained in the refrigerant is separated by
the demister filter.
MAINTENANCE
Most of the lubrication related deficiencies in rotating parts of the chiller are because of the oil itself. If adequate vis-
cosity, pressure and flow are not obtained, lubricating performance will decrease. Impure substances that are pres-
ent in the oil also are a cause for the deficiencies.
Freon type refrigerant have chemical attraction with the oil. The viscosity changes according to the temperature and
pressure of oil. We have designed the chiller with these problems into consideration.
An oil pump run by hermetic electro motor and a heater controlled by the controlling device are installed in the oil
tank to prevent the trouble caused by the refrigerant inflow into the oil, decrease of the viscosity, damage of the
pump caused by the cavitation (vaporizing of water and formation of bubbles as becoming partially low pressurized
when water or flow at high speed) and the oil inflow into the refrigerant by forming. For these reasons the oil tank is
maintained at a high temperature.
The reason to start the oil pump for certain while before the startup of the chiller, is to prevent the compressor's ini-
tial unsteady operation because the left over oil in bearings or in the oil line may contain significant amount of refrig-
erant flow in during the stoppage.
After the chiller has been shut down, oil pump will be operated until the compressor is totally stopped since the com-
pressor rotates due to the internal force.
The only action that can be taken to prevent lubrication inferiority caused by blazing of the oil is replacing the oil itself.
Thus when it is time for cooling operation, make sure that you do the oil replacing adequately.