LG PRHR Series Скачать руководство пользователя страница 5

Installation Manual  

5

ENGLISH

Installation

Installation

Select installation location of the HR unit suitable for following conditions 

• Avoid a place where rain may enter since the HR unit is for indoor. 
• Sufficient service space must be obtained.
• Refrigerant pipe must not exceed limited length. 
• Avoid a place subject to a strong radiation heat from other heat source. 
• Avoid a place where oil spattering, vapor spray or high frequency electric noise is expected. 
• Install the unit at a place in which it is not affected by operation noise. (Installation within cell such as meeting

room etc. may disturb business due to noise.)

• Place where refrigerant piping, drain piping and electrical wiring works are easy.

NOTES

*  Be sure to install the inspection door at the electric control side.
** If reducers are used, servicing space must be increased equal to reducer's dimension.

Selection of the best location

Dimensional drawings

(*) Inspection door
(servicing space) 

481

345

453

(174)

218

182

60

30

182

(174)

419

61

(137)

124

450

450

300 more

(**)(Servicing space)

300 more

(**)(Servicing space)

450 more

(Servicing space)

300 more

(**)(Servicing space)

7

1

2

3

6

4

5

100 more1

0

0

 m

o

re

(Servicing space)(S

e

rv

ic

in

g

 s

p

a

c

e

)

100 more

(Servicing space)

100 more1

0

0

 m

o

re

(Servicing space)(S

e

rv

ic

in

g

 s

p

a

c

e

)

100 more

(Servicing space)

(Unit: mm)

No.

Part Name

Description

PRHR041/031

PRHR021

1

Low pressure Gas pipe connection port

Ø28.58 Brazing connection

Ø22.2 Brazing connection

2

High pressure Gas pipe connection port

Ø22.2 Brazing connection

Ø19.05 Brazing connection

3

Liquid pipe connection port

Ø15.88 Brazing connection(PRHR041)
Ø12.7 Brazing connection(PRHR031)

Ø9.52 Brazing connection

4

Indoor unit Gas pipe connection port

Ø15.88 Brazing connection

Ø15.88 Brazing connection

5

Indoor unit Liquid pipe connection port

Ø9.52 Brazing connection

Ø9.52 Brazing connection

6

Control box

7

Suspension bolts

M10 or M8

M10 or M8

Содержание PRHR Series

Страница 1: ...ODELS PRHR Series Heat Recovery Unit Original instruction Please read this installation manual completely before installing the product Installation work must be performed in accordance with the national wiring standards by authorized personnel only Please retain this installation manual for future reference after reading it thoroughly ...

Страница 2: ...2 HR Unit PRHR Series Heat Recovery Unit Manual TABLE OF CONTENTS Safety Precautions 3 Features 4 Installation Part 4 Installation 5 Coil Exchanging Method 13 ...

Страница 3: ...ere is risk of fire electric shock explosion or injury Do not damage or use an unspecified power cord There is risk of fire electric shock explosion or injury Do not touch the power switch with wet hands There is risk of fire electric shock explosion or injury Avoid a place where rain may enter since the HR unit is for indoor There is risk of property damage failure of product or elec tric shock I...

Страница 4: ...h Sound Absorbing Insulation Material Current Minimum circuit Amps MCA Maximum fuse Amps MFA Power Supply PRHR021 PRHR031 PRHR041 16 24 32 8 8 8 26 40 40 26 40 40 18 20 22 39 7 44 1 48 5 801x218x617 801x218x617 801x218x617 31 5x8 6x24 3 31 5x8 6x24 3 31 5x8 6x24 3 Galvanized steel plate Ø9 52 3 8 Ø15 88 5 8 Ø9 52 3 8 Ø12 7 1 2 Ø15 88 5 8 Ø22 2 7 8 Ø28 58 1 1 8 Ø28 58 1 1 8 Ø19 05 3 4 Ø22 2 7 8 Ø22...

Страница 5: ...ual to reducer s dimension Selection of the best location Dimensional drawings Inspection door servicing space 481 345 453 174 218 182 60 30 182 174 419 61 137 124 450 450 300 more Servicing space 300 more Servicing space 450 more Servicing space 300 more Servicing space 7 1 2 3 6 4 5 100 more 100 more Servicing space Servicing space 100 more Servicing space 100 more 100 more Servicing space Servi...

Страница 6: ...ion bolts HR Unit Installation CAUTION Tighten the nut and bolt to prevent unit falling Six sided Nut M10 or M8 Hanger metal Hanger metal Hanger metal Flat washer Flat washer Flat washer M10 Suspension bolt M10 or M8 A 1 Using an insert hole in anchor hang the suspension bolt 2 Install a hexagon nut and a flat washer locally procured to the suspension bolt as shown in the figure in the bottom and ...

Страница 7: ...Gas pipe Ø15 88 Liquid pipe Ø9 52 Brazing Type Liquid pipe Liquid pipe Low pressure gas pipe Low pressure gas pipe High pressure gas pipe High pressure gas pipe Liquid pipe Low pressure gas pipe High pressure gas pipe Brazing Type CAUTION Whenever connecting the indoor units with the HR unit install the indoor units in numerical order from No 1 Ex In case of installing 3 indoor units No 1 2 3 O No...

Страница 8: ...pes as shown in the Figure Not connected pipe Always seal up the tip of unused pipe by brazing Thermal insulator for refrigerant pipe Local supply Make sure that there is no clearance here Connect the wires to the terminals on the control board individually according to the outdoor unit connection Ensure that the color of the wires of outdoor unit and the terminal No are the same as those of HR Un...

Страница 9: ...FF SW02M 1 Selection of the method for addressing valves of an HR unit Auto Manual Auto Manual Switch No 1 On Switch No 1 Off h Each model is shipped with the switches No 2 and No 3 pre adjusted as above in the factory Zoning setting ON 1 2 3 1 2 1 3 2 4 For 2 branches PRHR021A For 3 branches PRHR031A For 4 branches PRHR041A Initial Setting 1 branch Connected 2 branches Connected 3 branches Connec...

Страница 10: ...o use a PRHR041 for 2 branches HR unit after closing the 3rd and 4th pipes set the dip switch for 2 branches HR unit The unused port must be closed with a copper cap not with a plastic cap 2 SW05M Rotary S W for addressing HR unit Must be set to 0 when installing only one HR unit When installing multiple HR units address the HR units with sequentially increasing numbers starting from 0 Maximum 16 ...

Страница 11: ...er ently at its wired remote control S W No Setup No 1 Manual addressing of valve 1 No 2 Manual addressing of valve 2 No 3 Manual addressing of valve 3 No 4 Manual addressing of valve 4 SW03M Increase in the digit of 10 of valve address SW04M Increase in the last digit of valve address SW01M SW03M SW04M Write positions of indoor units connected with each port and Central address also write rotary ...

Страница 12: ...ess SW05M Rotary S W Prerequisite for manual valve addressing central control address of each indoor unit must be preset differently at its wired remote control S W No Setup No 1 Manual addressing of valve 1 No 2 Manual addressing of valve 2 No 3 Manual addressing of valve 3 No 4 Manual addressing of valve 4 SW03M Increase in the digit of 10 of valve address SW04M Increase in the last digit of val...

Страница 13: ... Bypass CN12 Branch 4 High CN07 Branch 3 High CN06 Branch 2 High CN05 Branch 1 High CN04 Branch 3 Bypass CN10 Branch 2 Bypass CN09 Branch 1 Bypass CN08 Coil Exchanging Method NOTICE 1 Remove the 2 securing screws Remove the cover by pulling on the bottom of the cover and lifting up 3 Remove the 4 securing screws Lift up and pull on the cover NOTES Refer to the label concerned the solenoid coil s p...

Страница 14: ...14 HR Unit ...