Installation Manual
11
ENGLISH
Installation
3. SW01M/SW03M/SW04M (Dip S/W and tact S/W for manual valve addressing)
1) Normal setting (Non-Zoning setting)
- Used in manual addressing of the valve in the HR unit
- Set the address of the valve of the HR unit to the central control address of the connected indoor unit.
- SW01M: selection of the valve to address
SW03M: increase in the digit of 10 of valve address
SW04M: increase in the last digit of valve address
- Prerequisite for manual valve addressing : central control address of each indoor unit must be preset differ-
ently at its wired remote control.
S/W No.
Setup
No.1
Manual addressing of valve #1
No.2
Manual addressing of valve #2
No.3
Manual addressing of valve #3
No.4
Manual addressing of valve #4
SW03M
Increase in the digit of 10 of valve address
SW04M
Increase in the last digit of valve address
SW01M
SW03M
SW04M
Write positions of indoor units connected with each port and Central address, also write rotary S/W number
of HR Unit like below example.
If the branch 4 is not connected with an indoor unit, don't write on blank of table.
Rotary S/W number
HR Unit
( Multi V Sync )
0
X
06
05
04
Central address
of indoor unit
( In case of manual addressing of
valves )
X
Conference
Room 1
Dormitory
Room 2
Lecture
Room 1
Position of
indoor unit
4
3
2
1
Number of branch
NOTICE