10 AHU Control Kit / EEV Kit
Before Installation
Selection of Evaporator(Air Handling Unit)
See table below for applicable units
Selecting the capacity setting 'Option PCB'(Accessory) according to the capacity mentioned below.
- The corresponding capacity setting 'Option PCB' needs to be selected depending on the need
capacity.
- After checking the need capacity, remove the 36k Option PCB equipped in the main PCB,
and set up the Option PCB fitted the need capacity in the main PCB.
CAUTION
Saturated Suction Temperature (SST) = 6°C, SH (Superheat) = 5K, Air Temperature = 27°C DB / 19°C WB.
(Main PCB)
EBR52358907
28K
0.88~1.08
7 ~ 9
22 ~ 26
EBR52358908
36k
0.88~1.08
9 ~11
25 ~ 32
EBR52358909
42k
0.88~1.08
11~ 13
31 ~ 35
EBR52358910
48k
1.23~1.51
13 ~ 16
33 ~ 45
EBR52358911
76k
1.93~2.35
20 ~ 24
50 ~ 64
EBR52358912
96k
1.93~2.35
25 ~ 31
64 ~ 72
Option PCB
P/No
Capacity
(Btu/h)
Allowed heat
exchanger
Volume (dm
3
)
Allowed heat
exchanger capacity
(kW)
Air flow rate
(CMM)
Capacity setting
'Option PCB'
Detail