Ownerʼs & Installation Manual
13
ENGLISH
TEMP
FAN
SPEED
OPER
MODE
When pressing the button and
button simultaneously for more than 3
seconds, the system will be entered into
the installer setting mode.
- After entering into the installer setting
mode, select the ceiling height setting
code value by pressing the button.
* Ceiling height setting code value : 05
1
Select the desired setting value with the
temperature up(
▲
), down(
▼
) button.
2
When pressing the button, currently
established ceiling height value will be
set up.
3
When pressing the button and
button simultaneously for more than 3
seconds after the setting has been
completed, the setting mode will be released.
- If there isn’t any button input for more
than 25 seconds, the installer setting
mode will also be released.
4
OPER
MODE
OPER
MODE
Code value
*Setting value
01: Low
02: Standard
03: High
04: Very high
OPER
MODE
Value
Installation instruction
Installer Setting -Ceiling Height Selection
This function is to adjust FAN Airflow rate according to ceiling height (For ceiling type product)
•
Ceiling height setting is available only for some products.
•
Ceiling height of ʻVery highʼ function may not exist depending on the indoor unit.
•
Refer to the product manual for more details.
Ceiling Height Level
Description
01
Low
Decrease the indoor airflow rate 1 step from standard level
02
Standard
Set the indoor airflow rate as standard level
03
High
Increase indoor airflow rate 1 step from standard level
04
Very high
Increase indoor airflow rate 2 steps from standard level
<Ceiling Height Selection Table>