22
LG MultiSITE
TM
Communications Manager
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
STAT (Status) LED
The green “STAT” LED provides a CPU machine status check, and should remain lit whenever the controller is powered. See Figure 10. If
the status LED does not light while power is applied, contact Technical Support.
BEAT (Heartbeat) LED
In normal operation, the yellow heartbeat “BEAT” LED blinks at 1 Hz, at 50%/50% on/off duty cycle. See Figure 10.
During controller bootup, this LED may blink at 1 Hz with a 90%/10% on/off duty cycle, or in some other irregular pattern. When boot up
completes, the platform daemon starts, and the normal 1 Hz flash at 50%/50% on/off duty cycle returns.
If the “BEAT” LED stays on constantly, does not light, or blinks very fast, contact Technical Support.
Note:
The 1Hz, 90%/10% on/off “BEAT” flash at bootup also occurs during other critical operations, such as a firmware upgrade to the controller
and/or any attached modules. Do not remove power from the controller while its “BEAT” LED flashes with a 90%/10% on/off duty cycle.
Wait for the normal (50%/50%) flash to return before removing power.
PRI, SEC (Ethernet) LEDs
There are two LEDs for each of the two LAN ports.
Green
(left-side) “Link” LED operates as follows:
• Off: No Ethernet link is made.
• On: Ethernet link is made.
Yellow
(right-side) “Activity” LED operates as follows:
• Off: No Ethernet activity.
• On: Blinking indicates activity (typical if Link is On).
STATUS LEDS