BMS PROTOCOL
ENGLISH
n
Outdoor unit Monitor point
No.
Name
Object Name
(XX : Unit Address
Number)
Object
Type
Unit
Inactive
Active
TEXT-0 TEXT-1 TEXT-2 TEXT-3 TEXT-4 TEXT-5
1
Compressor Operation Status outdoor_CompOperStatus_XX
BI
Stop(0)
Run(1)
3
Inverter Fan 1 frequency
outdoor_InverterFanFreq_XX
AI
-
4
High Pressure
outdoor_HighPressure_XX
AI
-
5
Low Pressure
outdoor_LowPressure_XX
AI
-
6
Suction Temperature
outdoor_SunctionTemp_XX
AI
°C
7
Liquid Pipe Temperature
outdoor_LiquidPipeTemp_XX
AI
°C
8
Heat Exchanger Temperature
outdoor_HexTemp_XX
AI
°C
9
Outdoor EEV
outdoor_OutdoorEEV_XX
AI
-
10
Subcool EEV
outdoor_SubCoolEEV_XX
AI
-
11
Hot Gas Valve
outdoor_HotgasValue_XX
BI
Stop(0)
Run(1)
12
Inverter Discharge Temperature outdoor_InverterDischargeTemp_XX
AI
°C
13
Outdoor Temperature
outdoor_OutdoorTemp_XX
AI
°C
14
Operation Mode
outdoor_OperationMode_XX
MI
STOP(1) COOL(2) HEAT(3)
NOTE
• ACP BACnet gateway is required for BACnet protocol.
• In case of PAHCMS000, BACnet protocol is not supported.
• For more details, refer to the manual of control product.