16
MultiSITE CRC 1 Controller
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
CONFIGURATION SCREENS
More Screens
–
continued
Press the right arrow button to display these screens. To adjust vane angle, user selects vane(s) by tapping
vane icon at the top of the screen, adjusts vane angle by using up/down arrows and then selects Apply button.
Note:
Vane fixed angle control for multi-vane systems occurs in pairs. Refer to the Vane Fixed Angle screen. If a 4-louver
device is identified, when the user chooses Vane 1 or Vane 3 control, the opposite vane (Vane 3 or Vane 1) will be
controlled at the same time. If Vane 2 or Vane 4 is selected, Vane 4 or Vane 2 will be controlled in lockstep with its
matching pair as well. The same control behavior holds for a 2-louver device.
Off(0)
Vane Direction
Airflow Up/Down
Off(0)
Airflow Left/Right
Off(0)
Airflow Circular
Apply
Reset
ALL
Vane Fixed Angle
Airflow Up / Down and
Airflow Left / Right con-
trols can both be “On” at
the same time. However,
when Airflow Circular
control is “On,” both of
the other two controls will
be set to “Off.”
Parameter
Parameter Settings
Definition
Airflow Up / Down
Choices: 0 = “Off”, 1 = “On”
Default value:
Off
Selects the vane direction of the airflow, up and down
Airflow Left / Right
Choices: 0 = “Off”, 1 = “On”
Default value:
Off
Selects the vane direction of the airflow, left and right
Airflow Circular
Choices: 0 = “Off”, 1 = “On”
Default value:
Off
For 4-way cassette IDUs only. Selects circular vane
direction
Apply
Sends the vane angle selected with the up and down
arrow keys to the IDU
Reset
Sets all vane angles to the default position of “3”