Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
40 | ELECTRICAL CONNECTIONS
MUL
TI V W
ater Mini Unit Engineering Manual
DIP SWITCH SETTINGS FOR USE
WITH GEN4 INDOOR UNITS
Generation 4 Equipment
LG’s indoor units are designated Generation 4 (Gen 4). For Gen 4 indoor units to operate with Gen 4 indoor unit features, the air conditioning
system must meet the following requirements:
• All indoor units, heat recovery units, and air / water source units
must be Gen 4 or higher.
• All air / water source units must have Gen 4 or higher software
installed.
• Air / water source units DIP switch 3 must be set to ON
(factory default setting is OFF).
• All controllers must support Gen 4 indoor unit features.
The figure at right shows the outdoor unit DIP switch. The "PRHR*3
Heat Recovery Unit to Air / Water Source Unit Compatibility" table
lists how combining different components will affect system opera-
tion. The "Serial Numbers of Air / Water Source Units with Gen 4
or Higher Software" table lists the serial numbers of air and water
source units that have Gen 4 or higher software. All air and water
source units, indoor units, heat recovery units, and controllers in a
system must be Gen 4 compatible or the system will not operate with
Gen 4 indoor unit features.
Figure 14: Location and Setting of Outdoor Unit DIP Switch 3.
1 2
7
6
5
4
3
1 2
7
6
5
4
3
ON
OFF
1 2
7
6
5
4
3
1 2
7
6
5
4
3
ON
OFF
Air/Water Source Unit DIP Switch No. 3
Air / Water Source Unit
Model Type
Multi V Air Source
Heat Pump
Multi V Air Source
Heat Recovery
Multi V IV Water Source
Heat Pump
Multi V IV Water Source
Heat Recovery
Serial Number of Air / Water
Source Units with
Gen 4 or Higher Software
502********* and Higher
503********* and Higher
504********* and Higher
Table 21: PRHR*3 Heat Recovery Unit to Air / Water Source Unit Compatibility.
Model
Starting Production Date
Production Starting Serial No.
Upgrade Software Service
Multi V 5 with LGRED*
ARUM****TE5
February 1, 2019
1902xxx
N/A
Multi V 5
ARUM****TE5
February 1, 2018
1802xxx
September 28, 2018
Multi V S
ARUB060GSS4
October 1, 2018
1810xxx
September 28, 2018
Multi V Water IV
ARWB****AS4
October 1, 2018
1810xxx
September 28, 2018
Multi V IV
ARUB****TE4
N/A
N/A
October 31, 2018
Multi V Water Mini
ARWN053GA2
N/A
N/A
N/A
Multi V II and III
ARUB****TE2,
ARUB****TE3
N/A
N/A
N/A
Multi V Water II
ARWB****A2
N/A
N/A
N/A
Table 22: Serial Numbers of Air / Water Source Units with Gen 4 or Higher Software.