Test Run
Display
Title
Cause of Error
Outside Unit related Error
1
0
4
*
Communication Error Between Master Outdoor
Unit and Other Outdoor Unit
Failing to receive Slave Unit signal at main PCB of Master Outdoor
Unit
1
1
3
*
Master Outdoor Unit Liquid pipe Temperature
Sensor Error
Liquid pipe temperature sensor of Master Outdoor Unit is open or
short
1
1
5
*
Master Outdoor Unit Subcooling Outlet Tempera-
ture Sensor Error
Master Outdoor Unit Subcooling Outlet Temperature Sensor open
or short
1
1
6
* Master Outdoor Unit Oil Level Sensor Error
Oil Level Sensor of Master Outdoor Unit is open or short
1
4
5
*
Master outdoor unit Main Board - External Board
communication Error
Master outdoor unit Main Board - External Board communication
Error
1
5
1
*
Failure of operation mode conversion at Master
Outside Unit
Failure of operation mode conversion at Master
Outside Unit
1
8
0
* Plate type heat exchanger freeze prevention
Plate type heat exchanger freeze prevention error
1
8
1
* Water temperature sensor error
Water temperature sensor open/short
1
8
2
* Communication error between MICOMs
Communication error between main MICOM and sub MICOM