Refrigerant piping system
Indoor unit connection
➔
Indoor unit connecting pipe from branch (a~f)
Indoor unit capacity [kW(Btu/h)]
≤ 5.6(19,100)
< 16.0(54,600)
≤ 22.4(76,400)
< 33(112,600)
Ø6.35(1/4)
Ø9.52(3/8)
Ø9.52(3/8)
Ø9.52(3/8)
Ø12.7(1/2)
Ø15.88(5/8)
Ø19.05(3/4)
Ø22.2(7/8)
Liquid pipe
[mm(inch)]
Gas pipe
[mm(inch)]
Oil trap application method between outside units
• Because of the possibility of oil being accumulated in the outside unit that has stopped, when there is a height difference be-
tween outside unit pipes or if the pipe distance between the outside units is over 2m, you must always apply an oil trap. (But,
the oil trap between outside units is limited to 1 time and is only applied to the gas pipe.)
• If the pipe distance between the outside units is 2m or below, and if the location of the main pipe is lower than that of the out-
side unit and if the location of the main pipe is lower than that of the outside unit, the oil trap does not have to be applied.
• If the location of the main pipe is higher than the location of the outside unit, be careful since the oil can be accumulated in the
stopped outside unit.
• If there is high/low difference between the outside unit pipes, oil can be accumulated to the outside unit on the lower location
until the unit stops.
Examples of Wrong Pipe Connections
If the main pipe is higher
than the outdoor units,
oil is accumulated in the
outdoor unit.
If there are differences in the height between
the outdoor units, oil is accumulated in the
lower outdoor unit.
Oil Trap