GENERAL DATA
2XWGRRU8QLW6SHFL¿FDWLRQV
Unit Model No.
ARUN072BSS5
6.0 Ton
ARUN096BSS5
8.0 Ton
Cooling Performance
Nominal Cooling Capacity (Btu/h)
1
72,000
96,000
Rated Cooling Capacity (Btu/h)
2
69,000
92,000
Heating Performance
Nominal Heating Capacity (Btu/h)
1
81,000
108,000
Rated Heating Capacity (Btu/h)
2
77,000
103,000
Operating Range
Cooling (°F DB)
3
23 to 122
23 to 122
Heating (°F WB)
-13 to +61
-13 to +61
Compressor
Inverter Type / Quantity
Hermetically Sealed Scroll / 1
Oil / Type
PVE / FW68D
Fan (Side Discharge)
Type
Axial Flow Fan
Motor Output (kW) x Qty.
0.25 x 2
Motor / Drive
Brushless Digitally Controlled / Direct
Operating Range (RPM)
Cooling
200 to 950
200 to 1,000
Heating
200 to 950
200 to 1,000
External Static Pressure (in. WG)
0.12
0.12
Maximum Air Volume (CFM)
7,416
7,416
Unit Data
Refrigerant Type
R410A
R410A
Refrigerant Control / Location
EEV / Indoor Unit
EEV / Indoor Unit
Max. Number Indoor Units / System
4
13
16
Sound Pressure Levels dB(A)
5
(Cooling / Heating)
55 / 57
59 / 60
Net Unit Weight (lbs.)
348
348
Shipping Weight (lbs.)
379
379
Communication Cables
6,7
2 x 18
2 x 18
Heat Exchanger
Material and Fin Coating
Copper Tube / Aluminum Fin and Black Coated Fin™ / Hydrophilic
Rows / Fins per inch
(3 x 14) x 2
(3 x 14) x 2
Piping
8
Liquid Line Connection (in., OD)
3/8 Braze
3/8 Braze
Vapor Line Connection (in., OD)
3/4 Braze
7/8 Braze
Factory Charge lbs. of R410A
13.2
13.2
Table 1:
9+]3KDVH2XWGRRU8QLW6SHFL¿FDWLRQV
1
Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft. of
refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units. All capaci-
ties are net with a Combination Ratio between 95–105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF
wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and
59ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
2
Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
3
Cooling with the Low Ambient Wind Baffle (sold separately) is covered to -9.9°F.
4
The System Combination Ratio must be between 50–130%.
5
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
6
Communication cable between outdoor unit and indoor units must be a minimum of 18 AWG, 2-conduc-
tor, twisted, stranded, shielded. Ensure the communication cable shield is properly grounded to the
outdoor unit chassis only.
Do not ground the outdoor unit to the indoor units communication cable at
any other point. Wiring must comply with all applicable local and national codes.
7
Power wiring is field provided, solid or stranded, and must comply with all local and national codes. See
next page for detailed electrical data.
8
LG requires that LATS software be used on all projects to ensure correct line sizing. Designer must
verify the shop drawing design against the as built design using LATS. Contractor must also use LG
manufactured Y-Branch and Header Kits only.
THREE-PHASE