80
ELECTRICAL WIRING
ENGLISH
Display
Title
Cause of Error
O
ut
do
or
u
ni
t
re
la
te
d
er
ro
r
2 3
1
Master Outdoor Unit Inverter
Compressor DC link Low Voltage
DC charging is not performed at Master Outdoor Unit
after starting relay turn on.
2
Slave1 Outdoor Unit Inverter
Compressor DC link Low Voltage
DC charging is not performed at Slave1 Outdoor Unit
after starting relay turn on.
3
Slave2 Outdoor Unit Inverter
Compressor DC link Low Voltage
DC charging is not performed at Slave2 Outdoor Unit
after starting relay turn on.
4
Slave3 Outdoor Unit Inverter
Compressor DC link Low Voltage
DC charging is not performed at Slave3 Outdoor Unit
after starting relay turn on.
2 4
1
Master Outdoor Unit High Pressure
Switch
System is turned off by Master Outdoor Unit high
pressure switch.
2
Slave1 Outdoor Unit High Pressure
Switch
System is turned off by slave1 Outdoor Unit high
pressure switch.
3
Slave2 Outdoor Unit High Pressure
Switch
System is turned off by slave2 Outdoor Unit high
pressure switch.
4
Slave3 Outdoor Unit High Pressure
Switch
System is turned off by slave3 Outdoor Unit high
pressure switch.
2 5
1
Master Outdoor Unit Input Voltage
High/ Low Voltage
Master Outdoor Unit input voltage is over 487V or below
270V
2
Slave1 Outdoor Unit Input Voltage High/
Low Voltage
Slave1 Outdoor Unit input voltage is over 487V or below
270V
3
Slave2 Outdoor Unit Input Voltage High/
Low Voltage
Slave2 Outdoor Unit input voltage is over 487V or below
270V
4
Slave3 Outdoor Unit Input Voltage High/
Low Voltage
Slave3 Outdoor Unit input voltage is over 487V or below
270V
2 6
1
Master Outdoor Unit Inverter
Compressor Start Failure
The First Start Failure by Master Outdoor Unit Inverter
Compressor Abnormality
2
Slave1 Outdoor Unit Inverter
Compressor Start Failure
The First Start Failure by Slave1 Outdoor Unit Inverter
Compressor Abnormality
3
Slave2 Outdoor Unit Inverter
Compressor Start Failure
The First Start Failure by Slave2 Outdoor Unit Inverter
Compressor Abnormality
4
Slave3 Outdoor Unit Inverter
Compressor Start Failure
The First Start Failure by Slave3 Outdoor Unit Inverter
Compressor Abnormality
2 9
1
Master Outdoor Unit Inverter
Compressor Over Current
Master Outdoor Unit Inverter Compressor Fault OR Drive
Fault
2
Slave1 Outdoor Unit Inverter
Compressor Over Current
Slave1 Outdoor Unit Inverter Compressor Fault OR Drive
Fault
3
Slave2 Outdoor Unit Inverter
Compressor Over Current
Slave2 Outdoor Unit Inverter Compressor Fault OR Drive
Fault
4
Slave3 Outdoor Unit Inverter
Compressor Over Current
Slave3 Outdoor Unit Inverter Compressor Fault OR Drive
Fault
Содержание MULTI V IV PRO JRUN180LLS4