PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
35
ENGLISH
(Table 4) Conditional Application
WARNING
!
• In case of pipe diameter B connected after first branch is bigger than the main pipe
diameter A, B should be of the same size with A.
Ex) In case indoor unit combination ratio 120% is connected to 24 HP(67.2 kW) outdoor unit.
1) Outdoor unit main pipe diameter A : Ø 34.9(Gas pipe), Ø 15.88(liquid pipe)
2) Pipe diameter B after first branch according to 120% indoor unit combination(80.6 kW)
: Ø 34.9(gas pipe), Ø 19.05(liquid pipe)
Therefore, pipe diameter B connected after first branch would be Ø 34.9(gas pipe) /
Ø 15.88(liquid pipe) which is same with main pipe diameter.
Condition
Example
1
Diameter of pipes between
first branch and the last branch
should be increased by one
step, except pipe diameter
B,C,D is same as Diameter A
40 m < B+C+D+e
90 m
B, C, D
Change a diameter
2
While calculating whole
refrigerant pipe length, pipe
B,C,D length should be
calculated twice.
A+Bx2+Cx2+Dx2
+a+b+c+d+e
≤
1 000 m
3
Length of pipe from each indoor
unit to the closest branch
a,b,c,d,e
≤
40 m
4
Length of pipe from outdoor
unit to the farthest indoor unit 5
(A+B+C+D+e)] - [Length of
pipe outdoor unit to the closest
indoor unit 1 (A+a)]
≤
40 m
(A+B+C+D+e)-(A+a)
≤
40 m
• To satisfy below condition to make 40 m ~ 90 m of pipe length after first branch.
Ø6.35
Ø9.52, Ø9.52
Ø12.7,
Ø12.7
Ø15.88, Ø15.88
Ø19.05,
Ø19.05
Ø22.2, Ø22.2
Ø25.4,
Ø25.4
Ø28.58, Ø28.58
Ø31.8,
Ø31.8
Ø34.9, Ø34.9
Ø38.1
l
h 30m
H
90m
L
Indoor
Unit
WARNING
!
Pipe length after header branching (a~e)
It is recommended that difference in length of the pipes connected to the Indoor Units is
minimized. Performance difference between Indoor Units may occur.