Installation Manual  13

Installation

Remote controller 

box body

Cord clamp
(accessory)

Lever carefully 

the box open 

using a screw 

driver, etc.

Front case

The lo

wer par

t

Face of wall

Under plate

Screw (accessory)

• Separate the under plate from Remote

controller box.

• Attach insulator to under plate.

• Fix the under plate on the wall

• Fix the cord clamps on the wall by ø 3 tapping screws (accessory).
• Fix the remote controller cord.

WIRED REMOTE CONTROLLER INSTALLATION

DISASSEMBLING

ELECTRICAL WIRING

 

Wire and make sure that teminal

numbers are matched on unit side and

remote controller side.

The maximum length of the cord is 100m.

If the length of the cord exceeds 50m,

use a wire size greater than 0.5mm

2

.

Remote controller

(Main board)

CN REMO

• Although the room temperature sensor is in the indoor unit, the remote controller should be installed in such

places away from direct sunlight and high humidity.

Installation of the remote controller

• Select places that are not splashed with water.
• Select controller position after receiving customer approval.
• The room temperature sensor is built in the indoor unit.
• This remote controller equipped with liquid crystal display. If this position is higher or lower, display is difficult

to see.(The standard height is 1.2 ~1.5m high)

Routing of the remote controller cord

• Keep the remote controller cord away from the refrigerant piping and the drain piping.
• To protect the remote controller cord from electrical noise, place the cord at least 5cm away from other

power cables. (audio equipment. television set, etc.)

• If the remote controller cord is secured to the wall, provide a trap at the top of the cord to prevent water

droplets from running.

Installation of Remote Control

Содержание MULTI-V CRNN-TD Series

Страница 1: ... manual completely before installing the product Installation work must be performed in accordance with the national wiring standards by authorized personnel only Please retain this installation manual for future reference after reading it thoroughly ENGLISH ITALIANO ESPAÑOL FRANÇAIS DEUTSCH PORTUGUESE ...

Страница 2: ...l Horizontal meter Flaring tool set Specified torque wrenches different depending on model No Spanner Half union Hexagonal wrench Gas leak detector Vacuum pump Gauge manifold Owner s manual Thermometer Installation Parts 3 Safety Precautions 4 Installation Selection of the best location7 Ceiling dimension and hang ing bolt location 8 Wiring Connection 9 Installation of Decoration Panel 10 Installa...

Страница 3: ... Intake Air Outlet Installation Parts Name Quantity Shape for gas pipe for liquid pipe Clamp metal 2 EA Insulation for fitting 1 SET Drain hose 1 EA Plastic band 8 EA Washer for hanging backet 4 EA Other Paper pattern for installation Owner s manual Installation manual ...

Страница 4: ...the possibility of injury or damage to properties only Be sure not to do Be sure to follow the instruction Installation Do not use a defective or under rated circuit breaker Use this appliance on a dedicated circuit There is risk of fire or electric shock For electrical work contact the dealer seller a qualified electri cian or an Authorized Service Center Do not disassemble or repair the product ...

Страница 5: ... the case edges and the fins on the condenser and evaporator For installation always contact the dealer or an Authorized Service Center There is risk of fire electric shock explosion or injury Do not install the product on a defective installation stand It may cause injury accident or damage to the product Be sure the installation area does not deteriorate with age If the base collapses the air co...

Страница 6: ...t To avoid vibration or water leakage Do not install the product where the noise or hot air from the out door unit could damage the neighborhoods It may cause a problem for your neighbors Use two or more people to lift and transport the product Avoid personal injury Do not install the product where it will be exposed to sea wind salt spray directly It may cause corrosion on the product Corrosion p...

Страница 7: ...he door way Ensure the spaces indicated by arrows from the wall ceiling or other obstacles The indoor unit must have the maintenance space Read completely then follow step by step Unit cm Ceiling Ceiling Board Ceiling Board 30 or more Above 250 400 or less 100 or more 50 or more 50 or more 30 or less Floor Installation Selection of the best location CAUTION In case that the unit is installed near ...

Страница 8: ...s Make sure that ventilation fan is enough to cover all noxious gases from this place Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam 2 Avoid installng air conditioner in such places where cooking oil or iron powder is generated 3 Avoid places where inflammable gas is generated 4 Avoid place where noxious gas is generated...

Страница 9: ...ng washer M10 Air Conditioner body The following parts are local purchasing Hanging Bolt W 3 8 or M10 Nut W 3 8 or M10 Spring Washer M10 Plate Washer M10 Air inlet side view Control box cover Indoor power cord Remote control cord Control box cover fitting screw 2 units Terminal Block in Indoor 1 L 2 N 3 4 INDOOR POWER INPUT Terminal Block in Outdoor A B C D Vcc Open the control box cover and conne...

Страница 10: ...lle including the air filter Decoration panel fixing screws hexagon M5 screws Temporally fitting at 2 places Tightening about 10mm Control box cover Piping side Inlet Grille Inlet Grille Inlet Grille Inlet Grille Inlet Grille Louver motor Decoration panel fixing screws Hexagon M5 screw Air conditioner unit Decoration panel Key holes Display Lead wire for louver motor and display The decoration pan...

Страница 11: ... to an end Feed water to the flexible drain hose and check the piping for leakage Be sure to check the drain pump for normal operating and noise when electrical wiring is complete When the test is complete connect the flexi ble drain hose to the drain port on the indoor unit Heat insulation material Polyethylene foam with thick ness more than 8 mm Drain test Maintenance drain port Upward routing n...

Страница 12: ... to burn out of the wires 4 Specification of power source 5 Confirm that electrical capacity is sufficient 6 Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate 7 Confirm that the cable thickness is as specified in the power sources specification Particularly note the relation between cable length and thickness 8 Never fail to equip...

Страница 13: ...om temperature sensor is in the indoor unit the remote controller should be installed in such places away from direct sunlight and high humidity Installation of the remote controller Select places that are not splashed with water Select controller position after receiving customer approval The room temperature sensor is built in the indoor unit This remote controller equipped with liquid crystal d...

Страница 14: ...e one trap per unit A single trap for converging units will prove ineffective c Rig the trap to allow for future changing b Suspension bolts should be used the support long stretches of drain pipe in order to ensure that a gradient of 1 100 is maintained PVC pipe should not be bent Spacing of supports for horizontal piping c The length of pipe laid horizontally should be kept a minimum Gradient of...

Страница 15: ...indoor unit The drain pipe is thermally insulated to prevent the formation of condensation inside the pipe The drain up mechanism should be fitted before the indoor unit is installed and when the electricity has been connected pour some water into the drain pan and cheek the drain pump to see that it is functioning correctly All connections should be secure Special care is needed with PVC pipe Ins...

Страница 16: ...Prevent any upward flow or reverse flow in any part 3 5mm or thicker formed thermal insulator is provid ed for the drain pipe 4 Upward routing is not allowed 5 Be sure to check the drain pump for normal opera tion and abnormal noise when electrical wiring is complete 1 50 1 100 MAX 700mm Elbow Drain pump Unit Drain pipe Local supply Thermal insulator Local supply Wall Drain hose ...

Страница 17: ...ear cover of the wired remote controller to set the mode 2 Select one of three selectable modes as follows Position 1 The room temperature is controlled by the thermistor of the main body Position 2 The room themperature is controlled by the thermis tor of the wired remote controller control the temper ature according to the position of wired remote con troller Position 3 The room temperature is c...

Отзывы: