3
4
ENGLISH
- Above setup must be done for all HR unit valves.
- The valve that is not connected with any indoor unit should be ad-
dressed with any other number than used address numbers of the
valves connected with indoor units.
(The valves does not work if the address numbers are same.)
- Above setup must be done for all HR unit valves.
- The valve that is not connected with any indoor unit should be ad-
dressed with any other number than used address numbers of the
valves connected with indoor units.
(The valves does not work if the address numbers are same.)
Completion of manual pipe detection
Reset the power of HR unit PCB.
Enter the central control address into
each indoor unit using its wired remote
control.
On the HR unit PCB, manually set address
of each valve of the HR unit to the central
control address of the indoor unit
connected to the valve.
Reset the power of outside unit PCB.
Wait for about 5 minutes.
The number of the indoor units installed is
displayed.
Ex)HR
र
The number of the indoor
Check the central control address of
indoor and HR unit.
Make sure that reset the outside unit
power when changing the central
control unit
Are the number
of indoor units connected to the
outside unit and displayed one
equal?
Execute in case of Auto pipe detection
failure
Turn No.1 of SW02M of HR unit PCB on.
NO
YES
No.
Display and setup
Setup and Contents
1
- Operation: None
- Display: None
2
- Operation: Turn dip S/W No.1 on to ad-
dress valve #1
- Display: Existing value saved in EEP-
ROM is displayed in 7-SEG.
3
- Operation: Set the digit of 10 to the
number in Group High data of the wired
remote control connected to the corre-
sponding indoor unit to the valve #1 by
pressing left tack S/W.
- Display: Digit increasing with the times
of pressing tack S/W is displayed in left
7-SEG
4
- Operation: Set the digit of 1 to the num-
ber in Group Low data of the wired re-
mote control connected to the
corresponding indoor unit to the valve
#1 by pressing right tack S/W.
- Display: Digit increasing with the times
of pressing tack S/W is displayed in
right 7-SEG
5
- Operation: Turn dip S/W No.1 off to
save the address of valve #1
- Display: "11" displayed in 7-SEG disap-
pears
7-SEG
SW01M
SW03M
SW04M
7-SEG
SW01M
SW03M
SW04M
7-SEG
SW01M
SW03M
SW04M
7-SEG
SW01M
SW03M
SW04M
7-SEG
SW01M
SW03M
SW04M
Example of manual valve addressing (Zoning
setting)
(In case that an indoor unit of central control address "11" is connected
to a valve #1 of an HR unit)
Zoning control is connecting 2 or more indoor units at one pipe of HR
unit. In case of Zoning control, in order to set controls with multiple in-
door units connection uses the rotary switch. Namely, only the rotary
switch changes from same valve set condition and set indoor units
connection.
1. On dip switch of the corresponding valves and sets the rotary
switch at 0.
2. Setting the number with tact switch.
3. In case of addition of indoor units to same port, increases 1 with the
rotary switch and sets number with tact switch.
4. In case of checking the number which the corresponding valve is
stored, turn on dip switch and set the number of rotary switch.
5. Indoor units set available 7 per a port(rotary switch 0~6), in case of
setting above of 7 with rotary switch, it will display error.
6. Setting the rotary switch on original condition(HR unit number set
conditions) after all finishing a piping setting.
7. The rotary switch set value of above number of indoor units which is
connected with FF and prevents a malfunction.
(Example: The case where 3 indoor units is connected in piping 1,
sets from rotary switch 0,1,2 and 3,4,5 with FF set)
- Prerequisite for manual valve addressing: central control address of
each indoor unit must be preset differently at its wired remote con-
trol.
No.
Display and setup
Setup and Contents
1
- Operation: None
- Display: None
2
- Operation : Turn dip S/W No.1 on to ad-
dress valve #1
- Display : Existing value saved in EEP-
ROM is displayed in 7-SEG.
3
- Operation : Set the digit of 10(1) to the
number in Group High data of the wired
remote control connected to the corre-
sponding indoor unit to the valve #1 by
pressing left tack S/W.
- Display : Digit increasing with the times
of pressing tack S/W is displayed in left
7-SEG.
4
- Operation : SW05M : 1
- Display : Display former value.
5
- Operation : Setting No. using SW03M
and SW04M, SW05M : 1
- Display : Display setting value.
6
- Operation : Turn dip S/W No.1 off to
save the address of valve #1
- Display : "11" displayed in 7-SEG disap-
pears.
7
- Operation : Return valve of addressing
HR unit.
- Display : None
7-SEG
SW01M
SW03M
SW04M
0
SW05M
7-SEG
SW01M
SW03M
SW04M
SW05M
0
7-SEG
SW01M
SW03M
SW04M
SW05M
0
1
7-SEG
SW01M
SW03M
SW04M
SW05M
7-SEG
SW01M
SW03M
SW04M
SW05M
1
7-SEG
SW01M
SW03M
SW04M
SW05M
1
7-SEG
SW01M
SW03M
SW04M
SW05M
0
Example of manual valve addressing (Non-
Zoning setting)
(In case that an indoor unit of central control address "11" is connected
to a valve #1 of an HR unit)
- Prerequisite for manual valve addressing: central control address of
each indoor unit must be preset differently at its wired remote con-
trol.
Flow chart of manual addressing for pipe de-
tection
Содержание multi V ARWB Series
Страница 44: ...44 ENGLISH ...