ELECTRICAL WIRING
Series outdoor units
When the power source is connected In series between the units.
When the power source is supplied to Each outdoor unit individually.
R S T N
Switch
Fuse
L
N
Communication cable
(2 Wires Cable)
Power cable
(4 Wires Cable)
Communication cable
(3 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
[Master]
[Indoor Units]
Outdoor
Power supply
(3Ø 4wires)
Indoor
Power supply
(1Ø 2wires)
(Main Switch)
[Slave1]
[Slave2]
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
L
N
Communication cable
(2 Wires Cable)
Power cable
(4 Wires Cable)
Communication cable
(3 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
[Master]
[Indoor Units]
Outdoor
Power supply
(3Ø 4wires)
Indoor
Power supply
(1Ø 2wires)
(Main Switch)
[Slave1]
[Slave2]
R S T N
Switch
Fuse
R S T N
Switch
Fuse
R S T N
Switch
Fuse
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
WARNING
When the total capacity is over than as follow, the power source do not use in series be-
tween the units.
The First terminal block could be burnt out. (Heat Pump : 68 Hp)
!
Frequency
Voltage range(V)
Outdoor
Indoor
60 Hz
400 V
220 V
50 Hz
380~415 V 220~240 V
Frequency
Voltage range(V)
Outdoor
Indoor
60 Hz
400 V
220 V
50 Hz
380~415 V 220~240 V