32
ENGLISH
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
• * : Assume equivalent piping length of Y branch to be 0.5 m, that of header to be 1 m, cal-
culation purpose
• Indoor Unit should be installed at lower position than the header.
• Piping length from outdoor branch to outdoor unit
≤
10 m, equivalent length : max 13 m
(for 22HP or more)
1 Outdoor Units
Example : 5 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch (Y branch)
Ⓒ
: Y branch
Ⓓ
: Indoor Unit
Ⓔ
: Header
Ⓕ
: Sealed piping
2 Outdoor Units
Example : 5 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch
Ⓒ
: Y branch
Ⓓ
: Indoor Unit
Ⓔ
: Connection branch pipe between Outdoor
units: ARCNN21
Ⓕ
: Header
Ⓖ
: Sealed piping
L 150 m(200 m : Conditional application)
40 m(90 m : Conditional application)
L 110 m
h 40 m
Branch pipe can not be used after header
Branch pipe can not be used after header
10 m or
less
H 110 m
Master
Slave
Master
Slave
L 150 m(200 m : Conditional application)
40 m(90 m : Conditional application)
ODU Capacity
Master ≥ Slave
h 40 m
h1
Master
Slave
Combination of Y branch/header method
WARNING
Pipe length after header branching (a~f)
It is recommended that difference in length of the pipes connected to the Indoor Units is
minimized. Performance difference between Indoor Units may occur.
!