FLARING WORK AND CONNECTION OF PIPING
Connection of piping-
Indoor
Preparing the indoor unit's piping and drain
hose for installation through the wall.
Remove the plastic tubing retainer (see
illustration below) and pull the tubing and
drain hose away from chassis.
Replace the plastic tubing holder in the
original position.
C
Tape the tubing, drain hose and the connecting
cable. Be sure that the drain hose is located at
the lowest side of the bundle. Locating at the
upper side can cause drain pan to overflow
inside the unit.
NOTE:
If the drain hose is routed inside the room,
insulate the hose with an insulation material* so that
dripping from "sweating"(condensation) will not damage
furniture or floors.
*Foamed polyethylene or equivalent is recommended.
Loop
Connecting
cable
Drain hose
Gas side
piping
Liquid side
piping
Tubing holder
To remove the holder,
press the bottom of
chassis near the holder
upward and pull the tab
out of its hole.
D
Indoor unit installation
Hook the indoor unit onto the upper portion of
the installation plate.(Engage the two hooks of
the rear top of the indoor unit with the upper
edge of the installation plate.) Ensure that the
hooks are properly seated on the installation
plate by moving it left and right
A
Route the indoor tubing and the drain hose
in the direction of rear left.
Drain hose
B
Insert the connecting cable into the indoor
unit from the outdoor unit through the
piping hole.
Do not connect the cable to the indoor unit.
Make a small loop with the cable for easy
connect ion later.
For left rear piping
CAUTION
When install, make sure
that the remaining parts
must be removed clearly
so as not to damage the
piping and drain hose,
especial ly power cord
and connecting cable.
Press the lower left and right sides of the
unit against the installation plate until the
hooks engage into their slots (clicking-sound).
E
Connecting the pipings to the indoor unit and
drain hose to drain pipe.
Align the center of the pipings and sufficiently
tighten the flare nut by hand.
Indoor unit tubing
Flare nut
Pipings
Drain hose
Connecting
cable
INSTALLATION
11