–22–
Make sure that the screws of the terminal are free from looseness.
WARNING
The power cord connected to the outdoor unit should be complied
with the following specifications (Rubber insulation, type H05RN-F
approved by HAR or SAA).
The connecting cable connected to the indoor and outdoor unit should
be complied with the following specifications (Rubber insulation,
type H05RN-F approved by HAR or SAA).
CAUTION
8.5mm
20mm
GN/YL
7.5mm
20mm
GN/YL
[Air inlet side view]
If the supply cord is damaged, it must be replaced by a special cord or assembly available from the manufacturer or its service agent.
NORMAL
CROSS-SECTIONAL
AREA 0.75mm
2
(36K)
1.25mm
2
(48K, 60K)
NORMAL
CROSS-SECTIONAL
AREA 2.5mm
2
(36K)
3.5mm
2
(48K, 60K)
Terminal Block of Outdoor Unit
1(L) 2(N) 3
4
5
1(L) 2(N) 3
4
5
Terminal Block of Outdoor Unit
1(L) 2(N) 3
4
5
Terminal Block of Indoor Unit
Terminal Block of Indoor Unit
Control box cover
Indoor
power cord
Remote
controller
cord
Control box cover
fitting screw(2 units)
POWER INPUT
R
S
T
N
POWER INPUT
R
S
T
N
1(L) 2(N) 3
4
5
Terminal Block of Outdoor Unit
1(L) 2(N) 3
4
5
1(L) 2(N) 3
4
5
Terminal Block of Outdoor Unit
1(L) 2(N) 3
4
5
Terminal Block of Indoor Unit
Terminal Block of Indoor Unit
POWER INPUT
1(L)
2(N)
POWER INPUT
1(L)
2(N)
1(L) 2(N) 3
4
5
• 3 Phase
NORMAL
CROSS-SECTIONAL
AREA 4.0mm
2
(36K)
6.0mm
2
(48K)
8.0mm
2
(60K)
• 1 Phase
Heat Pump Model
Cooling Model
Heat Pump Model
• 3 Phase
• 1 Phase
Cooling Model
5. Wiring Connection
• Open the control box cover and connect the Remote controller cord and Indoor power wires.