12
INSTALLATION
ENGLISH
The Indoor Unit Installation
Set screw of
paper model (4 pieces)
Paper model
for installation
Ceiling board
150mm
Ceiling board
Ceiling
Flat washer for M10
(accessory)
Keep the length of the bolt
from the bracket to 40mm
Open the ceiling board
along the outer edge of the
paper model
Flat washer for M10
(accessory)
Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10)
Nut
(W3/8 or M10)
Spring washer
(M10)
Air Conditioner body
Keep the length of 15~18mm
between the air conditioner bottom
surface and the ceiling surface
Wall
Indoor
Outdoor
Slope gradient for
drain Should be
1/50 ~ 1/100
The following parts is option.
①
Hanging Bolt - W 3/8 or M10
②
Nut - W 3/8 or M10
③
Spring Washer - M10
④
Plate Washer - M10
Drill the piping hole on the wall slightly tilted to the outdoor side using a Ø 65 hole-core drill.
Remote Controller Installation
Although the room temperature sensor is in the indoor unit, the remote controller should be
installed in such places away from direct sunlight and high humidity.
Installation of the remote controller
- Select places that are not splashed with water.
- Select control position after receiving customer approval.
- The room temperature sensor is built in the indoor unit.
- This remote controller equipped with liquid crystal display. If this position is higher or lower, dis-
play is difficult to see.(The standard height is 1.2 ~ 1.5m high)
Routing of the remote controller cord
- Keep the remote controller cord away from the refrigerant piping and the drain piping.
- To protect the remote controller cord from electrical noise, place the cord at least 5cm away
from other power cables (audio equipment, television set, etc.)
- If the remote controller cord is secured to the wall, provide a trap at the top of the cord to pre-
vent water droplets from running.
CAUTION
Tighten the nut and bolt to prevent unit
falling.
!