6RMI0-04C
47
Inverter Single
Notes
Equivalent pipe length = actual pipe number of bends x 0.3
Additional Refrigerant Charge
Example: For model LS120HSV2 having 20m(65.6ft) pipe length, additional refrigerant to be charged is
(20m(65.6ft)-7.5m(24.6ft)) x 20g/m(0.22oz/ft) = 250g(9.02oz)
* Specially LS091HSV2 / LS121HSV2 / LA090HSV2 / LA120HSV2 / LS090HYV / LS120HYV/ LA090HVP/LA120HVP
Additional refrigerant must be charged after 12.5m(41ft) (there is no need to charge till 12.5m(41ft) based on reliability)
CAUTION:
•
Capacity is based on standard length
and maximum allowance length is on
the basis of reliability.
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
Models
Max. Pipe
Length[m(ft)]
Max.
Elevation[m(ft)]
Additional
Refrigerant[g/m(oz/ft)
AS-W093F2B2(LAN090HVP/LAU090HVP)
15(49.2)
10(32.8)
20(0.22)
AS-W123F2B2(LAN120HVP/LAU120HVP)
15(49.2)
10(32.8)
20(0.22)
AS-W093MMM9(LSN090HYV/LSU090HYV)
15(49.2)
10(32.8)
20(0.22)
AS-W123MMM9(LSN120HYV/LSU120HYV)
15(49.2)
10(32.8)
20(0.22)
AS-W093B1Y9(LSN091HSV2/LSU091HSV2)
20(65.6)
10(32.8)
20(0.22)
AS-W093BRM9(LAN090HSV2/LAU090HSV2)
20(65.6)
10(32.8)
20(0.22)
AS-W123B1Y9(LSN121HSV2/LSU121HSV2)
20(65.6)
10(32.8)
20(0.22)
AS-W123BRM9(LAN120HSV2/LAU120HSV2)
20(65.6)
10(32.8)
20(0.22)
AS-W183C2Y9(LSN181HSV2/LSU181HSV2)
30(98.4)
15(49.2)
35(0.38)
AS-W183CRM9(LAN180HSV2/LAU180HSV2)
30(98.4)
15(49.2)
35(0.38)
AS-W243DGY9(LSN240HSV2/LSU240HSV2)
30(98.4)
15(49.2)
35(0.38)
AS-W243CRM9(LAN240HSV2/LAU240HSV2)
30(98.4)
15(49.2)
35(0.38)
AS-W303DGY9(LSN307HV2/LSU307HV2)
30(98.4)
15(49.2)
35(0.38)
AS-W363DGY9(LSN360HV2/LSU360HV2)
30(98.4)
15(49.2)
35(0.38)