Single Zone Mega, Standard Efficiency, and Mega 115V
MECHANICAL SPECIFICATIONS
General
LG Single Zone Mega, Standard Efficiency,
and Mega 115V Wall Mounted systems
comprise of a single outdoor unit connected
to a single indoor unit with a single refriger-
ant circuit.
This system is a Duct-Free Split system
that can operate in either cooling or heat-
ing mode. The system shall be capable of
changing mode within a maximum time of
three (3) minutes to ensure indoor tempera-
ture can be properly maintained.
The system is manufactured in a facility reg-
istered to ISO 9001 and ISO 14001, which is
a set of standards applying to environmental
protection set by the International Orga-
nization for Standardization (ISO). Wiring
in these units are in accordance with the
National Electrical Code (NEC).
Temperature Ranges
Mega (HEV2, HFV3)
Operating ranges for outdoor unit of 14°F to
118°F (DB) for cooling; 14°F to 65°F (WB)
for heating.
Operating ranges for indoor unit of 53°F to
75°F (WB) for cooling; 60°F to 86°F (DB) for
heating.
Mega 115V (HXV2)
Operating ranges for outdoor unit of 14°F to
118°F (DB) for cooling; 14°F to 65°F (WB)
for heating.
Operating ranges for indoor unit of 53°F to
75°F (WB) for cooling; 60°F to 86°F (DB) for
heating.
Casing / Frame
Outdoor unit is constructed with pre-coated
metal (PCM).
Indoor unit is constructed of heavy duty
Acrylonitrile Butadiene Styrene (ABS) and
High Impact Polystyrene (HIPS) plastic.
Refrigerant System
The refrigeration system consists of a single
refrigeration circuit and uses R410A refriger-
ant. The outdoor unit is provided with factory
installed components, including a refrigerant
strainer, check valves, oil separator,
accumulator, four-way reversing valve, EEV,
high and low side charging ports, service
valves, and interconnecting piping.
Refrigeration Oil Control
Heat Pump outdoor units have a centrifugal
oil separator and controls to ensure suf-
ficient oil supply is maintained, and that oil
does not travel with the refrigerant.
Compressors
The outdoor unit is equipped with one
hermetic, digitally controlled, inverter driven,
twin-rotary compressor to modulate capacity
(modulation in 1 Hz increments).
Frequency ranges for the (HEV2, HFV3)
ODUs are:
9k Btu/h = 10 to 70 Hz (cooling); 10 to 92 Hz
(heating)
12k Btu/h = 10 to 74 Hz (cooling); 10 to 98
Hz (heating)
18 Btu/h = 10 to 70 Hz (cooling); 10 to 87 Hz
(heating)
24k Btu/h = 10 to 76 Hz (cooling); 10 to 95
Hz (heating)
Frequency ranges for the (HXV2) ODUs are:
9k Btu/h = 10 to 74 Hz (cooling); 10 to 98 Hz
(heating)
12k Btu/h = 10 to 74 Hz (cooling); 10 to 98
Hz (heating)
Over-current protection and vibration isola-
tion are integrated with the compressor.
Outdoor Unit Coil
Heat Pump outdoor unit coils are of a
nonferrous construction with louvered fins
on copper tubing, and are protected with an
integral coil guard. Coil fins have a factory
applied corrosion resistant GoldFin™ mate-
rial with hydrophilic coating.
Fans and Motors
The outdoor unit includes one direct drive,
variable speed propeller type fan.
The Brushless Digitally Controlled (BLDC)
fan motor has inherent protection, perma-
nently lubricated bearings, and variable
speed with a maximum speed up to 950 rpm.
Raised guards are provided to limit contact
with moving parts.
The outdoor unit has horizontal discharge
airflow.
Electrical
The HEV2 or HFV3 model unit is available
in a 208-230V 60 Hz, 1-phase power supply.
The HXV2 model unit is available in a 115V
60 Hz, 1-phase power supply. The units are
capable of operating within voltage limits of
±10% rated voltage, and include overcurrent
protection.
Air Filter
Return air inlet has a fctory-supplied primary
removable, washable filter. Filters are ac-
cessed from the front of the unit without the
use of tools.
Controls
The unit is factory wired with necessary elec-
trical control components, integral micropro-
cessors, printed circuit boards, thermistors,
sensors, terminal blocks, and lugs for power
wiring.
Microprocessor-based algorithms provide
component protection, soft-start capability,
refrigeration system pressure, temperature,
defrost, and ambient control.